Artificial intelligence (AI) policy: ASHRAE prohibits the entry of content from any ASHRAE publication or related ASHRAE intellectual property (IP) into any AI tool, including but not limited to ChatGPT. Additionally, creating derivative works of ASHRAE IP using AI is also prohibited without express written permission from ASHRAE. For the full AI policy, click here. 

Close
logoShaping Tomorrow’s Global Built Environment Today

Grid-Interactive Design (Demand Flexibility)

AI Data Center Energy Performance Framework

Share This

 Back to AI Data Center Energy Performance Framework

Grid-Interactive Design (Deman Flexibility)   

 Impact

A grid-interactive design transforms data center speed to power and operations using real-time communication and coordination with the local and/or regional electrical grid to optimize energy consumption while enabling active grid support and maintaining its availability and resiliency. In addition to managing when and how much power is consumed, grid‑interactive data centers can provide services such as fast load response, energy export, and other forms of flexibility that support grid stability. Since AI training can have very large millisecond level load variations that can jeopardize grid stability, this technique provides a meaningful strategy to mitigate these risks.

These capabilities are enabled by advanced, bidirectional power conversion architectures (e.g., solid‑state transformers [SSTs] and bidirectional converters) that allow data centers to transition from being passive grid loads to controllable, responsive grid assets. The grid-interactive approach is critical as AI-driven workloads are dramatically increasing power and cooling demands, thereby challenging sustainability and cost-efficiency goals.

Author Acknowledgements

Back to top


Highlights

Below are the main strategies for enabling grid-interactive data center design, considering energy consumption, availability, resiliency, sustainability, and cost efficiency.

  1. Design for Grid Coordination. Ensure the data center can dynamically interact with the electrical grid to optimize energy use and help with grid stability while also providing verifiable grid support services, such as fast load response, reserve capacity, or controlled export from on‑site resources when technically and contractually enabled and lower emissions when possible.

  2. Prioritize Renewable Integration and Storage. Incorporate on-site and off-site renewables and intelligent energy storage to reduce operating costs. This strategy can also reduce the emissions footprint.

  3. Build Resiliency into Microgrids. Enable separation and automated failover or automatic transfer to maintain uptime during grid disruptions. DC‑based microgrids further enhance grid interactivity by avoiding mode transitions between grid-following and grid-forming operation. The interlinking converter to the grid becomes one of multiple coordinated sources alongside energy storage and on‑site generation.

  4. Consider Emissions–Aware Computing. Use source power analytics to schedule workloads and manage resources as efficiently as possible.

  5. Differentiate Grid Support from Demand Response. Grid‑interactive designs should distinguish between:
    • Grid support from inverter-based resources (IBRs) enabled by bidirectional power converters and governed by interconnection standards such as IEEE 1547 and associated protocols (e.g., IEEE 2030.5, DNP3, SunSpec Modbus); and
    • Demand response and load flexibility, which primarily modulate consumption and are typically coordinated using protocols such as OpenADR.

      While voltage and frequency ride‑through requirements for IBRs are defined in IEEE 1547 and can be satisfied without communications, evolving ride‑through expectations for large loads and data centers are increasingly part of broader grid resiliency considerations.

Back to top


Discussion

A grid-interactive design enables a data center to actively communicate and coordinate with the electrical grid. The need for grid-interactive design is driven by the rapid growth of very large AI workloads that significantly increase power and cooling demands. Traditional data center designs focus on reliability and performance but overlook energy optimization and greenhouse gas emissions. As energy costs rise and sustainability targets become more stringent, data centers must evolve from passive energy consumers to active participants in managing the electricity usage from the electrical grid.

Key capabilities enabled by grid-interactive design include the ability to participate in demand response (DR) programs, use on-site or off-site renewable energy sources, and intelligently manage workloads based on real-time grid conditions. These capabilities not only reduce operational costs but also reduce emissions and enhance resiliency through microgrids and other automated failover and transfer strategies. By aligning with interoperability standards that use secure communications, grid-interactive data centers can deliver both economic and environmental benefits.

In addition to planning for grid interactivity in the data center design phase, there are also important considerations in the operational phase that enable grid interactivity. The growth of artificial intelligence has rapidly increased the energy demand from data centers. To meet this electricity demand, significant investment and time are needed for expanding generation and modernizing distribution and transmission networks. Incorporating demand flexibility – such as flexible interconnection agreements - into energy planning can help accelerate “speed to power” by enabling faster access to available capacity.  In the short term, as these updates are being made, many utilities may experience transmission and distribution constraints and occasional supply–demand imbalances.

Modern data centers, run by tech companies, are now recognized not just as energy consumers but also as potential contributors to grid flexibility. Demand flexibility refers to altering electricity use based on external signals like dynamic pricing or grid requests. In practice, this flexibility is partial and situational (e.g., only a fraction of data center load may be adjustable, only at certain times, and only when operational constraints, reliability requirements, and service‑level agreements allow). For data centers, this means adjusting power usage without majorly affecting service levels or grid stability. For data centers to provide demand flexibility, there need to be incentives both for data center users to participate and for data centers to utilize flexibility for grid resilience.

 A data center’s energy efficiency can significantly address the transmission and distribution constraints. Therefore, data centers should reduce electricity use through advanced cooling, hardware upgrades (resulting in consolidation and decommissioning), software design, and better data management. Other buildings in the distribution network can ease system constraints by improving building envelopes and installing energy-efficient devices, though building owners will need incentives for such upgrades.

Beyond energy efficiency, data centers can provide demand optimization through active or passive strategies. While technology maturity is improving rapidly, not all existing data centers are architected to safely expose load flexibility to the grid, and broader adoption will require continued progress in integration, controls, and operating practices, as well as clarification of liability and accountability. Active on-site generation strategies involve creating a micro-grid with local generation options like:

  1. On-site renewables with electricity storage. Designers can choose co-located renewables paired with a battery energy storage system (BESS) to smooth output. Operators can align compute with on-site generation windows.
  2. Combined heating, cooling, and power generation. Future designs may further increase flexibility by enabling reuse of waste heat for adjacent buildings, district heating, or industrial processes, by improving low-heat high performance computing, and by reducing or eliminating mechanical chilling as IT hardware evolves to support higher inlet coolant temperatures.
  3. Fossil-fuel generators. Even a generator that runs on low-carbon fuels and emissions controls is best for the data center long term.

While on-site generation can support the grid under coordinated conditions, islanding during grid stress is often necessary to maintain data center reliability, comply with interconnection requirements, and avoid worsening grid instability. It is important to distinguish between traditional backup power systems, where energy storage is used only during utility outages, and micro-grid designs that operate storage and generation continuously and can participate in grid‑interactive services during normal conditions. In addition, DC microgrid architectures can simplify grid‑interactive operation by avoiding transitions between grid‑following and grid‑forming modes and by reducing conversion losses associated with repeated AC–DC energy transfers.

A data center’s demand flexibility depends on factors like utilization rate, power consumption variability of jobs, and the job flexibility for the smart scheduler. This flexibility can be spatial (geographical) or temporal (time-based):

  1. Spatial demand flexibility. Many data centers have distributed infrastructure across regions or even countries. This allows them to move compute workloads to regions with surplus power or lower congestion, using price-aware schedulers and service level agreements that allow deferral/migration.
  2. Temporal load shifting refers to optimizing compute workloads based on time of day. There are several passive demand flexibility options to help mitigate supply–demand imbalances:
    1. Regulation/reserve services. These services provide two forms of grid support: (1) frequency regulation is a continuous (24/7), fast-acting service that responds in seconds, and (2) operating reserves that are typically dispatched for contingency events and respond over seconds to minutes. Grid-interactive uninterruptible power supplies (UPSs) and grid-scale batteries can be used to provide these services.
    2. Energy arbitrage. Unlike regulation/reserve services, which respond to small events, energy arbitrage routinely shifts energy over time or space. Grid-interactive UPSs and grid-scale batteries charge during surplus and discharge during peak demand. These services are less profitable but more frequent and do not need advance contracts. Arbitrage helps solve congestion and optimize low-cost generation. Participation in energy arbitrage is subject to utility, market, and regulatory constraints that may limit power import, export, or simultaneous charge and discharge in some jurisdictions.
    3. Load-based energy shifting and demand response. From a grid services perspective, both load-based flexibility (e.g., intelligent workload scheduling, cooling optimization) and storage-based flexibility (e.g., batteries) provide similar capabilities. The distinction is therefore not the type of service provided, but the mechanism used to deliver it (load variation versus stored energy). In this context, data centers can deliver energy shifting and demand response services through controlled adjustment of compute workloads, cooling systems (e.g., pre-cooling, thermal storage), and other flexible loads.
    4. Cooling systems. Data centers expend 20-40% of their energy on cooling (Shehabi et al., 2024). While many smaller data centers use air cooling, most hyperscale centers use liquid cooling. Strategies to reduce cooling loads include pre-cooling and use of thermal inertia by lowering temperatures ahead of scarcity events, then riding with reduced chiller load. Additionally, data centers can leverage free cooling when available. Free cooling uses favorable ambient conditions to reduce or eliminate mechanical chilling during certain periods and may be combined with pre‑cooling to shift active cooling away from peak or constrained times. Operators can also modestly raise the supply air (liquid cooling) setpoint, which can save energy directly and indirectly decrease humidification needs. Another option includes controlling auxiliary cooling equipment such as optimizing pump/fan speeds via variable frequency drives (VFDs). Using active thermal energy storage such as chilled water or ice storage can shift cooling electricity usage away from peaks or congested periods. Other important considerations are (1) water scarcity and cooling strategy compatibility, (2) local water regulations and community sensitivity, and (3) tradeoffs between water‑based vs dry cooling at a site level.
  3. Market participation and signals. Not all data center sites are suitable for full grid-interactive operation due to regulatory, market, utility, or reliability constraints, and applicability will vary by location. Some of these considerations influence site selection and interconnection strategy.  Where feasible, data centers can enroll in capacity, day-ahead, and real-time programs with verifiable baselines, based on historical operating data and metering as well as telemetry. These data centers may provide ancillary services including frequency regulation, fast frequency response, and possibly voltage support with appropriate inverters. They may engage in local flexibility markets to relieve feeder/transformer overload constraints in congested nodes. Today’s AI data centers using alternating current most often interface with the grid through rectifier and inverter UPSs rather than direct inverter infeed. Emerging architectures using bidirectional converters, SSTs, and DC distribution can reduce conversion losses and enable more direct and responsive grid support.
  4. Incentivizing flexibility. To minimize service disruption and user dissatisfaction due to the temporal movement of workloads, schedulers will require detailed information about the requirements and urgency of user workloads. While current job schedulers offer some flexibility in terms of variable job sizes, runtime durations, and compute hardware selection, data centers do not sufficiently incentivize data center owners/operators to utilize these advanced scheduling features. To enhance demand flexibility in data centers, dynamic prices should be offered to data center customers or tenants. For example, data center owners/operators can specify the price they are willing to pay for jobs on different hardware or node configurations. Similarly, data centers can dynamically offer discounts for running jobs with grid‑optimized characteristics, such as tolerance for delay, throttling, or execution during off‑peak or low‑congestion periods. This approach encourages a market-like dynamic where users request reasonable discounts and data centers honor these requests.
    However, only using the price of electricity as the incentive to the data center owners is unlikely to make much difference because the cost of energy is a small fraction of the total cost of operating the center and hyperscalers seem to currently be willing to pay whatever is needed to get computing power online. Other incentive options that may appeal to decisionmakers include reduced interconnection costs or prioritized access to service connections in exchange for a contractual commitment to participate in a defined number of demand‑reduction or grid‑support events.

By combining grid-interactive storage, flexible workload orchestration, and intelligent cooling and auxiliary controls, hyperscale data centers can deliver fast, verifiable demand flexibility that mitigates supply–demand imbalances while preserving uptime—and can monetize this flexibility through market participation or faster interconnection.

Back to top


Recommended Practices

  • 1. Implement bidirectional energy flow.

    Enable data centers to consume energy from the grid and supply energy back to the grid (e.g., from on-site renewables, battery energy storage systems). Reference IEEE 2030.5 for interoperability. When implemented using advanced bidirectional power electronics architectures (e.g., bidirectional converters and solid-state transformers), these interfaces enable active grid support services such as fast load response, reserve capacity, and controlled export from on‑site resources in addition to energy management.

  • 2. Integrate with renewable energy.

    Design the data center to use renewables (e.g., solar, wind, geothermal, hydroelectric) on-site or nearby to supplement electrical grid energy. Reference ANSI/ASHRAE Standard 90.4 for renewable credits.

  • 3. Deploy energy storage systems

    Use algorithms for batteries or other storage systems to charge during electrical grid low-demand periods (and at times of high renewable energy production) and discharge during times of peak demand or on-site fossil fuel–powered generation. Energy suppliers and/or regional authorities (such as state public service commissions) define the dynamic pricing and operational protocols that battery systems can use to interact with the grid.

  • 4. Enable resiliency and reliability

    Incorporate microgrid designs that can separate from the grid during outages and operate independently for a specific time period. Reference IEEE 1547 for interconnection standards.

  • 5. Incorporate grid-interactive and demand-responsive systems and/or designs.

    Implement workload orchestration that can be scheduled or throttled based on electrical grid conditions (e.g., job sorting, shift non-critical tasks to off-peak hours). Non-ITE strategies include thermal energy storage, resetting cooling and water heating thermostats, lighting dimming controls, and reducing or shifting other non-critical loads. Integration with predictive analytics to forecast energy demand and real-time electrical grid conditions can enable successful grid-interactive systems.

  • 6.Operate greenhouse gas emissions–aware computing.

    Shift non-critical workloads to times or days and/or locations when or where the grid is cleaner to reduce greenhouse gas emissions.

Back to top


Where to Learn More

Abera, S., Balakrishnan, M., & Kumar, A. Performance–Energy Trade‑off in CMPs with Per‑Core DVFS., Springer LNCS, 2018.

Shehabi et al., 2024 United States Data Center Energy Usage Report, LBNL, December 2024.

Referenced standards

IEEE 2030.5 (https://standards.ieee.org/ieee/2030.5/11216) enables communication and interoperability between smart grid devices and the utility grid.

IEEE 1547 (https://standards.ieee.org/ieee/1547/5915) covers interconnection and interoperability of distributed energy resources (DERs).

ANSI/ASHRAE Standard 90.4-2025, Energy Standard for Data Centers.

Other relevant standards

OpenADR (https://www.openadr.org) provides a framework for communication between utilities and customer facilities to manage energy use during peak periods.

CTA-2045 (https://shop.cta.tech/products/cta-2045) is primarily used with residential appliances, but the concept of standardized communication for energy management aligns with grid-interactive principles.

FERC Order 2222 (https://ferc2222.org) allows distributed energy resources to join and compete in wholesale electricity markets.

Back to top


Case Studies

Vulcan Test Platform: Demonstrating the Data Center as a Flexible Grid Asset (https://research-hub.nlr.gov/en/publications/vulcan-test-platform-demonstrating-the-data-center-as-a-flexible-/)

Back to top

Close