NOTE: All documents linked from this page are in
PDF-format.
Interpretation 62.1-2013-1 – January 25, 2015 (Refers to the requirements presented in ANSI/ASHRAE Standard 62.1-2013, Section 6.2.2.1 and Table 6.2.2.1, regarding health care spaces.)
Interpretation 62.1-2013-2 – January 25, 2015 (Refers to the requirements presented in ANSI/ASHRAE Standard 62.1-2013, Sections 6 .1.2 and 6.3, regarding the Indoor Air Quality (IAQ) Procedure.)
Interpretation 62.1-2013-3 – January 25, 2015 (Refers to the requirements presented in ANSI/ASHRAE Standard 62.1-2013, Sections 6.3.1 thru 6.3.6, regarding the Indoor Air Quality (IAQ) Procedure.)
Interpretation 62.1-2013-4 – January 25, 2015 (Refers to the requirements presented in ANSI/ASHRAE Standard 62.1-2013, Section 6.3.4, regarding the Indoor Air Quality Procedures Design Approach: Air Cleaning.)
Interpretation 62.1-2013-5 – January 24, 2016 (Refers to the requirements presented in ANSI/ASHRAE Standard 62.1-2013, Section 6.2.5.1, regarding the determination of the zone primary airflow (Vpz) for VAV systems.)
Interpretation 62.1-2013-6 – March 16, 2017 (Refers to the requirements presented in ANSI/ASHRAE Standard 62.1-2013, Section 6.2.7.1.1, regarding DCV and the use of CO2 sensors in return air ductwork at the system level.)