Number
|
Chemical Name
|
Chemical Formula
|
| |
Methane Series
|
| 11 |
trichlorofluoromethane |
CCl 3F |
| 12 |
dichlorodifluoromethane |
CCl 2F 2 |
| 12B1 |
bromochlorodifluoromethane |
CBrClF 2 |
| 13 |
chlorotrifluoromethane |
CClF 3 |
| 13B1 |
bromotrifluoromethane |
CBrF 3 |
| 13I1 |
trifluoroiodomethane |
CF3 I |
| 14e |
tetrafluoromethane (carbon tetrafluoride) |
CF 4 |
| 21 |
dichlorofluoromethane |
CHCl 2F |
| 22 |
chlorodifluoromethane |
CHClF 2 |
| 23 |
trifluoromethane |
CHF 3 |
| 30 |
dichloromethane (methylene chloride) |
CH 2Cl 2 |
| 31 |
chlorofluoromethane |
CH 2ClF |
| 32 |
difluoromethane (methylene fluoride) |
CH 2F 2 |
| 40 |
chloromethane (methyl chloride) |
CH 3Cl |
| 41 |
fluoromethane (methyl fluoride) |
CH 3F |
| 50 |
methane |
CH 4 |
|
|
|
Number
|
Chemical Name
|
Chemical Formula
|
| |
Ethane Series
|
| 113 |
1,1,2-trichloro-1,2,2-trifluoroethane |
CCl 2FCClF 2 |
| 114 |
1,2-dichloro-1,1,2,2-tetrafluoromethane |
CClF 2CClF 2 |
| 115 |
chloropentafluoroethane |
CClF 2CF 3 |
| 116 |
hexafluoroethane |
CF 3CF 3 |
| 123 |
2,2-dichloro-1,1,1-trifluoroethane |
CHCl 2CF 3 |
| 124 |
2-chloro-1,1,1,2-tetrafluoroethane |
CHClFCF 3 |
| 125 |
pentafluoroethane |
CHF 2CF 3 |
| 134a |
1,1,1,2-tetrafluoroethane |
CH 2FCF 3 |
| 141b |
1,1-dichloro-1-fluoroethane |
CH 3CCl 2F |
| 142b |
1-chloro-1,1-difluoroethane |
CH 3CClF 2 |
| 143a |
1,1,1-trifluoroethane |
CH 3CF 3 |
| 152a |
1,1-difluoroethane |
CH 3CHF 2 |
| 170 |
ethane |
CH 3CH 3 |
|
|
|
Number
|
Chemical Name
|
Chemical Formula
|
| |
Ethers
|
| E170 |
Methoxymethane (dimethyl ether) |
CH3OCH3 |
|
|
|
Number
|
Chemical Name
|
Chemical Formula
|
| |
Propane
|
| 218 |
octafluoropropane |
CF 3CF 2CF 3 |
| 227ea |
1,1,1,2,3,3,3-heptafluoropropane |
CF 3CHFCF 3 |
| 236fa |
1,1,1,3,3,3-hexafluoropropane |
CF 3CH 2CF 3 |
| 245fa |
1,1,1,3,3-pentafluoropropane |
CHF 2CH 2CF 3 |
| 290 |
propane |
CH 3CH 2CH 3 |
|
|
|
Number
|
Chemical Name
|
Chemical Formula
|
| |
Cyclic Organic Compounds
|
| C318 |
octafluorocyclobutane |
-(CF 2) 4- |
|
|
| Miscellaneous Organic Compounds |
|
Number
|
Chemical Name
|
Chemical Formula
|
|
hydrocarbons
|
| 600 |
butane |
CH 3CH 2CH 2CH 3 A3 |
| 600a |
2-methylpropane (isobutane) |
CH(CH 3) 2CH 3 A3 |
| 601 |
pentane |
CH 3CH 2CH 2 CH 2CH 3 |
| 601a |
2-methylbutane (isopentane) |
CH(CH 3) 2 CH 2CH 3 |
| oxygen compounds |
| 610 |
ethoxyethane (ethyl ether) |
CH 3CH 2 OCH 2CH 3 |
| 611 |
methyl formate |
HCOOCH 3 |
| sulfur compounds |
| 620 |
(Reserved for future assignment) |
|
|
|
|
Number
|
Chemical Name
|
Chemical Formula
|
| |
Nitrogen Compounds
|
| 630 |
methanamine (methyl amine) |
CH 3NH 2 |
| 631 |
ethanamine (ethyl amine) |
CH 3CH 2(NH 2) |
|
|
|
Number
|
Chemical Name
|
Chemical Formula
|
| |
Inorganic Compounds
|
| 702 |
hydrogen |
H 2 |
| 704 |
helium |
He |
| 717 |
ammonia |
NH 3 |
| 718 |
water |
H 2O |
| 720 |
neon |
Ne |
| 728 |
nitrogen |
N 2 |
| 732 |
oxygen |
O 2 |
| 740 |
argon |
Ar |
| 744 |
carbon dioxide |
CO 2 |
| 744A |
nitrous oxide |
N 2O |
| 764 |
sulfur dioxide |
SO 2 |
|
|
|
Number
|
Chemical Name
|
Chemical Formula
|
| |
Unsaturated Organic Compounds
|
| 1130(E) |
trans-1,2-dichloroethene |
CHCl=CHCl |
| R-1132a |
1,1-difluoroethylene |
CF2=CH2 |
| R-1132(E) |
trans-1,2-difluoroethene |
(E)-CFH=CFH |
| 1150 |
ethene (ethylene) |
CH2=CH2 |
| R-1224yd(Z) |
(Z)-1-chloro-2,3,3,3-tetrafluoropropene |
CF3CF=CHCl |
| 1233zd(E) |
trans-1-chloro-3,3,3-trifluoro-1-propene |
CF3CH=CHCl |
| 1234yf |
2,3,3,3-tetrafluoro-1-propene |
CF3CF=CH2 |
| 1234ze(E) |
trans-1,3,3,3-tetrafluoro-1-propene |
CF3CH=CHF |
| 1270 |
propene (propylene) |
CH3CH=CH 2 |
| 1336mzz(E) |
trans-1,1,1,4,4,4-hexafluoro-2-butene |
CF3CH=CHCF3 |
| 1336mzz(Z) |
cis-1,1,1,4,4,4-hexaflouro-2-butene |
CF3CH=CHCF3 |
Refrigerant Blends
|
|
Number
|
Refrigerant Composition (Mass % )
|
| |
Zeotropes
|
| 400 |
R-12/114 (must be specified) (50.0/50.0) (60.0/40.0) |
|
| 401A |
R-22/152a/124 (53.0/13.0/34.0) |
|
| 401B |
R-22/152a/124 (61.0/11.0/28.0 |
|
| 401C |
R-22/152a/124 (33.0/15.0/52.0) |
|
| 402A |
R-125/290/22 (60.0/2.0/38.0) |
|
| 402B |
R-125/290/22 (38.0/2.0/60.0) |
|
| 403A |
R-290/22/218 (5.0/75.0/20.0) |
|
| 403B |
R-290/22/218 (5.0/56.0/39.0) |
|
| 404A |
R-125/143a/134a (44.0/52.0/4.0) |
|
| 405A |
R-22/152a/142b/C318 (45.0/7.0/5.5/42.5) |
|
| 406A |
R-22/600a/142b (55.0/4.0/41.0) |
|
| 407A |
R-32/125/134a (20.0/40.0/40.0) |
|
| 407B |
R-32/125/134a (10.0/70.0/20.0) |
|
| 407C |
R-32/125/134a (23.0/25.0/52.0) |
|
| 407D |
R-32/125/134a (15.0/15.0/70.0) |
|
| 407E |
R-32/125/134a (25.0/15.0/60.0) |
|
| 407F |
R-32/125/134a (30.0/30.0/40.0) |
|
| 407G |
R-32/125/134a (2.5/2.5/95.0) |
|
| 407H |
R-32/125/134a (32.5/15.0/52.5) |
|
| 407I |
R-32/125/134a (19.5/8.5/72.0) |
|
| 408A |
R-125/143a/22 (7.0/46.0/47.0) |
|
| 409A |
R-22/124/142b (60.0/25.0/15.0) |
|
| 409B |
R-22/124/142b (65.0/25.0/10.0) |
|
| 410A |
R-32/125 (50.0/50.0) |
|
| 410B |
R-32/125 (45.0/55.0) |
|
| 411A |
R-1270/22/152a) (1.5/87.5/11.0) |
|
| 411B |
R-1270/22/152a (3.0/94.0/3.0) |
|
| 412A |
R-22/218/143b (70.0/5.0/25.0 k |
|
| 413A |
R-218/134a/600a (9.0/88.0/3.0) |
|
| 414A |
R-22/124/600a/142b (51.0/28.5/4.0/16.5) |
|
| 414B |
R-22/124/600a/142b (50.0/39.0/1.5/9.5) |
|
| 415A |
R-22/152a (82.0/18.0) |
|
| 415B |
R-22/152a (25.0/75.0) |
|
| 416A |
R-134a/124/600 (59.0/39.5/1.5) |
|
| 417A |
R-125/134a/600 (46.6/50.0/3.4) |
|
| 417B |
R-125/134a/600 (79.0/18.3/2.7) |
|
| 417C |
R-125/134a/600 (19.5/78.8/1.7) |
|
| 418A |
R-290/22/152a (1.5/96.0/2.5) |
|
| 419A |
R-125/134a/E170 (77.0/19.0/4.0) |
|
| 419B |
R-125/134a/E170 (48.5/48.0/3.5) |
|
| 420A |
R-134a/142b (88.0/12.0) |
|
| 421A |
R-125/134a (58.0/42.0) |
|
| 421B |
R-125/134a (85.0/15.0) |
|
| 422A |
R-125/134a/600a (85.1/11.5/3.4) |
|
| 422B |
R-125/134a/600a (55.0/42.0/3.0) |
|
| 422C |
R-125/134a/600a (82.0/15.0/3.0) |
|
| 422D |
R-125/134a/600a (65.1/31.5/3.4) |
|
| 422E |
R-125/134a/600a (58.0/39.3/2.7) |
|
| 423A |
134a/227ea (52.5/47.5) |
|
| 424A |
R-125/134a/600a/600/601a (50.5/47.0/0.9/1.0/0.6) |
|
| 425A |
R-32/134a/227ea (18.5/69.5/12) |
|
| 426A |
R-125/134a/600/601a (5.1/93.0/1.3/0.6) |
|
| 427A |
R-32/125/143a/134a (15.0/25.0/10.0/50.0) |
|
| 427C |
R-32/125/143a/134a (25.0/25.0/10.0/40.0) |
|
| 428A |
R-125/143a/290/600a (77.5/20.0/0.6/1.9) |
|
| 429A |
R-E170/152a/600a (60.0/10.0/30.0) |
|
| 430A |
R-152a/600a (76.0/24.0) |
|
| 431A |
R-290/152a (71.0/29.0) |
|
| 432A |
R-1270/E170 (80.0/20.0) |
|
| 433A |
R-1270/290 (30.0/70.0) |
|
| 433B |
R-1270/290 (5.0/95.0) |
|
| 433C |
R-1270/290 (25.0/75.0) |
|
| 434A |
R-125/143a/134a/600a (63.2/18.0/16.0/2.8) |
|
| 435A |
R-E170/152a (80.0/20.0) |
|
| 436A |
R-290/600a (56.0/44.0) |
|
| 436B |
R-290/600a (52.0/48.0) |
|
| 436C |
R-290/600a (95.0/5.0) |
|
| 437A |
R-125/134a/600/601 (19.5/78.5/1.4/0.6) |
|
| 438A |
R-32/125/134a/600/601a (8.5/45.0/44.2/1.7/0.6) |
|
| 439A |
R-32/125/600a (50.0/47.0/3.0) |
|
| 440A |
R-290/134a/152a (0.6/1.6/97.8) |
|
| 441A |
R-170/290/600a/600 (3.1/54.8/6.0/36.1) |
|
| 442A |
R-32/125/134a/152a/227ea (31.0/31.0/30.0/3.0/5.0) |
|
| 443A |
R-1270/290/600a (55.0/40.0/5.0) |
|
| 444A |
R-32/152a/1234ze(E) (12.0/5.0/83.0) |
|
| 444B |
R-32/152a/1234ze(E) (41.5/10.0/48.5) |
|
| 445A |
R-744/134a/1234ze(E) (6.0/9.0/85.0) |
|
| 446A |
R-32/1234ze(E)/600 (68.0/29.0/3.0) |
|
| 447A |
R-32/125/1234ze(E) (68.0/3.5/28.5) |
|
| 447B |
R-32/125/1234ze (E) (68.0/8.0/24.0) |
|
| 448A |
R-32/125/1234yf/134a/1234ze(E) (26.0/26.0/20.0/21.0/7.0) |
|
| 448B |
R-32/125/1234yf/134a/1234ze(E) (21.0/21.0/20.0/31.0/7.0) |
|
| 449A |
R-32 /125 /1234yf /134a (24.3/24.7/25.3/25.7) |
|
| 449B |
R-32/125/1234yf/134a (25.2/24.3/23.2/27.3) |
|
| 449C |
R-32/125/1234yf/134a (20.0/20.0/31.0/29.0) |
|
| 450A |
R-134a/1234ze(E) (42.0/58.0) |
|
| 451A |
R-1234yf/134a (89.8/10.2) |
|
| 451B |
R-1234yf/134a (88.8/11.2) |
|
| 452A |
R-32/125/1234yf (11.0/59.0/30.0) |
|
| 452B |
R-32/125/1234yf (67.0/7.0/26.0) |
|
| 452C |
R-32/125/1234yf (12.5/61.0/26.5) |
|
| 453A |
R-32/125/134a/227ea/600/601a (20.0/20.0/53.8/5.0/0.6/0.6) |
|
| 454A |
R-32/1234yf (35.0/65.0) |
|
| 454B |
R-32/1234yf (68.9/31.1) |
|
| 454C |
R-32/1234yf (21.5/78.5) |
|
| 455A |
R-744/32/1234yf (3.0/21.5/75.5) |
|
| 456A |
R-32/134a/1234ze(E) (6.0/45.0/49.0) |
|
| 457A |
R-32/1234yf/152a (18.0/70.0/12.0) |
|
| 457B |
R-32/1234yf/152a (35.0/55.0/10.0) |
|
| 457C |
R-32/1234yf/152a (7.5/78.0/14.5) |
|
| 458A |
R-32/125/134a/227ea/236fa (20.5/4.0/61.4/13.5/0.6) |
|
| 459A |
R-32/1234yf/1234ze(E) (68.0/26.0/6.0) |
|
| 459B |
LTR 11: R-32/1234yf/1234ze(E) (21.0/69.0/10.0) |
|
| 460A |
LTR 10: R-32/125/134a/1234ze(E) (12.0/52.0/14.0/22.0) |
|
| 460B |
LTR4X10: R-32/125/134a/1234ze(E) (28.0/25.0/20.0/27.0) |
|
| 460C |
R-32/125/134a/1234ze(E) (2.5/2.5/46.0/49.0) |
|
| 461A |
R-125/143a/134a/227ea/600a (55.0/5.0/32.0/5.0/3.0) |
|
| 462A |
R-32/125/143a/134a/600 (9.0/42.0/2.0/44.0/3.0) |
|
| 463A |
R-744/32/125/1234yf/134a (6.0/36.0/30.0/14.0/14.0) |
|
| 464A |
R-32/125/1234ze(E)/227ea (27.0/27.0/40.0/6.0) |
|
| 465A |
R-32/290/1234yf (21.0/7.9/71.1) |
|
| 466A |
R-32/125/131I (49.0/11.5/39.5) |
|
| 467A |
R-32/125/134a/600a (22.0/5.0/72.4/0.6) |
|
| 468A |
R-1132a/32/1234yf (3.5/21.5/75.0) |
|
| 468B |
R-1132a/32/1234yf (6.0/13.0/81.0) |
|
| 468C |
R-1132a/32/1234yf (6.0/42.0/52.0) |
|
| 469A |
R-744/32/125 (35.0/32.5/32.5) |
|
| 470A |
R-744/32/125/134a/1234ze(E)/227ea (10.0/17.0/19.0/7.0/44.0/3.0) |
|
| 470B |
R-744/32/125/134a/1234ze(E)/227ea (10.0/11.5/11.5/3.0/57.0/7.0) |
|
| 471A |
R-1234ze(E)/227ea/1336mzz(E) (78.7/4.3/17.0) |
|
| 472A |
R-744/32/134a (69.0/12.0/19.0) |
|
| 472B |
R-744/32/134a (58.0/10.0/32.0) |
|
| 473A |
R-1132a/23/744/125 (20.0/10.0/60.0/10.0) |
|
| 474A |
R-1132(E)/1234yf (23.0/77.0) |
|
| 475A |
R-1234yf/134a/1234ze(E) (45.0/43.0/12.0) |
|
| 476A |
R-134a/1234ze(E)/1336mzz(E) (10.0/78.0/12.0) |
|
|
|
|
Refrigerant Composition (Mass % )
|
|
Number
|
Azeotropes
|
| 500 |
R-12/152a (73.8/26.2) |
|
| 501 |
R-22/12 (75.0/25.0) |
|
| 502 |
R-22/115 (48.8/51.2) |
|
| 503 |
R-23/13 (40.1/59.9) |
|
| 504 |
R-32/115 (48.2/51.8) |
|
| 505 |
R-12/31 (78.0/22.0) |
|
| 506 |
R-31/114 (55.1/44.9) |
|
| 507A |
R-125/143a (50.0/50.0) |
|
| 508A |
R-23/116 (39.0/61.0) |
|
| 508B |
R-23/116 (46.0/54.0) |
|
| 509A |
R-22/218 (44.0/56.0) |
|
| 510A |
R-E170/600a (88.0/12.0) |
|
| 511A |
R-290/E170 (95.0/5.0) |
|
| 512A |
R-134a/152a (5.0/95.0) |
|
| 513A |
R-1234yf/134a (56.0/44.0) |
|
| 513B |
R-1234yf/134a (58.5/41.5) |
|
| 514A |
R-1336mzz(Z)/1130(E) (74.7/25.3) |
|
| 515A |
R-1234ze (E)/227ea (88.0/12.0) |
|
| 515B |
R-1234ze(E)/227ea (91.1/8.9) |
|
| 516A |
R-1234yf/134a/152a (77.5/8.5/14.0) |
|