Artificial intelligence (AI) policy: ASHRAE prohibits the entry of content from any ASHRAE publication or related ASHRAE intellectual property (IP) into any AI tool, including but not limited to ChatGPT. Additionally, creating derivative works of ASHRAE IP using AI is also prohibited without express written permission from ASHRAE. For the full AI policy, click here. 

Close
logoShaping Tomorrow’s Global Built Environment Today

Titles, Purposes, and Scopes

Share This

III. Titles, Purposes, and Scopes

Withdrawn and Discontinued Projects

Guidelines
Guideline 0-2019 (SSPC 300)
Guideline 0.2-2015 (SSPC 300)
Guideline 0.3P (SSPC 300)
Guideline 1.1-2025 (SSPC 300)
Guideline 1.2-2019 (SSPC 300)
Guideline 1.3-2018 (SSPC 300)
Guideline 1.4-2019(SSPC 300)
Guideline 1.5-2025 (SSPC 300)
Guideline 1.6P (SSPC 300)
Guideline 1.7P (SSPC300)
Guideline 4-2019 (GPC 4)
Guideline 6-2015
Guideline 10 (SGPC 10)
Guideline 11-2021 (GPC 11)
Guideline 12-2023 (SSPC 400)
Guideline 13-2024 (SGPC 13)
Guideline 14-2023 (SGPC 14)
Guideline 16-2025
Guideline 20-2010 (RA2016)
Guideline 21-2022
Guideline 22-2025
Guideline 23-2016 (GPC 23)
Guideline 27-2019 (GPC 27)
Guideline 28-2021 (SSPC 161)
Guideline 29-2019
Guideline 32-2018 (GPC 32)
Guideline 33-2021
Guideline 34-2019
Guideline 35P (GPC 35)
Guideline 36 (SGPC 36)
Guideline 37P (GPC 37)
Guideline 38-2023
Guideline 39-2024
Guideline 40-2017 (GPC 40)
Guideline 41 (SGPC 41)
Guideline 42-2023 (SSPC 62.1)
Guideline 43-2025 (SSPC 170)
Guideline 44 (SGPC 44)
Guideline 45P (GPC 45P)
Guideline 47P (GPC 47)
Guideline 48P (SSPC 161)
Guideline 49P (GPC 49)
Guideline 50P (GPC 50)

Standards
Standard 15-2024 (SSPC 15)
Standard 15.2-2024 (SSPC 15)
Standard 16-2016 (SPC 16)
Standard 17-2022
Standard 20-2019 (SPC 20)
Standard 22-2023
Standard 23-2022
Standard 24-2025

Standards (cont.)
Standard 25-2018 (SPC 25)
Standard 26-2010 (RA2020) (SPC 26)
Standard 28-1996 (RA 2020) (SPC 28)
Standard 29-2024
Standard 30-2025 (SSPC 30)
Standard 32.1-2022
Standard 32.2-2018 (RA 2022)
Standard 33-2016 (RA 2026) (SPC 33)
Standard 34-2024 (SSPC 34)
Standard 35-2014 (RA 2024) (SPC 35)
Standard 37-2024
Standard 40-2025
Standard 41.1-2024 (SSPC 41)
Standard 41.2-2026 (SSPC 41)
Standard 41.3-2025 (SSPC 41)
Standard 41.4-2015 (RA 2025) (SSPC 41)
Standard 41.6-2025 (SSPC 41)
Standard 41.7-2025 (SSPC 41)
Standard 41.8-2023 (SSPC 41)
Standard 41.9-2025 (SSPC 41)
Standard 41.10-2024 (SSPC 41)
Standard 41.11-2023 (SSPC 41)
Standard 41.13-2023 (RA 2026) (SSPC 41)
Standard 51-2025 (AMCA 210-25)
Standard 52.2-2025 (SSPC 52.2)
Standard 55-2023 (SSPC 55)
Standard 62.1-2025 (SSPC 62.1)
Standard 62.2-2025 (SSPC 62.2)
Standard 63.2-2024
Standard 64-2020 (SPC 64)
Standard 70-2023
Standard 72-2022 (SSPC 72)
Standard 78-1985 (RA 2017)
Standard 79-2024
Standard 84-2020
Standard 86-2013 (RA 2016) (SPC 86)
Standard 90.1-2025 (SSPC 90.1)
Standard 90.1MR-P (SPC 90.1)
Standard 90.2-2024 (SSPC 90.2)
Standard 90.4-2025 (SSPC 90.4)
Standard 97-2007 (RA 2017) (SPC 97)
Standard 100-2024 (SSPC 100)
Standard 103-2022
Standard 105-2021
Standard 110-2016 (RA 2025) (SPC 110)
Standard 111-2024
Standard 113-2022 (SPC 113)
Standard 116-2010
Standard 118.1-2022
Standard 118.2-2022
Standard 120-2022

Standards (cont.)
Standard 124-2007 (RA 2026) (SPC 124)
Standard 125-2020
Standard 126-2020 (SPC 126)
Standard 127-2020 (SSPC 127)
Standard 128-2026
Standard 129-1997 (RA 2022) (SPC 129)
Standard 130-2025
Standard 133-2024
Standard 135-2024 (SSPC 135)
Standard 135.1-2025 (SSPC 135)
Standard 138-2021
Standard 139-2025
Standard 140-2023 (SSPC 140)
Standard 143-2024
Standard 145.1-2024 (SSPC 145)
Standard 145.2-2025 (SSPC 145)
Standard 145.4P (SSPC 145)
Standard 146-2020
Standard 147-2019 (SSPC 147)
Standard 150-2025
Standard 153-2021 (SPC 153)
Standard 154-2022 (SSPC 154)
Standard 155-2024
Standard 158.1-2024
Standard 158.2-2024
Standard 160-2021 (SSPC 160)
Standard 161-2023 (SSPC 161)
Standard 164.1-2025 (SSPC 164)
Standard 164.2-2012 (RA 2026) (SSPC 164)
Standard 164.3-2015 (SSPC 164)
Standard 164.4-2021 (SSPC 164)
Standard 169-2025 (SSPC 169)
Standard 170-2025 (SSPC 170)
Standard 171-2017 (SPC 171)
Standard 172-2024 (SPC 172)
Standard 173-2012 (RA 2026)
Standard 174-2022
Standard 180-2018 (SPC 180)
Standard 181-2023
Standard 182-2020 (SPC 182)
Standard 183-2024
Standard 184-2020 (SPC 184)
Standard 185.1-2020 (SSPC 185)
Standard 185.2-2020 (SSPC 185)
Standard 185.3-2024 (SSPC 185)
Standard 185.4-2024 (SSPC 185)
Standard 188-2021 (SSPC 400)
Standard 189.1-2023 (SSPC 189.1)
Standard 189.3-2025 (SSPC 189.3)
Standard 190-2020

Standards (cont.)
Standard 191P (SPC 191)
Standard 193-2010 (RA 2024) (SPC 193)
Standard 194-2025
Standard 195 (SPC 195)
Standard 196P (SPC 196)
Standard 198-2013 (SPC 198)
Standard 199-2016 (RA 2026)
Standard 200-2024
Standard 201-2016 (RA2026)
Standard 202-2024 (SSPC 300)
Standard 203-2018 (RA 2025)
Standard 204-2020 (SPC 204)
Standard 205-2023 (SSPC 205)
Standard 206-2024
Standard 207-2025
Standard 209-2024 (SSPC 209)
Standard 210P (SPC 210)
Standard 211-2018 (RA 2023) (SSPC 211)
Standard 212-2019 (SPC 212)
Standard 213P (SPC 213)
Standard 214-2017 (RA 2023)
Standard 215-2018 (RA 2021)
Standard 216-2020
Standard 217-2020 (SPC 217)
Standard 218-2026
Standard 219-2021 (SPC 219)
Standard 220P (SPC 220)
Standard 221-2020 (SSPC 221)
Standard 222-2025
Standard 223P (SSPC 135)
Standard 224 –2023 (SSPC 224)
Standard 225 -2020 (RA 2025)
Standard 227P (SPC 227)
Standard 228-2023 (SSPC 228)
Standard 229P (SPC 229)
Standard 230-2022 (SSPC 300)
Standard 231-2026 (SSPC 231)
Standard 232-2024 (SSPC 232)
Standard 233P (SPC 233)
Standard 234P
Standard 235P (SPC 235)
Standard 236P (SPC 236)
Standard 240P (SPC 240)
Standard 241-2023 (SSPC 241)
Standard 242P (SPC 242)
Standard 243P (SPC 243)
Standard 244P (SPC 244)
Standard 245P (SPC 245) 
Standard 514-2023 (SSPC 400)


ASHRAE Guideline 0-2019 – Published guideline. (Supersedes ASHRAE Guideline 0-2013)
The Commissioning Process

1. Purpose

1.1 
The purpose of this guideline is to describe a Commissioning Process (Cx) capable of verifying that the facility and its systems meet the Owner’s Project Requirements (OPR).

2. Scope

2.1 
The procedures, methods, and documentation requirements in this guideline describe each phase of the project delivery and the associated Commissioning Processes from predesign through occupancy and operation, without regard to specific elements, assemblies, or systems.

2.2 This guideline provides the following:

  1. Overview of the Commissioning Process Activities
  2. Description of the Commissioning Processes for each project phase
  3. Requirements for acceptance during each phase
  4. Requirements for documentation during each phase
  5. Requirements for training of operations and maintenance (O&M) personnel

ASHRAE Guideline 0-2019 – Guideline 0 on continuous maintenance. SSPC 300 to be cognizant project committee for maintenance of Guideline 0 (approved June 2016). Revised TPS approved February 1, 2020.
The Commissioning Process for New Buildings and New Systems

1. Purpose

1.1
This Guideline recommends measures that exceed minimum requirements contained in ASHRAE Standard 202. This guideline describes a Commissioning Process (Cx) for verifying that the building and its systems meet the Owner’s Project Requirements (OPR).

2. Scope

2.1
The procedures, methods, and documentation requirements in this guideline describe each phase of the project delivery and the associated Commissioning Processes and scope from predesign through warranty expiration for commissioned systems for new buildings, major renovations, and additions to existing buildings.

2.2 This guideline provides the following:

  1. Overview of Commissioning Process Activities
  2. Description of the Commissioning Processes for each project phase
  3. Requirements for acceptance during each phase
  4. Requirements for documentation during each phase
  5. Requirements for training of operations and maintenance (O&M) personnel
  6. Requirements for initial establishment of ongoing Commissioning Process

ASHRAE Guideline 0.2-2015 Published Guideline.
The Commissioning Process for Existing Systems and Assemblies

1. Purpose

1.1
The purpose of this guideline is to describe the procedures, methods, documentation, requirements, and physical activities of the Commissioning (Cx) Process for existing buildings, systems, and assemblies using the principles developed in ASHRAE Guideline 0, The Commissioning Process.

2. Scope

2.1
This guideline applies to existing buildings, systems, and assemblies.


Guideline 0.2-2015R – Revision project authorized March 2018 by SSPC 300 with same TPS. SSPC 300 to be cognizant project committee for revision and maintenance of Guideline 0.2 (approved June 2016). Revised Guideline to be placed on continuous maintenance upon publication of the revised edition (approved June 2019).
Commissioning Process for Existing Systems and Assemblies


ASHRAE Guideline 0.3P Proposed Guideline, approved May 2021. SSPC 300 to develop Guideline 0.3P
Ongoing Commissioning Process for Buildings, Systems and Assemblies

1. Purpose

1.1
The purpose of this guideline is to describe an Ongoing Commissioning Process (OCx) for existing buildings, systems, and assemblies that have completed the new building or existing building commissioning process using the principles developed in ASHRAE Standards and Guidelines.  This OCx process is intended to maintain and improve the facility operations performance achieved by the previous commissioning and continue to meet the current facility requirements.

2. Scope 

2.1
This guideline applies only to existing buildings, systems, and/or assemblies that were previously commissioned.

2.2 This guideline addresses the following:

  1. Overview of Ongoing Commissioning Process (OCx) activities
  2. Assembly of the OCx Team, review of the current facility requirements (CFR), and development of the OCx Plan.
  3. Implementation of system/assembly performance measurements and verification processes.
  4. Assessment of achievement of the CFR.
  5. Investigation of unacceptable performance outcomes.
  6. Development and implementation of tune-up recommendations and reverification.
  7. Updating of the Systems Manual.
  8. Updating of facility O&M plans and personnel training.
  9. Development and delivery of the OCx Report.
  10. Updating the OCx Plans.

ASHRAE Guideline 1.1-2025 – Published guideline (supersedes ASHRAE Guideline 1.1-2007)
Application of the Commissioning Process to New HVAC&R Systems

1. Purpose

1.1 The purpose of this guideline is to provide specific technical detail that augments ASHRAE Guideline 0, The Commissioning Process for New Buildings and New Systems, and ANSI/ASHRAE/IES Standard 202,The Commissioning Process Requirements for New Buildings and New Systems, specific to commissioning new heating, ventilating, air-conditioning, and refrigerating (HVAC&R) systems.

2. Scope

2.1
This document provides specific commissioning content that expands on application of the Commissioning Process (Cx) contained in ASHRAE Guideline 0 and ANSI/ASHRAE/IES Standard 202 for each project delivery phase from predesign through occupancy and operation for all types and sizes of HVAC&R systems. This includes the following requirements:

  1. The system- and assembly-related content for inclusion in the Owner’s Project Requirements (OPR)
  2. Defining the focus of design and submittal reviews, commissioning meetings, commissioning checklists execution process, and development of evaluation procedures to fully implement the Cx
  3. Evaluation of the HVAC&R systems meeting the OPR, Basis of Design (BoD), and contract documents through each phase of the project
  4. Verification of maintainability and operability of commissioned HVAC&R systems
  5. Documentation of issues, resolutions, and benefits of the process throughout the commissioning of HVAC&R systems
  6. Systems Manual documentation
  7. Training for operations and maintenance personnel and occupants

2.2 This document establishes a foundation that allows an Owner to implement an existing building Cx as established in ASHRAE Guideline 0.2, The Commissioning Process for Existing Systems and Assemblies, and ASHRAE Guideline 1.2, Application of the Commissioning Process to Existing HVAC&R Systems.

SSPC 300 is the cognizant project committee for maintenance of Guideline 1.1. Guideline 1.1 on continuous maintenance.


ASHRAE Guideline 1.2-2019 Published Guideline
Technical Requirements for the Commissioning Process for Existing HVAC&R Systems and Assemblies

1. Purpose

1.1
The purpose of this guideline is to provide requirements for the application of the Commissioning (Cx) Process described in ASHRAE Guideline 0.2 to existing heating, ventilating, air-conditioning, and refrigerating (HVAC&R) systems and assemblies.

2. Scope

2.1
This guideline applies to the procedures, methods, and documentation requirements for each phase of the Commissioning (Cx) Process applied to existing HVAC&R systems and assemblies, including:

  1. Development of facility goals and Current Facility Requirements (CFR)
  2. Discovery and evaluation of available documentation for existing HVAC&R systems
  3. Evaluation of the condition of existing HVAC&R systems
  4. Development of a prioritized Cx Plan, including schedule and budget estimates
  5. Development of recommendations
  6. Implementation of recommendations
  7. Verification of completed recommendations
  8. Development of Systems Manual
  9. Training of facility personnel
  10. Development of Cx Reports
  11. Ongoing commissioning (OCx) activities

2.2 This guideline focuses on the following:

  1. Energy use
  2. Operations and Maintenance (O&M)
  3. Indoor Environmental Quality (IEQ)

SSPC 300 to be cognizant project committee for revision and maintenance of Guideline 1.2 (approved June 2016). Guideline to be placed on continuous maintenance upon publication of next revised edition (approved June 2019). Revised TPS (only Title amended) approved June 2024.
Application of the Commissioning Process to Existing HVAC&R Systems


ASHRAE Guideline 1.3-2018 – Published Guideline 
Building Operation and Maintenance Training for the HVAC&R Commissioning Process 

1. Purpose

1.1
The purpose of this guideline is to provide methodologies and formats for developing training plans, conducting training programs, and documenting training results for the operation and maintenance of building HVAC&R systems during the Commissioning (Cx) Process. 

2. Scope

2.1 
The procedures, methods and documentation requirements in this guideline cover the development of training plans, assembly and preparation of training materials, and conduction of training programs for HVAC&R operations and maintenance (O&M) personnel. 

2.2 The guideline addresses

  1. development of training requirements and plans;
  2. verification of personnel training needs and results;
  3. training formats and examples of training records;
  4. sources and development of training materials;
  5. methods of conducting training;
  6. evaluating training programs;
  7. recording of training. 

SSPC 300 to be cognizant project committee for revision and maintenance of Guideline 1.3 (approved June 2016). Guideline to be placed on continuous maintenance upon publication of next revised edition (approved June 2019). Revised TPS (only Title amended) approved June 2024.
Application of The Commissioning Process to Building Operation and Maintenance Training 


ASHRAE Guideline 1.4-2019 – Published Guideline (Supersedes ASHRAE Guideline 1.4-2014)
Preparing Systems Manuals for Facilities

1. Purpose

1.1
This guideline provides procedures for producing a Systems Manual as a resource for training, operations, maintenance, and upgrading of facilities.

2. Scope

2.1
This guideline applies to information from planning, commissioning, design, construction, testing, and training activities, and operations planning for new, renovated, and existing facilities, equipment, and assemblies.


SSPC 300 to be cognizant project committee for revision and maintenance of Guideline 1.4 (approved June 2016). Guideline 1.4 on continuous maintenance.


ASHRAE Guideline 1.5-2025 – Published guideline (supersedes ASHRAE Guideline 1.5-2017)

Application of the Commissioning Process for Smoke Control Systems

1. Purpose

1.1 The purpose of this guideline is to describe the technical requirements for the application of the Commissioning Process (Cx), described in ASHRAE Guideline 0 and Standard 202, that will verify that the smoke control system fulfills the Owner’s Project Requirements (OPR).

2. Scope

2.1 The procedures, methods, and documentation requirements in this guideline describe the application of the Commissioning Process (Cx) for each project delivery phase, from Predesign through Occupancy/Operations, for all types and sizes of smoke control systems, to support Cx Activities described in ASHRAE Guideline 0 and Standard 202. Requirements include the following:

  1. Smoke control systems to fully support the Cx Activities
  2. Verification during each phase of the Cx
  3. Acceptance during each phase
  4. Documentation during each phase
  5. A Systems Manual
  6. Training for operations and maintenance (O&M) personnel and occupants

2.2 The procedures, methods, and documentation requirements apply to new construction and Ongoing Cx Activities or requirements of all or portions of buildings and facilities. They also can be applied to rehab, retrocommissioning, or recommissioning projects.

SSPC 300 is the cognizant project committee for maintenance of Guideline 1.5. Guideline 1.5 on continuous maintenance.


ASHRAE Guideline 1.6P Proposed Guideline, approved November 4, 2017. SSPC 300 to develop Guideline 1.6P.
Commissioning of Data Centers

1. Purpose  

1.1
This guideline provides technical support for the application of the commissioning process to data centers.

2. Scope  
This guideline:

2.1
 Provides assistance in the application of ASHRAE Guideline 0 or ASHRAE Standard 202 to data centers;

2.2
 Addresses commissioning process issues that are particular to data centers;

2.3
 Provides technical support for the commissioning of data centers;

2.4
 Is intended for use with new and existing buildings;

2.5
Applies to data center support infrastructure – not to data equipment networks.

SSPC 300 to be cognizant project committee for revision and maintenance of Guideline 1.6P. Guideline to be placed on continuous maintenance.  Revised TPS (only Title amended) approved June 2024.


GPC 1.7P, Proposed Guideline authorized on 7/1/26 (Austin). This Guideline is being developed by SSPC 300.
Application of the Commissioning Process to Semiconductor Fabrication Facilities  

1. Purpose
The purpose of this guideline is to establish a standardized, scalable, and rigorous commissioning expectations for semiconductor fabrication facilities. It defines procedures that ensure critical systems, supporting high-precision, cleanroom, and mission-critical environments, are designed, installed, verified, and operated in alignment with the Owner’s Project Requirements (OPR). The guideline supports both initial commissioning and ongoing performance management, enabling reliable operations, process quality, energy efficiency, and regulatory compliance across the facility lifecycle.

2. Scope
This guideline applies to the commissioning and performance validation of new, renovated, and existing semiconductor manufacturing environments. It includes all phases of the facility lifecycle, from conceptual design through occupancy, tool integration, and ongoing commissioning. The guideline is applicable to various types of semiconductor operations, including but not limited to:

  1. Wafer fabrication facilities (Fabs)
  2. Research and development cleanrooms
  3. Tool installation and process bays
  4. Sub-fab infrastructure and interstitial mechanical zones
  5. Packaging, assembly, and test environments

ASHRAE Guideline 4-2019 - Published guideline. (Supersedes ASHRAE Guideline 4-2008) 
Preparation of Operations and Maintenance Documentation for HVAC&R Systems 

1. Purpose
To guide those responsible for the design, manufacturing, construction, commissioning, and operation of building HVAC&R and on-site generation systems in the preparation and delivery of operations and maintenance (O&M) documentation that 

  1. is simple to prepare and update, 
  2. is delivered on time, 
  3. is easy to use, and 
  4. provides accurate and relevant information. 

2. Scope
This guideline covers the format, content, delivery, and updating of building HVAC&R systems operations and maintenance (O&M) documentation that is normally provided by the Design Team and Construction Team members. 

This guideline can be used for two separate purposes. First, it can be used in the construction of new buildings that are not commissioned buildings. Second, it can be used as a guide for existing building documentation as a guideline for O&M documentation. 

GPC 4-2019R – Revision committee authorized by Standards Committee on September 27, 2023 with same TPS.
Preparation of Operating and Maintenance Documentation for HVAC&R Systems 


ASHRAE Guideline 6-2015 - Published guideline. 
Refrigerant Information Recommended for Product Development and Standards 

1. Purpose 

  1. This guideline identifies the types of refrigerant data that may be required by product development and system design engineers, ASHRAE standards, and appropriate codes to successfully apply a refrigerant in refrigeration or air conditioning equipment.
  2. This guideline also provides refrigerant suppliers and researchers with examples of measurement methods, previous research, and desired accuracy levels for various refrigerant properties. 

2. Scope

2.1 
This guideline lists the types of refrigerant information recommended as the minimum necessary for refrigerant research and development, and commercial application or for use in ASHRAE standards. 

2.2 This guideline covers property data for fluids used as refrigerants in HVAC&R applications. These include saturated and unsaturated halocarbons, saturated and unsaturated hydrocarbons, ethers, and inorganic compounds (such as ammonia and carbon dioxide). 

2.3 The guideline also addresses:

  1. basic chemical data
  2. thermophysical property data
  3. materials compatibility data and
  4. safety, health, and environmental information.

2.4 Suggested accuracies and methods that may be used in obtaining the data either are given, or references to applicable standards or other sources. 


ASHRAE Guideline 10-2023- Published guideline. Supersedes ASHRAE Guideline 10-2016.
Interactions Affecting the Achievement of Acceptable Indoor Environments

1. Purpose
To provide guidance regarding factors and their interactions as they affect the indoor environmental conditions acceptable to human occupants with regard to comfort and health.

2. Scope

2.1 This guideline provides guidance regarding factors and their interactions and includes thermal comfort, indoor air quality, sound and vibration, and non-ionizing electromagnetic radiation (including visible light).

2.2 This guideline applies to the design, construction, commissioning, operation and maintenance of buildings.

2.3 This guideline applies to all indoor or enclosed spaces that people may occupy.

Exceptions:

  1. Areas of buildings intended primarily for manufacturing, commercial processing, or industrial processing
  2. Parking garages
  3. Storage spaces intended for only incidental human occupancy
  4. Other such enclosed spaces not designed predominantly for human occupancy

SGPC 10 to maintain and revise Guideline 10. Guideline 10 on continuous maintenance. SGPC 10 authorized 10/1/2010.
Interactions Affecting the Achievement of Acceptable Indoor Environments


ASHRAE Guideline 11-2021 - Published guideline. Supersedes Guideline-11-2018.
Field Testing of HVAC Controls Components

1. Purpose
This guideline provides procedures for field testing and adjusting of control components used in building heating, ventilating, and air-conditioning (HVAC) systems.

2. Scope
This guideline covers the procedures, formats, and methods necessary for evaluation and documentation of the performance of devices and systems that control HVAC systems.

GPC 11-2021R –  Revision committee approved on 4/14/2025 with the same TPS. 


ASHRAE Guideline 12-2023 – Published guideline. Supersedes ASHRAE Guideline 12-2020.
Managing the Risk of Legionellosis Associated With Building Water Systems

1.  Purpose
The purpose of this guideline is to provide information and guidance for control of Legionellosis associated with building water systems.

2.  Scope

2.1 
This guideline applies to new and existing centralized cold and hot potable building water systems and to non-potable building water systems in human-occupied commercial, institutional, multi-unit-residential and industrial buildings, including, hotels, office buildings, hospitals and other health care facilities, assisted living facilities, schools, universities, commercial buildings, industrial buildings, and centralized systems in multifamily residential buildings.  While buildings with non-centralized building water systems and single-family residential buildings are not included, some of the information may be useful for such building water systems.

2.2  This guideline is intended for use by building owners and those involved in the design, construction, installation, commissioning, management, operation, maintenance and service of centralized building water systems as well as by manufacturers of associated equipment.

2.3  This guideline is also intended for use in the implementation of ANSI/ASHRAE Standard 188, Legionellosis: Risk Management for Building Water Systems, and does not require previous training or certification in any hazard analysis, risk assessment, or risk management methodologies.

This guideline is also intended for use in the practice of ANSI/ASHRAE Standard 188, “Legionellosis: Risk Management for Building Water Systems”.

SSPC 400 is the cognizant project committee for maintenance of Guideline 12 (approved January 2024).


ASHRAE Guideline 13-2024 – Published guideline. (Supersedes Guideline 13-2015)
Specifying Building Automation Systems

1. Purpose
The purpose of this guideline is to provide recommendations for developing specifications for building automation systems (BASs) in heating, ventilating, and air-conditioning (HVAC) control applications.

2. Scope
This guideline covers building automation systems (BASs) for heating, ventilating, and air-conditioning (HVAC) control, monitoring, and management functions. The guideline specifies hardware performance, installation, and training. It also addresses system architecture, input/output structure, communication, program configuration, system testing, and documentation. The guideline only includes examples of how to integrate with fire, life safety, lighting, and other systems. The design and specification of these non-HVAC systems is not part of this document. There is also no specification of facility management functions, as this is beyond the scope of this document.

  1. Direct digital control (DDC) for HVAC equipment control, monitoring, and management functions
  2. DDC hardware performance and installation
  3. System training
  4. System architecture
  5. Input/output structure
  6. Communication
  7. Program configuration
  8. System testing
  9. Documentation
  10. Integration with other building systems such as lighting, fire and life safety, security, and factory-installed equipment controls
  11. Integration with other enterprise level applications, such as facility management, preventive maintenance, or energy management systems.

The guideline does not include specifying control of fire or life safety systems or equipment, nor does it include specifying security systems or enterprise level applications.

SGPC 13  to maintain and revise Guideline 13. Guideline on continuous maintenance.


ASHRAE Guideline 14-2023, Published standard. Supersedes ASHRAE Guideline 14-2014. This was approved for continuous maintenance in March 2024.
Measurement of Energy, Demand and Water Savings 

1. Purpose
The purpose of this document is to provide guidelines for reliably measuring the energy, demand and water savings achieved in conservation projects. 

2. Scope
This document provides procedures for using measured preretrofit and postretrofit billing data (e.g., kWh, kW, Mcf, kgal) for the calculation of energy, demand, and water savings. 

2.1 What Is Included. The procedures

  1. Include the determination of energy, demand, and water savings from individual facilities or meters
  2. Apply to all forms of energy, including electricity, gas, oil, district heating/cooling, renewables, and water and wastewater
  3. Encompass all types of facilities: residential, commercial, institutional, and industrial 

2.2 What Is not Included. The procedures do not include

  1. Sampling methodologies used in large-scale demand-side management programs
  2. Metering standards
  3. Major industrial process loads 

GPC 14-2014R – Revision committee approved on 6/28/2017 with the same TPS. GPC 14 placed on continuous maintenance March 27, 2024. SGPC 14 responsible to maintain and revise Guideline 14.


ASHRAE Guideline 16-2025 - Published guideline. (Supersedes ASHRAE Guideline 16-2022)  
Selecting Outdoor, Return, and Relief Dampers for Air-Side Economizer Systems 

1.  Purpose
This guideline provides the basis for selecting and sizing control dampers (outdoor, return, and relief) commonly found in constant-air-volume (CAV) and variable-air-volume (VAV) air-handling units (AHU) and systems with air-side economizers. 

2. Scope

2.1 This guideline covers the application of mixed-air control dampers in AHUs and systems that incorporate air-side economizer systems for cooling. 

2.2 This guideline addresses the selection of control dampers based on damper characteristics and damper pressure drop. 

2.3 This guideline is not intended to cover dampers used elsewhere in heating, ventilating, and air-conditioning (HVAC) systems. 

2.4 This guideline does not cover air mixing. 


ASHRAE Guideline 20-2010 (RA2016) - Published guideline.
Documenting HVAC&R Work Processes and Data Exchange Requirements

1. Purpose
To define a systematic procedure for documenting work processes (Use Cases) and data exchange requirements for specific HVAC&R activities.

2. Scope
This guideline

  1. Defines methods for documenting Use Cases and data exchange requirements related to HVAC&R activities involving equipment, systems, design services, and other services over the life cycle of capital facilities. Use Case documentation will employ domain expert terminology and a consistent format to facilitate review and adoption by industry participants
  2. Outlines procedures for web-based management of Use Cases to support development of formal data definitions and implementation in HVAC&R industry software.

ASHRAE Guideline 21-2022 (IEEE Standard 1635-2018) – Published guideline. Supersedes ASHRAE Guideline 21-2018 (IEEE Standard 1635-2012. 
Guide for the Ventilation and Thermal Management of Batteries for Stationary Applications 

1.1 Scope 

This guide discusses the ventilation and thermal management of stationary battery systems as applied to the following: 

  1. Vented (flooded) lead-acid (VLA) 
  2. Valve-regulated lead-acid (VRLA) 
  3. Vented nickel-cadmium (Ni-Cd) 
  4. Partially recombinant vented nickel-cadmium 
  5. Lithium ion (Li-ion) 

For each category, both the technology and the design of the battery are described in order to facilitate user understanding of the environmental issues associated with each type of technology. 

The scope of this document includes only stationary batteries under conditions of expected use. Multiple operating modes are identified, including failure modes. 

The ventilation practices described in this guide represent the “best practice” based on the information available at the time this document was developed. The user should evaluate these practices against their operating experience, operating conditions, number and size of battery systems, manufacturer’s recommendations, resources, and needs in developing an environment that is conducive to safety and optimum operation of the equipment. These recommendations were developed without consideration of economics, availability of equipment and personnel, or relative importance of the application. Design of a ventilation system for a specific battery installation requires consideration of all issues, not just the technical issues considered in this document. 


ASHRAE Guideline 22-2025- Published Guideline. (Supersedes Guideline 22-2012).
Instrumentation for Monitoring Central Chilled Water Plant Efficiency

1. Purpose
This guideline defines recommended methods to determine chilled-water plant thermal load, energy use, and efficiency.
This guideline defines the following:

  1. Recommended measurement systems and calculation methods to determine energy consumption and thermal flows for cooling and heating, and
  2. Procedures for acquiring test data and calculating system efficiency

2. Scope

2.1 
This guideline applies to the following:

  1. Chilled-water plants using any type of liquid-chilling system as defined in Section 3
  2. Chilled-water plants using any liquid, as defined in Section 3 ,to transfer thermal energy

2.2 This guideline does not apply to the following:

  1. Design or operation of chilled-water plants, or
  2. Section, application, or operation of system components

ASHRAE Guideline 23-2016 - Published guideline. 
Guideline for the Design and Application of Heating, Ventilation and Air Conditioning Equipment for Rail Passenger Vehicles 

1. Purpose
To establish recommended design and application guidelines necessary to achieve an acceptable level of performance and safety for heating, ventilating, and air-conditioning equipment used on rail passenger vehicles operating in the environment of rail transportation systems. 

2. Scope
This guideline addresses rail passenger vehicles used in regularly scheduled public transportation service. 

2.1 The guideline addresses environmental conditions, equipment configurations, air filtration, temperature and humidity controls, determination and test verification of heating and cooling capacity, ventilation standards, passenger comfort criteria, materials, packaging, noise, vibration and shock, refrigerant selection, energy efficiency, corrosion protection, voltage and electrical requirements, power supply, and electromagnetic interference. 

GPC 23-2016R - Revision project committee authorized February 1, 2020.
Guideline for the Design and Application of Heating, Ventilation and Air Conditioning Equipment for Rail Passenger Vehicles


ASHRAE Guideline 27-2019 – Published Guideline    
Measurement Procedures for Gaseous Contaminants in Commercial Buildings 

1. Purpose
This guideline provides recommended procedures for effective measurement of airborne gas and vapor concentrations inside commercial buildings. Its goal is to provide consistent procedures to follow so field measurements of contaminant concentrations are accurate and reproducible, avoiding typical problems that may cause unreliable or inconsistent results., while recommending sample acquisition techniques, sampling locations in equipment and spaces, sampling requirements, and criteria for data analysis. 

2. Scope 
This document provides guidance on the procedures to follow when measuring gas-phase concentrations of contaminants in commercial buildings. The subject measurements are those used to establish existing, baseline or changed conditions as a function of the building systems or interior environments. The methods in this guideline emphasize obtaining meaningful data within a reasonable time period at a reasonable cost. This guideline does not apply to industrial or residential buildings. It does not address:

  1. specific measurement equipment or devices, or
  2. calibration of instruments. 

ASHRAE Guideline 27-2019R. Revision project approved February 7, 2023 with the same TPS.


ASHRAE Guideline 28-2021– Published Guideline. Supersedes ASHRAE Guideline 28-2016.
Air Quality Within Commercial Aircraft

1. Purpose
This Guideline serves as a companion to ASHRAE Standard 161 and provides supplemental information on air quality in air-carrier aircraft and on measurement and testing related to aircraft air quality.

2. Scope

  1. This guideline applies to commercial passenger air-carrier aircraft carrying 20 or more passengers and certified under Title 14 CFR Part 25.
  2. This guideline considers chemical, physical, and biological contaminants as well as, but not limited to, factors such as moisture, temperature and pressure that may affect air quality.

SSPC 161 to revise and maintain Guideline 28. Guideline 28 placed on continuous maintenance January 2015.


ASHRAE Guideline 29-2019 - Published Guideline. Supersedes ASHRAE Guideline 29-2009
Guideline for Risk Management of Public Health and Safety in Buildings

1. Purpose
To provide guidance for the practical evaluation, design, and implementation of measures to reduce multiple risks in new and existing buildings.

2. Scope

2.1
 This guideline contains qualitative and quantitative methods for management of the risk of extraordinary incidents in buildings. Specific subject areas of concern include air, food, and water. The extraordinary events addressed in this guideline include fire, seismic events, chemical and biological releases, blast, and other extraordinary hazards. The guideline will address extraordinary incidents from a multi-hazard perspective, and will cover both intentional and accidental occurrences. The guideline addresses aspects of building performance that affect occupant health and safety, including egress; chemical, biological, and radiological (CBR) protection; fire protection; smoke removal or purging; filtration; air quality; entrance paths for contaminants; and building envelopes.


ASHRAE Guideline 32-2018 - Published Guideline. Supersedes ASHRAE Guideline 32-2012 
Management for Sustainable, High-Performance Operations & Maintenance 

1. Purpose 
The purpose of this guideline is to provide guidance to achieve, maintain, and continuously enhance sustainable, high performance buildings and building systems and assemblies through operations and maintenance (O&M) practices at lowest economic and environmental life cycle cost while maintaining safety, indoor air quality (IAQ), and functionality, including productivity. 

2. Scope 
This guideline applies to the ongoing operational practices for building assemblies and systems, particularly with respect to energy efficiency, water consumption, productivity, occupant comfort, indoor air quality (IAQ), health and safety. 

GPC 32-2018R – Revision committee approved on 6/29/2022 with the same TPS.


ASHRAE Guideline 33-2021 - Published Guideline. (Reaffirmation of Guideline 33-2013 (RA 2016))
Guideline for Documenting Indoor Airflow and Contaminant Transport Modeling

1. Purpose
This guideline establishes a method and format for documenting inputs, assumptions, methods and outputs utilized when conducting indoor airflow and contaminant transport modeling studies. 

2. Scope
This guideline applies to the application of airflow and contaminant modeling for analyses of indoor air quality, thermal comfort, energy and events related to chemical, biological and radiological agents.

This guideline only applies to modeling efforts using multizone network models, computational fluid dynamics (CFD) or combinations of the two.


ASHRAE Guideline 34-2019 – Published Guideline 
Energy Guideline for Historic Buildings 

1. Purpose
The purpose of this guideline is to provide sound advice on the practices, processes, and workflows that should be followed when performing energy efficiency and energy conservation improvement projects and programs involving historic buildings, while minimizing disturbance to the historic character, characteristics, and materials (significance, value, and qualities) of the building. 

2. Scope

2.1
 
This guideline applies to buildings that are listed as historic buildings or which are eligible to be so listed by applicable law in the jurisdiction where the building is located. 

2.2 This guideline applies to projects which are intended to improve the:

  1. energy efficiency of operation and maintenance,
  2. efficiency of energy-using building systems and equipment, and
  3. energy performance of the building’s envelope. 

2.3 This guideline applies to projects which include:

  1. envelope modifications and upgrades to control heat and moisture transfer and limit air infiltration, and
  2. adding new HVAC, service water heating or lighting systems, or modifying existing systems, to improve energy efficiency while maintaining or improving human comfort and indoor environmental quality. 

ASHRAE Guideline 35P - Proposed Guideline Proposed Guideline authorized 6/26/2013 (Denver)
Method for Determining the Energy Consumption Caused By Air-Cleaning and Filtration Devices

1. Purpose
The purpose of this guideline is to establish a consistent methodology to determine the energy consumption created by the introduction of air cleaning and filtration devices into an air stream.

2. Scope

2.1
This guideline applies to air cleaning devices for removing particulate and gas phase contaminants in general ventilation systems.

2.2
This guideline does not apply to UV-C devices or electrically-powered general ventilation air-cleaning devices.


ASHRAE Guideline 36-2024 - Published Guideline. Supersedes ASHRAE Guideline 36-2021.
High Performance Sequences of Operation for HVAC Systems

1. Purpose
The purpose of this guideline is to provide uniform sequences of operation for heating, ventilating, and air-conditioning (HVAC) systems that are intended to maximize HVAC system energy efficiency and performance, provide control stability, and allow for real-time fault detection and diagnostics.

2. Scope
2.1 This guideline provides detailed sequences of operation for HVAC systems.

2.2
This guideline describes functional tests that when performed will confirm implementation of the sequences of operation.

SSPC 36 to revise and maintain Guideline 36. Guideline 36 placed on continuous maintenance May 2018


ASHRAE Guideline 37P - Proposed Guideline Authorized July 2, 2014 (Seattle)
Guidelines for the Application of Upper-Air (Upper Room) Ultraviolet Germicidal (UV-C) Devices to Control the Transmission of Airborne Pathogens

1.Purpose   
The purpose of this guideline is to provide information and recommendations for dosing, placement and safe usage of Upper-Air UV-C devices.

2. Scope

2.1
The guideline applies to passive and fan-assisted Upper-Air UV-C devices.

2.2
The guideline applies for proper installation, operating and maintenance procedures for the safe use of these devices.


ASHRAE Guideline 38-2023 - Published Guideline 
Guideline for Using Metal Pressure Vessels to Test Materials Used in Refrigeration Systems (Supersedes ASHRAE Guideline 38-2018) 

1. Purpose

This guideline is intended to establish a test procedure using metal pressure vessels for the evaluation of materials used in refrigeration systems. The use of metal vessels allows for the testing of a variety of materials, regulation of the pressure of the test, use of a realistic sample size to oil/refrigerant ratio, and other analytical tests, such as extraction. 

2. Scope

This guideline describes the preparation of metal pressure vessels and the procedure for charging them with refrigerant and with the materials to be tested. A procedure for heating the metal vessel and regulating the pressure is described. Post-test evaluations can be performed quantitatively and/or qualitatively by observing the metal vessel contents to gain information for determining the compatibility, suitability, or chemical stability of materials in the refrigerant environment. The technique described can be used to evaluate many different types of materials. The guideline does not describe the detailed preparation of the materials to be tested prior to placing them in the metal vessel. The materials to be tested can be aged over a broad range of temperatures and pressures that fall within the safety limits of the vessel. Detailed safety precautions are included. Properly performing this test requires careful attention to the detailed experimental technique and careful adherence to safety procedures. 


ASHRAE Guideline 39-2024 – Published Guideline 
Method of Test for Measuring Fractionated Compositions of Refrigerant Blends 

1. Purpose 

The purpose of this guideline is to establish test methods and procedures to obtain accurate experimentally determined fractionation (vapor and liquid) compositions of refrigerant blends under simulated isothermal leak events from containers and equipment in storage, transport, operation, and service. A fractionation analysis is undertaken to determine the worst case of fractionation for flammability (WCFF) of a refrigerant blend in order to assign flammability safety classifications under criteria established in ANSI/ASHRAE Standard 34. The WCFF, with respect to flammability and worst case of formulation (WCF) compositions of a refrigerant blend, are tested for flammability to determine the refrigerant’s lower flame limit and burning velocity, which is used, along with the calculated heat of combustion, in assigning a flammability safety classification for a refrigerant blend. 

2. Scope

This guideline defines a standardized test apparatus and procedure for experimentally conducting fractionation analyses of refrigerant blends to determine the worst case of fractionation for flammability (WCFF) composition of refrigerant blends or to validate computer simulation programs for fractionation analysis. 


ASHRAE Guideline 40-2017 - Published Guideline. 
Refrigeration Oil Description 

1. Purpose

The purpose of this guideline is to describe lubricants used in refrigeration and air-conditioning systems based on molecular structure, physical properties, and chemical properties. Because the properties of generically similar lubricants can vary significantly depending on source of formulation, terms such as “refrigeration lubricant” have little meaning in defining such materials. This guideline defines those properties critical to the precise identification of refrigeration lubricants, along with recognized test procedures for the determination of these properties. 

2. Scope

2.1 Application. This guideline applies to lubricants used or proposed as compressor lubricants in refrigeration systems. 

2.2 Test Methods. This guideline provides recognized test methods to

  1. describe a specific class of refrigeration lubricant without the use of commercial designations,
  2. describe the molecular structure for various classes of refrigeration lubricants, and
  3. define the critical properties needed to describe a refrigeration lubricant using recognized test procedures. 

2.3 Limits. This guideline is not intended to define refrigeration oil quality through the establishment of test specifications or requirements. In addition, performance tests intended to measure quality have been excluded from this guideline. 

GPC 40-2017R  – Revision committee authorized June 2020.
Refrigeration Oil Description


ASHRAE Guideline 41-2023 - Published Guideline. Supersedes ASHRAE Guideline 41-2-2020) 
Design, Installation and Commissioning of Variable Refrigerant Flow (VRF) Systems  

1. Purpose     
This guideline provides a procedure for the design, installation, and commissioning of variable refrigerant flow (VRF) systems.  

2. Scope

2.1 This guideline provides the procedures and design factors a design engineer should consider; the requirements and installation factors the installing contractor should consider; and the performance, commissioning, and operational factors the contractor and maintenance personnel should consider for a variable refrigerant flow (VRF) system. 

2.2 This guideline is intended for use with nonresidential building systems (including, but not limited to, hotels, office buildings, hospitals and other health care facilities, assisted living facilities, schools and universities, commercial buildings, industrial buildings, etc.) and centralized heating/cooling systems in multifamily residential buildings. This guideline is not intended for use with low-rise, single-family, residential buildings. 

2.3 This guideline is intended for use by design engineers, installing contractors, owners, operators, users, maintenance personnel, and equipment manufacturers. 

2.4 This guideline applies to the design, installation, and commissioning of VRF in new buildings, and to the retrofit and renovation of existing buildings.


ASHRAE Guideline 42 - 2023. Published Guideline 
Enhanced Indoor Air Quality in Commercial and Institutional Buildings

1. Purpose
The purpose of this guideline is to recommend measures that exceed minimum requirements for improving indoor air quality in commercial and institutional buildings.   These measures are intended to provide enhanced indoor air quality that is acceptable to human occupants and that minimizes adverse health effects.

2. Scope

2.1
This guideline applies to spaces intended for human occupancy within commercial and institutional buildings except those within dwelling units in residential occupancies in which occupants are non-transient.

2.2 This guideline provides recommendations related to certain sources, and for ventilation and air-cleaning-system design, installation, commissioning, and operation and maintenance.

SSPC 62.1 is responsible for the development of this guideline approved June 29, 2016. 


ASHRAE Guideline 43-2025 -  SSPC 170 is responsible for the development of this guideline. 
Operations Guideline for Ventilation of Health Care Facilities

1. Purpose
The purpose of this guideline is to provide recommendations for the operation of heating, ventilation and air conditioning (HVAC) systems that provide environmental control in health care facilities for the safety and comfort of health care facility occupants.

2. Scope: This guideline:

2.1
pertains to the operation of health care facility HVAC systems and equipment, their normal and routine maintenance, major tasks of periodic maintenance, and energy conservation;

2.2 applies to all health care facilities; contains guidance for operational parameters and preventative maintenance, based on the capabilities of the infrastructure, and the risks incurred in the systems and spaces, including the needs of infection prevention, to support asepsis during perioperative care or invasive procedures, and for ancillary and support services, e.g. disinfection or sterilization of reusable devices and instruments;

2.3 lists the health care spaces which should be monitored for compliance, which parameters should be monitored in each, and the means of monitoring and recording;

2.3.1 describes acceptable ranges for each parameter in each monitored space type, and contains time-dependent protocols to be followed when parameters are out of the acceptable range;

2.4 applies to emergency operations, continuity of service, and resiliency planning; includes guidance on maintaining, modifying, or overriding space parameters monitoring during emergency operations; specifies what environmental conditions are minimally acceptable, signifying urgent, contingent strategies to discontinue services in spaces or for types of equipment as part of a facility’s emergency response;

2.5 does not cover the design of new facilities or equipment, including additions and renovations of HVAC systems, or the spaces served by HVAC systems.


ASHRAE Guideline 44-2024 Published Guideline. 
Protecting Building Occupants from Smoke During Wildfire and Prescribed Burn Events 

1. Purpose

The purpose of this guideline is to recommend building measures to minimize occupant health impacts from wildfire and prescribed burn smoke events. 

2. Scope

2.1 This guideline applies to commercial buildings; institutional buildings, including health care facilities; and multiunit residential buildings, as well as dedicated spaces within these building types intended for temporary human occupancy during a wildfire or prescribed burn smoke event. 

2.2 This guideline addresses buildings expected to be occupied by potentially at-risk populations, including children and older adults. 

2.3 This guideline provides recommendations related to the design, installation, commissioning, operation, and maintenance of building envelope, ventilation, and air-cleaning systems. 

2.4 This guideline and its measures do not apply to internally generated smoke (e.g., from internal fires or structure fires).


ASHRAE Guideline 45P - Proposed Guideline Authorized July 1, 2021. Revised TPS approved by Standards Committee on April 14, 2025.
Measurement of Performance for Buildings Except Low-Rise Residential Buildings

1. Purpose 
The purpose of this document is to provide guidelines for reliably measuring whole building performance pertaining to occupied buildings, except low-rise residential buildings. 

2. Scope
This document provides procedures for measuring whole building performance, including energy, water and indoor environmental quality (IEQ), pertaining to all occupied buildings except low-rise residential buildings.

2.1. What Is Included. The procedures include:

  1. IEQ (thermal comfort, indoor air quality, lighting, and acoustics);
  2. energy, water, and on-site renewables;
  3. occupant behaviors;
  4. metrics, measurement methods (including data integrity), and benchmarking/evaluation methods;
  5. multiple levels of measurements (accuracy/complexity); and
  6. fall types of occupied buildings except low-rise residential buildings.

2.2 What Is not Included. The procedures do not include:

  1. greenhouse gas (GHG) and carbon emission metrics;
  2. rating methods; or
  3. quantitative measurement cost.

ASHRAE Guideline 47P, Design, Installation and Commissioning of Central Domestic Electric Heat Pump Hot Water Systems in New Multifamily Buildings – Proposed Guideline authorized January 2024. Revised TPS approved by Standards Committee in November 2025.
Central Heat Pump Service Water Heating Systems in Multifamily Buildings

1. Purpose

1.1 To provide guidance for central heat pump service water heating (SWH) systems in multifamily buildings, including: 

  1. System Sizing and Design
  2. Equipment Selection
  3. Installation Considerations
  4. Startup and Performance Confirmation
  5. Operations and Maintenance

1.2 To inform design engineers, installing contractors, owners, operators, users, maintenance personnel, and equipment manufacturers about the special considerations for these systems.

2. Scope
This guideline applies to central heat pump SWH systems in multifamily buildings. 


ASHRAE Guideline 48P – Proposed Guideline authorized October 2024. Revised TPS approved by Standards Committee on April 14, 2025.
Operational Best Practices for Air Quality within Commercial Aircraft

1. Purpose
This guideline serves as a companion to ANSI/ASHRAE Standard 161 by describing operational best practices to assist aircraft operators to meet or exceed Standard 161 requirements.

2. Scope

2.1
This guideline applies to the occupied portions of passenger aircraft with a seating capacity of 20 or more passengers during ground and flight operations and to the occupied portions of cargo aircraft with a maximum allowable gross takeoff weight greater than 19,000 lb (8,600 kg) during ground and flight operations. 

2.2 This guideline considers control of air contaminants, infectious areosols thermal conditions, and related factors such as humidity and pressure.

SSPC 161 is the cognizant project committee for the development of Guideline 48P.


ASHRAE Guideline 49P, Integration of Future Weather Data into Built Environment Analysis

1. Purpose
This guideline provides recommendations for reliable, transparent, and replicable use of future weather data in analysis of the built environment.

2. Scope
Recommendations provided by this guideline cover:

  1. Data: Selection and evaluation of future weather data.
  2. Use cases: Climate mitigation and adaptation calculations for the built environment, including design, sustainability, uncertainty and risk, resilience and robustness, and related analyses. 
  3. Scale: Analysis of buildings and their systems, campuses, communities, and urban environments.

Proposed Guideline approved by Standards Committee  - June 25, 2025.


ASHRAE Guideline 50P, Proposed Guideline authorized on 7/1/26 (Austin).
Acceptable Indoor Air Quality for Crewed Spacecraft and Habitats 

1. Purpose
The purpose of this guideline is to specify the recommended indoor air quality that an environmental control and life support system for a crewed off-planet spacecraft or habitat should provide to be acceptable to human occupants and to minimize adverse health effects. This guideline is intended for application in new commercial spacecraft and habitats.

2. Scope
This guideline applies to spaces intended for human occupancy within commercial spacecraft and habitats operated in microgravity and in a surrounding vacuum. This guideline provides recommendations for the design, installation, performance verification, and operation and maintenance of air cleaning and air conditioning systems. This guideline contains recommendations related to certain contaminants and contaminant sources including, but not limited to, crew members, experiment processes, docked vehicle atmosphere mixing, material off-gassing, moisture, and biological growth.


ANSI/ASHRAE Standard 15-2024 – Published standard. (Supersedes ANSI/ASHRAE Standard 15-2022) 
Safety Standard for Refrigeration Systems

1. Purpose
This standard specifies safe design, construction, installation, and operation of refrigeration systems.

2. Scope

2.1
 This standard establishes safeguards for life, limb, health and property and prescribes safety requirements.

2.2 This standard applies to:
a. the design, construction, test, installation, operation, and inspection of mechanical and absorption refrigeration systems, including heat-pump systems used in stationary applications;
b. modifications, including replacement of parts or components if they are not identical in function and capacity; and
c. substitutions of refrigerants having a different designation.

2.3 This standard shall not apply to refrigeration systems using ammonia (R-717) as the refrigerant.

2.4 This standard does not apply to residential refrigeration systems serving only a single dwelling unit or sleeping unit complying with ASHRAE Standard 15.2.

SSPC 15 to maintain and revise Standard 15. Standard on continuous maintenance. 


SSPC 15 to maintain and revise Standard 15. Standard on continuous maintenance. Revised TPS approved February 5, 2020
Safety Standard for Refrigeration Systems

1. Purpose  
This standard specifies safe design, construction, installation, and operation of refrigeration systems.

2. Scope

2.1
This standard establishes safeguards for life, limb, health and property and prescribes safety requirements.

2.2 This standard applies to:
a. the design, construction, test, installation, operation, and inspection of mechanical and absorption refrigeration systems, including heat-pump systems used in stationary applications;
b. modifications, including replacement of parts or components if they are not identical in function and capacity; and
c. substitutions of refrigerants having a different designation.

2.3 This standard shall not apply to refrigeration systems using ammonia (R-717) as the refrigerant.

2.4 This standard does not apply to residential refrigeration systems serving only a single dwelling unit or sleeping unit complying with ASHRAE Standard 15.2.


ANSI/ASHRAE Standard 15.2-2024 – Published standard. (Supersedes ANSI/ASHRAE Standard 15.2-2022) 
Safety Standard for Refrigeration Systems in Residential Applications 

1. Purpose
This standard specifies the minimum requirements for the safe design and installation of refrigeration systems used in residential applications. 

2. Scope

2.1 This standard applies to listed refrigeration systems in the following residential applications that are limited to serving only a single dwelling unit or sleeping unit: 

  1. One- and two-family dwellings and townhouses
  2. Detached outbuildings associated with a one- or two-family dwelling or townhouse and located on the same property included in Section 2.1(a)
  3. Individual dwelling units and sleeping units located in a multifamily dwelling 

SSPC 15 to maintain and revise Standard 15.2. Standard on continuous maintenance. 


ANSI/ASHRAE Standard 16-2016 - Published standard. Supersedes Standard 16-1983.
Method of Testing For Rating Room Air Conditioners, Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps for Cooling and Heating Capacity

1. Purpose
The purpose of this standard is to prescribe test methods for determining the cooling and heating capacity of room air conditioners, packaged terminal air conditioners and packaged terminal heat pumps.

2. Scope
This standard:

  1. establishes uniform methods of testing to obtain rating data,
  2. specifies test equipment for performing such tests,
  3. specifies data required and calculations to be used, and
  4. lists and defines the terms used in testing.

SPC 16-2016R - Revision committee authorized November 2020 with the same TPS.
Method of Testing for Rating Room Air Conditioners, Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps for Cooling and Heating Capacity


ANSI/ASHRAE Standard 17-2022 - Published standard. (Supersedes Standard 17-2015 
Method of Testing Capacity of Electronic and Thermostatic Refrigerant Expansion Valves  

1. Purpose

This standard prescribes a method of testing the capacity of electronic and thermostatic refrigerant expansion valves for use in vapor-compression refrigeration systems. 

2. Scope

2.1  This standard is applicable to 

   a. electronic and thermostatic expansion valves (also referred to in this standard as “expansion valves”) as defined in Section 3; 

   b. expansion valves of the direct-acting type but not the pilot-operated type; and 

   c. many currently used refrigerants deemed available and suitable according to ANSI/ASHRAE Standard 15, Safety Standard for    Refrigeration Systems and ANSI/ASHRAE Standard 34, Designation and Safety Classification of Refrigerants.

2.2 This standard specifies procedures, apparatus, and instrumentation that will produce accurate capacity data. 

2.3 This standard does not 

   a. specify tests for production, specification compliance, or field testing of expansion valves or 

   b. specify capacity rating conditions for testing expansion valves. 

SPC 17-2015R -Revision project committee authorized June 27, 2018. Revised TPS approved October 2021.
Method of Testing Capacity of Electronic and Thermostatic Refrigerant Expansion Valves

1. Purpose
This standard prescribes a method of testing the capacity of electronic and thermostatic refrigerant expansion valves for use in vapor-compression refrigeration systems

2. Scope
This standard is applicable to:

  1. electronic and thermostatic expansion valves (also referred to in this standard as expansion valves) as defined in Section 3 Definitions,
  2. expansion valves of the direct-acting type but not the pilot-operated type, and
  3. many currently used refrigerants deemed available and suitable according to ANSI/ASHRAE Standard 15 Safety Code for Mechanical Refrigeration and ANSI/ASHRAE Standard 34 Designation and Safety Classification of Refrigerants.

This standard specifies procedures, apparatus, and instrumentation that will produce accurate capacity data.

This standard does not:

  1. specify tests for production, specification compliance, or field testing of expansion valves, nor
  2. specify capacity rating conditions for testing expansion valves. These may be found in AHRI Standard 750 Thermostatic Refrigerant Expansion Valves, AHRI Standard 751 Thermostatic Refrigerant Expansion Valves, AHRI 1370 Performance Rating of Electronic Expansion Valves, and AHRI 1371 Performance Rating of Electronic Expansion Valves.

ANSI/ASHRAE Standard 20-2019 – Published standard. Published standard. Supersedes ANSI/ASHRAE Standard 20-1997. 
Methods of Laboratory Testing Remote Mechanical-Draft Air-Cooled Refrigerant Condensers 

1. Purpose
This standard prescribes methods of laboratory testing remote mechanical-draft, air-cooled refrigerant condensers.  

2. Scope

2.1
This standard provides: 

  1. methods of laboratory testing for obtaining performance data,

  2. definition of terms, 

  1. specification of data to be recorded, 

  1. calculation formulas, 

  1. test limits and tolerances, and

  2. apparatus and instrumentation with associated accuracies. 

2.2 This standard does not cover:

  1. methods of test for production or field use, 

  1. heat exchangers that do not fully condense refrigerant vapor, as in heat reclaim applications, 

  1. methods for rating condensers, nor 

  1. external air resistance devices not provided by the manufacturer 

SPC 20-2019 – SPC 20-2019 – Revision committee authorized by Standards Committee on September 27, 2023 with same TPS .  
Methods of Laboratory Testing Remote Mechanical-Draft Air-Cooled Refrigerant Condensers 


ANSI/ASHRAE Standard 22-2023 - Published standard. Supersedes ANSI/ASHRAE Standard 22-2018.
Methods of Testing for Rating Liquid-Cooled Refrigerant Condensers

1. Purpose
This standard prescribes methods of testing the thermal performance and liquid-side pressure drop of liquid cooled refrigerant condensers.

2. Scope
This standard applies to the methods of testing for thermodynamic performance rating of liquid-cooled refrigerant condensers that operate at subcritical pressures of the refrigerant.

SPC 22-2018R Revision committee approved by Standards Committee on 3/31/2021.
Methods of Testing for Rating Liquid-Cooled Refrigerant Condensers


ANSI/ASHRAE Standard 23-2022 Published standard
Methods for Performance Testing Positive Displacement Refrigerant Compressors and Compressor Units

1. Purpose
This standard prescribes methods for performance testing positive displacement refrigerant compressors and compressor units including capacity, isentropic efficiency and volumetric efficiency.

2. Scope
1. This standard applies to methods for performance testing single-stage and multi-stage positive displacement refrigerant compressors and compressor units.
2. This standard applies to compressors and compressor units which either (a) do not have intermediate cooling or refrigerant injection, or (b) do have intermediate cooling or refrigerant injection and the power required for intermediate cooling or refrigerant injection, if any, is included in the measured total input power to the compressor or compressor unit.


ANSI/ASHRAE Standard 24-2025 - Published standard. (Supersedes ANSI/ASHRAE Standard 24-2019)  
Methods of Testing for Rating Evaporators Used for Cooling Liquids 

1. Purpose
This standard prescribes methods of testing the thermal performance and liquid-side pressure drop of evaporators that operate at subcritical pressures of the evaporating refrigerant. 

2. Scope
This standard 

  1. lists and defines the terms for rating the thermal performance and liquid-side pressure drop of evaporators used for cooling liquids; 
  2. establishes the methods of test that shall be used as a basis for obtaining the thermal performance and pressure drop of evaporators that operate at subcritical pressures of the evaporating refrigerant; and 
  3. applies to laboratory testing for purposes of rating evaporators within its scope. This standard is not intended for field testing of evaporators of any type. 

ANSI/ASHRAE Standard 25-2018 - Published standard. (Reaffirmation of ANSI/ASHRAE Standard 25-2001)
Methods of Testing Forced Convection and Natural Convection Air Coolers for Refrigeration

1. Purpose
This standard establishes uniform methods of testing for obtaining performance data, lists and defines the terms used in testing, specifies data to be recorded and formulas to be used in calculations, and sets limits and tolerances in testing.  

2. Scope 

This standard applies to factory-made, forced-circulation free-delivery unit coolers operating with a volatile refrigerant fed by either direct expansion or liquid overfeed at wet and/or dry conditions. This standard does not include the following: 

   a. Air conditioning units used primarily for comfort cooling for which testing methods are given in other standards 

   b. Unit coolers operating at latent load conditions with a refrigerant saturation temperature of less than 32°F (0.0°C) 

   c. Unit coolers installed in or connected to ductwork or with external air resistance devices not provided by the manufacturer 

   d. Unit coolers using zeotropic refrigerants with glides greater than 12.6°F (7.0°C) 

   e. Field testing of unit coolers 

SPC 25-2018R – Revision project committee authorized September 27, 2023 with same TPS. 


ANSI/ASHRAE Standard 26-2010 (RA2020) - Published standard. Supersedes ANSI/ASHRAE Standard 26-2010. 
Mechanical Refrigeration and Air Conditioning Installations Aboard Ship  

1. Purpose
This standard provides the minimum general requirements for the design, construction, installation, operation, inspection and maintenance of mechanical refrigeration and air conditioning equipment aboard ships to permit the safe, efficient and reliable operation of such systems. 

2. Scope

2.1 This standard covers:

  1. refrigeration and air conditioning systems that are an integral part of the main mechanical plant of merchant, fishing and seafood processing ships, and 
  2. refrigerated sea water and brine chilling systems that air condition and dehumidify passenger and cargo spaces, chill or freeze perishable cargo or maintain storage of chilled or frozen cargo. 

2.2 This standard does not cover:

  1. details of system designs or applications, 
  2. small, self contained units which are not an integral part of the ship's main mechanical plant such as electric water coolers, reach-in refrigerators and room air conditioners, 
  3. cargo containers with self contained refrigeration systems, and 
  4. liquefied gas ships. 

2.3 Exceptions to the literal details of this standard may be used when approved by the authorities having jurisdiction when equivalent safety, efficiency and reliability are achieved. 

SPC 26-2010R– Revision project authorized January 22, 2014 (New York) with the same TPS.
Mechanical Refrigeration and Air Conditioning Installations Aboard Ship


ANSI/ASHRAE Standard 28-1996 (RA 2020) - Published standard. Reaffirmation of ANSI/ASHRAE Standard 28-1996 (RA 2010) 
Method of Testing Flow Capacity of Refrigerant Capillary Tubes 

1. Purpose
This standard provides uniform methods for laboratory testing the flow capacity of refrigerant capillary tubes. 

2. Scope

2.1 This standard prescribes two test method a traditional method and an alternative method, for determining the flow capacity of capillary tubes such as are used for refrigerant metering in refrigeration systems. Both methods use dry nitrogen and provide comparable results, but the alternative method is more convenient if electronic devices are used.

2.2 The results obtained by the prescribed procedures are indicative of the refrigerant flow characteristics of the tube but are not intended to represent the actual refrigerant flow characteristics in a refrigerating cycle. 

2.3 The scope of this standard does not include specifications of tolerances on tube diameters or nitrogen flow capacity, however, acceptable variation in test results is suggested. 

SPC 28-1996R – Revision project authorized June 26, 2013 (Denver) with the same TPS. 


ANSI/ASHRAE Standard 29-2024 - Published standard. Supersedes ANSI/ASHRAE Standard 29-RA2018 
Methods of Testing Automatic Ice Makers 

1. Purpose

This standard prescribes a method of testing automatic ice makers by: 

   a. specifying procedures to be used when testing automatic ice makers, 
   b. establishing the types of equipment to which the provisions of the standard apply, 
   c. defining terms describing the equipment covered and terms related to testing, 
   d. specifying the type of instrumentation and test apparatus required in testing, 
   e. specifying a uniform method for calculation of results, and 
   f. specifying data and results to be recorded. 

2. Scope 
   a. This standard does not include automatic ice makers installed in household refrigerators, combination refrigerator-freezers, and household freezers.  


ANSI/ASHRAE Standard 30-2025 - Published Standard. Supersedes ASHRAE Standard 30-2019).  
Method of Testing Liquid Chillers 

1. Purpose

1.1
The purpose of this standard is to prescribe methods of testing to measure the thermal capacity, energy efficiency, and liquid pressure drop of packaged liquid chiller equipment using a refrigerant vapor compression cycle. 

1.2
This standard does not specify methods of establishing published ratings or performance tolerances. 

2. Scope

2.1
This standard applies to the following packaged equipment using any type of compressor: 

  1. liquid chilling 

  1. liquid heating 

  1. simultaneous liquid chilling and liquid heating 

2.1.1 Using the following methods of heat rejection during the cooling cycle or heat absorption during the heating cycle: 

  1. air cooled 

  1. adiabatically cooled 

  1. evaporatively cooled 

  1. liquid cooled 

2.2 This standard includes packaged equipment provided in more than one assembly if the separated or remote assemblies are designed to be used together and are connected together during the test. 

2.3
This standard does not include the following types of equipment: 

  1. self-contained, mechanically refrigerated drinking-water coolers within the scope of ASHRAE Standard 18 

  1. unitary water-to-air heat pump equipment within the scope of ASHRAE Standard 37 

  1. absorption water chilling packages included within the scope of ASHRAE Standard 182 

2.4 This standard does not include testing of chillers in field installations.

2.5 This standard does not specify the test operating conditions. 

2.6 This standard does not specify methods of performance ratings certification. 

SSPC 30 to maintain and revise Standard 30. Standard 30 placed on continuous maintenance January 2018. 


ANSI/ASHRAE Standard 32.1-2022 - Published Standard. (Supersedes ANSI/ASHRAE Standard 32.1-2017)
Method of Testing for Rating Refrigerated Vending Machines for Sealed Beverages

1. Purpose: 
The purpose of this standard is to specify methods of testing for rating the capacity and efficiency of self-contained, mechanically refrigerated vending machines for sealed beverages.

2. Scope: 

2.1 This standard:

  1. establishes uniform methods of testing for determining laboratory performance of refrigerated beverage vending machines;
  2. applies to refrigerated beverage vending machines and combination machines;
  3. lists and defines the terms used in the methods of testing;
  4. defines standard sealed-beverage storage capacity; and
  5. establishes test conditions for rating.

2.2 The provisions of this standard do not apply to climate-controlled snack vending machines, frozen-food vending machines, refrigerated-food-served-hot vending machines, or hot-beverage vending machines.


ANSI/ASHRAE Standard 32.2-2018 (RA 2022) – Published Standard. Supersedes ANSI/ASHRAE Standard 32.2-2018 
Methods of Testing for Rating Pre-Mix and Post-Mix Beverage Dispensing Equipment 

1. Purpose
The purpose of this standard is to specify uniform methods of testing for rating the capacity and efficiency of pre-mix and post-mix beverage dispensing equipment. 

2. Scope

This standard 

  1. establishes uniform methods of testing for determining the performance of premix and postmix chilled-beverage dispensers that are electrically operated and mechanically refrigerated or ice cooled; 

  1. defines the terms used in the methods of testing; and 

  1. establishes test conditions for rating. 

This standard does not cover 

  1. drink-quality elements other than temperature or 

  1. frozen beverage types. 


ANSI/ASHRAE Standard 33-2016 (RA 2026) - Published standard. Supersedes ASHRAE Standard 33-2000. 
Methods of Testing Forced-Circulation Air-Cooling and Air-Heating Coil 

1. Purpose

1.1 The purposes of this standard are to: 

  1. Describe and specify testing instruments and apparatus 
  2. Describe and specify laboratory test methods and procedures 
  3. Describe and specify test data to be recorded 
  4. Describe and specify calculations to be made from test data 
  5. Define terms used in testing 
  6. Specify standard thermodynamic properties 

1.2 It is not the purpose of this standard to specify the types of tests used for production or field testing. 

2. Scope

2.1 This standard prescribes laboratory methods of testing forced-circulation air-cooling coils, for application under non-frosting conditions and forced-circulation air-heating coils to ensure uniform performance information for establishing ratings.  


SPC 33-2016R - Revision project committee authorized June 22, 2019. 
Methods of Testing Forced-Circulation Air-Cooling and Air-Heating Coils  


ANSI/ASHRAE Standard 34-2024 - Published standard. (Supersedes ANSI/ASHRAE Standard 34-2022)
Designation and Safety Classification of Refrigerants

1. Purpose
This standard is intended to establish a simple means of referring to common refrigerants instead of using the chemical name, formula, or trade name. It establishes a uniform system for assigning reference numbers, safety classifications, and refrigerant concentration limits to refrigerants. The standard also identifies requirements to apply for designations and safety classifications for refrigerants and to determine refrigerant concentration limits

2. Scope
This standard provides an unambiguous system for numbering refrigerants and assigning composition-designating prefixes for refrigerants. Safety classifications based on toxicity and flammability data are included along with refrigerant concentration limits for the refrigerants. This standard does not imply endorsement or concurrence that individual refrigerant blends are suitable for any particular application.

SSPC 34 to maintain and revise Standard 34. Standard on continuous maintenance.
Designation and Safety Classification of Refrigerants


ANSI/ASHRAE Standard 35-2014 (RA2024) - Published standard. Supersedes  ANSI/ASHRAE Standard 35-2014) 
Method of Testing Desiccants for Refrigerant Drying  

1. Purpose 

1.1 This standard establishes a method of testing desiccants for use in refrigerant drying. 

2. Scope

2.1 This standard provides a method of testing desiccants only. For testing and rating driers, which use these desiccants, see ASHRAE Standard 63.1. (see Annex A, Informative Bibliography). 

2.2 The principle of this standard is to keep a desiccant of known water content in contact with the desired refrigerant until equilibrium has been established under known temperature conditions, after which the water content of the refrigerant is determined. 

2.3 This standard is applicable for all desiccants which do not react to the desired refrigerant. 

SPC 35-2014R -Revision project committee authorized 6/27/2018. Revised TPS approved June 2020. 
Method of Testing Refrigerant Driers and Desiccant Materials  

1. Purpose
The purpose of this standard is to prescribe test methods for measuring flow capacity and moisture capacity performance characteristics of refrigerant driers and measuring the moisture capacity characteristic of desiccant materials. 

2. Scope

2.1 This standard provides a method of testing moisture capacity for all molded core and loose filled driers.  Liquid line driers can be measured for flow using this standard excluding suction line driers which are covered in ASHRAE Standard 78.  This standard applies to hermetic and non-hermetic driers. 

2.2 This standard provides a method of testing desiccant and adsorbents including molecular sieve, activated alumina, silica gel, activated carbon, and their mixtures.  This standard is applicable for all desiccants which do not react to the desired refrigerant 


ANSI/ASHRAE Standard 37-2024 - Published standard. (Supersedes ANSI/ASHRAE Standard 34-2009 RA 2019)
Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment

1. Purpose
The purpose of this standard is to provide test methods for determining the cooling capacity of unitary air-conditioning equipment and the cooling or heating capacities, or both, of unitary heat pump equipment.

1.2 These test methods do not specify methods of establishing ratings that involve factors such as manufacturing tolerances and quality control procedures.

2. Scope

2.1 This standard applies to electrically driven mechanical-compression unitary air conditioners and heat pumps consisting of one or more assemblies that include an indoor air coil(s), a compressor(s), and an outdoor coil(s). Where such equipment is provided in more than one assembly, the separated assemblies are designed to be used together.

2.2 This standard does not include methods of testing the following:

  1. cooling coils for separate use
  2. condensing units for separate use
  3. room air conditioners
  4. heat-operated unitary equipment 
  5. liquid chilling packages 
  6. multiple indoor air coils operating simultaneously in heating and cooling modes.

SPC 37-2009R Revision committee approved by Standards Committee on 6/27/2012. SPC 37 merged with SPC 116 on January 24, 2015. SPC 37 will develop a standard with a combined TPS. Revised TPS approved by Standards Committee, October 13, 2015.


ANSI/ASHRAE Standard 40-2025 - Published standard. (Supersedes ANSI/ASHRAE Standard 40-2014 2014 (RA2024)  
Methods of Testing for Rating Heat-Operated Unitary Air-Conditioning and Heat-Pump Equipment  

1. Purpose

1.1   This standard provides test methods for determining the heating and cooling output capacities and energy inputs of unitary air-conditioning and heat pump equipment that is heat-operated (see Section 3, “Definitions”). 
1.2   These test methods may be used as a basis for rating such equipment, but it is not the purpose of this standard to specify methods of establishing ratings. 

2. Scope

2.1   This standard applies to heat-operated unitary air conditioners and heat pumps consisting of one or more assemblies, including engine-driven systems. Where such equipment is provided in more than one assembly, the separate assemblies are designed to be used together.

2.2 Equipment within the scope of this standard may be classified as follows: 

  1. Component arrangements:
    1. factory-assembled equipment employing heat-operated or mechanical refrigeration cycle or cycles (e.g., a packaged unit)
    2. equipment employing a heat-operated or mechanical refrigeration cycle with indoor and outdoor sections in separate assemblies (e.g., a split system)
    3. equipment employing a heat-operated or mechanical refrigeration cycle as a liquid chiller with cooling coil in separate assembly (e.g., chiller)
    4. equipment employing refrigeration cycles and heating functions (e.g., chiller/heater)
  2. Method of providing air circulation through indoor section:
    1. with circulating fan incorporated with indoor assembly
    2. without circulating fan, for use with separate fan or air handler, or with heating equipment incorporating a fan
  3. Medium for heat transfer to or from the outdoors:
    1. air
    2. water (or brine)
    3. evaporatively cooled condenser (cooling only) 

2.3   This standard does not include methods of testing the following types of equipment: 

  1. Heat-operated absorption and engine-driven liquid chillers not part of a unitary air conditioner or heat pump 

  1. Electrically driven unitary air conditioners or heat pumps 

  1. Refrigerating systems employing the Peltier effect 

  1. Desiccant-based cooling systems 

SSPC 41 formed Tech Weekend 2005 to maintain and revise the 41 series individual standards.
Standard Methods for Measurement. 

ANSI/ASHRAE Standard 40-2014R Revision committee approved by Standards Committee on September 14, 2018
Methods of Testing for Rating Heat Operated Unitary Air-Conditioning and Heat-Pump Equipment

ANSI/ASHRAE Standard 41.1-2024 Published standard. Supersedes ANSI/ASHRAE Standard 41.1-2020.   

Standard Methods for Temperature Measurement 

1. Purpose
This standard prescribes methods for measuring temperature under laboratory and field conditions.  

2. Scope

2.1 This standard applies to temperature measurements under laboratory and field conditions for use in performance testing heating, ventilating, air-conditioning, and refrigeration systems and components. 

2.2 This standard does not apply to wet-bulb or dew-point temperature measurement methods within the scope of ANSI/ASHRAE Standard 41.6. 


ANSI/ASHRAE Standard 41.2-2026 - Published standard. Supersedes ANSI/ASHRAE Standard 41.2-2022 
Standard Methods for Air Velocity and Airflow Measurement 

1. Purpose
This standard prescribes methods for air velocity and airflow measurement, including consideration of density effects. 

2. Scope 

  1. This standard applies to air velocity and airflow measurement for testing heating, ventilating, air conditioning, and refrigerating systems and components at pressures within the range of –25 kPa to +25 kPa (–100 in. of water to +100 in. of water) referenced to atmospheric pressure.
  2. This standard includes airflow mixing methods to obtain more uniform temperatures and velocities. 

 SSPC 41 to maintain and revise Standard 41.2. 


ANSI/ASHRAE Standard 41.3-2025 – Published standard. Supersedes ANSI/ASHRAE Standard 41.1-2022) 
Standard Methods for Pressure Measurement 

1. Purpose
This standard prescribes methods for pressure measurements under laboratory and field conditions. 

2. Scope          
This standard applies to pressure measurements under laboratory and field conditions for testing heating, ventilation, air-conditioning, and refrigeration systems and components. 


ANSI/ASHRAE Standard 41.4-2015 (RA 2025) - Published standard. Supersedes ANSI/ASHRAE Standard 41.4-1996
Standard Method for Measuring the Proportion of Lubricant in Liquid Refrigerant 

1. Purpose
This standard prescribes a method for measuring the proportion of lubricant in liquid refrigerant. 

2. Scope

2.1 This standard uses the gravimetric method as the primary method, but alternative methods can be used if those methods are calibrated against the primary method. 
2.2 This standard does not apply to collected samples that contain less than 0.001 g (0.015 grains) of lubricant. 

Standard 41.4-2015R is being revised by SSPC 41. (Standards are on Periodic Maintenance).

ANSI/ASHRAE Standard 41.6-2025 – Published Standard. Supersedes ANSI/ASHRAE Standard 41.6-2021 
Standard Methods for Humidity Measurement 

1. Purpose
This standard prescribes methods for measuring the humidity of moist air with instruments. 

2. Scope 

2.1 This standard applies to the measurement of humidity of moist air from sea level to 3048 m (10,000 ft), and within the dry-bulb temperature range of -50°C to 160°C (-58°F to 320°F), and within the dew point temperature range of -50°C to 99°C (-58°F to 210°F). 

2.2 This standard applies to methods for the measurement of wet-bulb temperature, dew-point temperature and relative humidity. 


ANSI/ASHRAE Standard 41.7-2025 - Published standard. Supersedes ANSI/ASHRAE Standard 41.7-2021.  
Standard Methods for Gas Flow Measurement 

1. Purpose
This standard prescribes methods for gas flow measurement. 

2. Scope
This standard applies to laboratory and field gas flow measurement for testing heating, ventilating, air-conditioning, and refrigerating systems and components. This standard is restricted to applications where the entire flow stream of gas enters and exits the gas flowmeter in a “gas-only” state during data recording with the following exceptions: 

  1. This standard does not apply to airflow measurements at pressures within this range: -25 kPa to +25 kPa (-100 in. of water to +100 in. of water) referenced to ambient pressure. Those measurements are within the scope of ANSI/ASHRAE Standard 41.2. 
  2. This standard does not apply to fan performance rating airflow measurements. Those measurements are within the scope of ANSI/ASHRAE Standard 51. 
  3. This standard does not apply to gaseous-phase refrigerant mass flow measurements where the gas flow includes circulating lubricant. Those measurements are within the scope of ANSI/ASHRAE Standard 41.10. 

ANSI/ASHRAE Standard 41.8-2023 -  Published standard. Supersedes ANSI/ASHRAE Standard 41.8-2016 (RA2019) 
Standard Methods for Liquid Flow Measurement 

1. Purpose
This standard prescribes methods for liquid flow measurement. 

2. Scope
This standard applies to laboratory and field liquid flow measurement for testing heating, ventilating, air-conditioning, and refrigerating systems and components.  This standard is restricted to applications where the entire flow stream of liquid enters and exits the liquid flowmeter in a “liquid-only” state during data recording with the following exception: 

  1. This standard does not apply to liquid-phase refrigerant mass flow measurements where the liquid flow includes circulating lubricant. Those measurements are within the scope of ASHRAE Standard 41.10. 

ANSI/ASHRAE Standard 41.9-2025 - Published standard. (Supersedes ASHRAE Standard 41.9-2021.)
Standard Methods for Refrigerant Mass Flow Measurements Using Calorimeters

1. Purpose
This standard prescribes methods for measuring mass flow rates for refrigerants and refrigerant/lubricant mixtures using calorimeters.

2. Scope

2.1 This standard applies to measuring mass flow rates for refrigerants and refrigerant/lubricant mixtures using calorimeters in laboratories.

2.2 This standard applies where the entire flow stream of the refrigerant or the refrigerant/lubricant mixture enters the calorimeter as a subcooled liquid and leaves as a superheated vapor (evaporator type).

2.3 This standard applies where the entire flow stream of the refrigerant or the refrigerant/lubricant mixture enters the calorimeter as a superheated vapor and leaves as a subcooled liquid (condenser type).


ANSI/ASHRAE Standard 41.10-2024. Published standard. Supersedes ANSI/ASHRAE Standard 195.2013. 
Standard Methods for Refrigerant Volumetric or Mass Flow Measurement Using Flowmeters 

1. Purpose 
This standard prescribes methods for refrigerant volumetric or mass flow rate measurement using flowmeters in laboratory and field applications. Each refrigerant mass flow rate is determined by subtracting the measured lubricant mass flow rate from the measured refrigerant/lubricant mixture mass flow rate. 

2. Scope

2.1 This standard applies to the following:

  1. refrigerant volumetric or mass flow rate measurements using flowmeters in laboratory and field applications.
  2. systems where the refrigerants are mixed with lubricant.
  3. systems where the entire flow stream of the refrigerant in the refrigerant/lubricant mixture both enters and exits the flowmeter in a gaseous phase, in a liquid phase, or in a supercritical phase during data recording. 

2.2 This standard does not apply to the following: 

  1. Flow rate measurement of gaseous refrigerant not mixed with lubricant within the scope of ANSI/ASHRAE Standard 41.7 
  2. Flow rate measurement of liquid refrigerant not mixed with lubricant within the scope of ANSI/ASHRAE Standard 41.8 

ANSI/ASHRAE Standard 41.11-2023 – Published Standard. Supersedes ANSI/ASHRAE Standard 41.11-2020. 
Standard Methods for Power Measurement 

1. Purpose
This standard prescribes methods for power measurements. 

2. Scope 
This standard applies to power measurements under laboratory and field conditions when testing heating, ventilating, air-conditioning, and refrigerating systems and components. 

Standard 41.11-2010R is being revised by SSPC 41. Revision project approved by SSPC 41 February 1, 2022. (Standard 41.10 is on Periodic Maintenance).


ANSI/ASHRAE Standard 41.13-2023 Published Standard. 
Standard Methods for Fuel Higher Heating Value Measurement 

1. Purpose
This standard prescribes methods for determining fuel higher heating values. 

2. Scope
This standard applies to determining fuel higher heating values for use in testing heating, ventilating, air-conditioning, and refrigeration systems and components under laboratory and field conditions. 


ANSI/ASHRAE Standard 51-2025 (AMCA 210-25) - Published standard. Supersedes ASHRAE Standard 51-2007) (AMCA is the lead organization) 
Laboratory Methods of Testing Fans for Certified Aerodynamic Performance Rating 

1. Purpose

This standard establishes uniform test methods for a laboratory test of a fan or other air moving device to determine its aerodynamic performance in terms of airflow rate, pressure developed, power consumption, air density, speed of rotation and efficiency for rating or guarantee purposes. 

2. Scope

This standard applies to a fan or other air moving device when air is used as the test gas with the following exceptions: 

  1. Air circulating fans (ceiling fans, desk fans);
  2. Positive pressure ventilators;
  3. Compressors with inter-stage cooling; 
  4. Positive displacement machines; 
  5. Test procedures to be used for design, production, or field testing. 

ANSI/ASHRAE Standard 52.2-2025 - Published standard. Supersedes ANSI/ASHRAE Standard 52.2-2017) 
Method of Testing General Ventilation Air Cleaning Devices for Removal Efficiency by Particle Size 

1. Purpose
This standard establishes a test procedure for evaluating the performance of air-cleaning devices as a function of particle size. 

2. Scope

2.1 This standard describes a method of laboratory testing to measure the performance of general ventilation air cleaning devices. 

2.2 The method of testing measures the performance of air cleaning devices in removing particles of specific diameters as the devices become loaded by standardized loading dust fed at intervals to simulate accumulation of particles during service life. The standard defines procedures for generating the aerosols required for conducting the test. The standard also provides a method for counting airborne particles of 0.3 to 10 µm in diameter upstream and downstream of the air cleaning device in order to calculate removal efficiency by particle size. 

2.3 This standard also establishes performance specifications for the equipment required to conduct the tests, defines methods of calculating and reporting the results obtained from the test data, and establishes a minimum efficiency reporting system which can be applied to air cleaning devices covered by this standard. 

SSPC 52.2 to maintain and revise Standard 52.2. Standard placed on continuous maintenance on January 21, 2006.
Method of Testing General Ventilation Air Cleaning Devices for Removal Efficiency by Particle Size

ANSI/ASHRAE 55-2023 - Published standard. Supersedes ASHRAE Standard 55-2020. 
Thermal Environmental Conditions for Human Occupancy 

1. Purpose
The purpose of this standard is to specify the combinations of indoor thermal environmental factors and personal factors that will produce satisfactory thermal environmental conditions acceptable for a majority of the occupants within the space. 

2. Scope
2.1 The environmental factors addressed in this standard are temperature, thermal radiation, humidity, and air speed; the personal factors are those of activity and clothing. 

2.2 It is intended that all of the criteria in this standard be applied together, as comfort in the indoor environment is complex and responds to the interaction of all of the factors that are addressed herein. 

2.3 This standard specifies thermal environmental conditions acceptable for healthy adults at atmospheric pressure equivalent to altitudes up to 3000 m (10,000 ft) in indoor spaces designed for human occupancy for periods not less than 15 minutes. 

2.4 This standard does not address such nonthermal environmental factors as air quality, acoustics, illumination, or other physical, chemical, or biological space contaminants that may affect comfort or health. 

2.5 This standard shall not be used to override any safety, health, or critical process requirements. 

SSPC 55 to maintain and revise Standard 55. Standard 55 placed on continuous maintenance January 24, 2004.

ANSI/ASHRAE Standard 62.1-2025 - Published standard. Supersedes ANSI/ASHRAE Standard 62.1-2019. 
Ventilation and Acceptable Indoor Air Quality 

1. Purpose

1.1 The purpose of this standard is to specify minimum ventilation rates and other measures intended to provide indoor air quality (IAQ) that is acceptable to human occupants and that minimizes adverse health effects. 
1.2 This standard is intended for regulatory application to new buildings, additions to existing buildings, and those changes to existing buildings that are identified in the body of the standard. 
1.3 This standard is intended to be used to guide the improvement of indoor air quality in existing buildings. 

2. Scope

2.1 This standard applies to spaces intended for human occupancy within buildings except those within dwelling units in residential occupancies in which occupants are nontransient.

2.2 This standard defines requirements for ventilation and air-cleaning-system design, installation, commissioning, and operation and maintenance.

2.3 In addition to ventilation, this standard contains requirements related to certain contaminants and contaminant sources, including outdoor air, construction processes, moisture, and biological growth. 

2.4 This standard does not prescribe specific ventilation rate requirements for the following: 

  1. Spaces that contain smoking or that do not meet the requirements in the standard for separation from spaces that contain smoking 
  2. Patient care areas not listed in this standard 
  3. Laboratories with hazardous materials 
SSPC 62.1 to maintain and revise Standard 62.1. Standard 62.1 on continuous maintenance.

ANSI/ASHRAE Standard 62.2-2025 – Published Standard. 
Ventilation and Acceptable Indoor Air Quality in Residential Buildings

1. Purpose
This standard defines the roles and minimum requirements for mechanical ventilation and natural ventilation systems and other measures intended to provide acceptable indoor air quality (IAQ) in individual dwelling units.

2. Scope
This standard applies to dwelling units in residential occupancies in which the occupants are nontransient.

2.1 This standard considers chemical, physical, and biological contaminants that can affect air quality. Thermal comfort requirements are not included in this standard.
Informative Note: See ANSI/ASHRAE Standard 55, Thermal Environmental Conditions for Human Occupancy, for thermal comfort requirements.

2.2  While acceptable indoor air quality (IAQ) is the goal of this standard, it will not necessarily be achieved, even if all requirements are met.

  1. because of the diversity of sources and contaminants in indoor air and the range of susceptibility in the population;
  2. because of the many other factors that may affect occupant perception and acceptance of IAQ, such as thermal environment, visual environment and psychological factors;
  3. if the ventilation air is unacceptable and this air is brought into the dwelling unit without first being cleaned;
  4. because of contaminant transport from adjacent spaces;
  5. if the system or systems are not operated and maintained as designed; or
  6.  when high-polluting events occur.

2.3  This standard does not claim to achieve acceptable IAQ in buildings in which smoking is permitted.
Informative Note: See the ASHRAE Position Document on Environmental Tobacco Smoke (ETS) for more information on (ETS) in buildings.

SSPC 62.2 to maintain and revise Standard 62.2. Standard placed on continuous maintenance 6/28/1997. Revised TPS approved June 2026.

Ventilation and Acceptable Indoor Air Quality in Residential Buildings

 1. Purpose
This standard defines the roles and minimum requirements for mechanical ventilation and natural ventilation systems and other measures intended to provide acceptable indoor air quality (IAQ) in individual dwelling units.

2. Scope
This standard applies to dwelling units in residential occupancies designed for nontransient occupancy.

2.1 This standard considers chemical, physical, and biological contaminants that can affect air quality. Thermal comfort requirements are not included in this standard.
Informative Note: See ANSI/ASHRAE Standard 55, Thermal Environmental Conditions for Human Occupancy, for thermal comfort requirements.

2.2  While acceptable indoor air quality (IAQ) is the goal of this standard, it will not necessarily be achieved, even if all requirements are met.

  1. because of the diversity of sources and contaminants in indoor air and the range of susceptibility in the population;
  2. because of the many other factors that may affect occupant perception and acceptance of IAQ, such as thermal environment, visual environment and psychological factors;
  3. if the ventilation air is unacceptable and this air is brought into the dwelling unit without first being cleaned;
  4. because of contaminant transport from adjacent spaces;
  5. if the system or systems are not operated and maintained as designed; or
  6.  when high-polluting events occur.

2.3  This standard does not claim to achieve acceptable IAQ in buildings in which smoking is permitted.
Informative Note: See the ASHRAE Position Document on Environmental Tobacco Smoke (ETS) for more information on (ETS) in buildings.


ANSI/ASHRAE Standard 63.2-2024 - Published standard. Supersedes ANSI/ASHRAE Standard 63.2-2017. 
Method of Testing Liquid-Line Filter Drier Filtration Capability 

1. Purpose
The purpose of this standard is to prescribe a laboratory test method for evaluating the filtration capability of filters and filter driers used in liquid lines of refrigeration systems. 

2. Scope

2.1 This laboratory test method evaluates the capability of liquid-line filters and filter driers only for removing and retaining solid particles of a standard test contaminant. 

2.2 The test method may be applied to all hermetic refrigerant liquid-line filters and filter driers up to and including Model 417S (line size 23 mm maximum). 

2.3 The technique employed in this standard is the one-pass test method. In this test, a clean-up filter is installed downstream of the test sample and is designed to retain and prevent recirculation of most of the contaminant particles that are not collected by the test sample in the first pass. 

2.4 Filter driers have the added capability of removing and retaining certain dissolved contaminants. This standard does not provide measurement of this capability. 


ANSI/ASHRAE Standard 64-2020 - Published standard. Supersedes ANSI/ASHRAE Standard 64-2011. 
Methods of Laboratory Testing Remote Mechanical-Draft Evaporative Refrigerant Condensers 

1. Purpose
This standard prescribes methods of laboratory testing remote mechanical-draft evaporative refrigerant condensers. 

2. Scope

2.1 This standard provides a method of laboratory testing for obtaining performance data of remote mechanical-draft evaporative refrigerant condensers, including: 

  1. definition of terms, 
  2. specification of data to be recorded, 
  3. calculation formulas, 
  4. test limits and tolerances, and 
  5. apparatus and instrumentation with associated accuracies. 

2.2 This standard does not cover the following: 

  1. methods of test for production or field use, 
  2. heat exchangers that do not fully condense refrigerant vapor, as in heat reclaim applications, 
  3. methods for rating condensers, nor 
  4. the performance impact of external air resistance devices not provided by the manufacturer. 
  5. thermal performance corrections for barometric pressure, fan horsepower, and makeup water. 

ANSI/ASHRAE Standard 70-2023 - Published standard.  
Method of Testing the Performance of Air Outlets and Air Inlets 

1. Purpose
The purpose of this standard is to define laboratory methods of testing air outlets and air inlets used to terminate ducted and unducted systems for distribution and return of building air. 

2. Scope

2.1 This standard includes the specifications for test instruments, facilities, installations, procedures, and methods of calculation for determining aerodynamic performance and sound generation of air outlets and air inlets. 

2.2 The test methods in this standard apply to both isothermal and non-isothermal conditions. 

SPC 70-2006R - Revision committee approved by Standards Committee on 6/28/2014 (Seattle) with same TPS
Method of Testing for Rating the Performance of Air Outlets and Air Inlets

ANSI/ASHRAE Standard 72-2022- Published Standard.
Method of Testing Open and Closed Commercial Refrigerators and Freezers 

1. Purpose
The purpose of this standard is to prescribe a uniform method of testing open and closed commercial refrigerators and freezers for rating so that comparative evaluations can be made of energy consumption, product temperature performance, refrigeration load, the suction pressures required, and other performance factors. 

2. Scope
This standard applies to the following types of open and closed commercial refrigerators and freezers used for displaying or holding foods for which refrigeration is either required or desired: 

  1. both horizontal and vertical open and closed refrigerators and freezers, and 
  2. both remote and self-contained open and closed refrigerators and freezers 

This Standard does not apply to walk-in coolers, or refrigerators and freezers where the refrigerated air is in communication with walk-in coolers. 

SSPC 72 to maintain and revise Standard 72. Standard placed on continuous maintenance June 28, 2014

ANSI/ASHRAE Standard 78-1985 (RA 2017) - Published standard. Supersedes ANSI/ASHRAE Standard 78-1985. 
Method of Testing Flow Capacity of Suction Line Filters and Filter-Driers 

1. Purpose
This standard establishes a method for measuring the flow capacity of refrigerant suction line filters and filter-driers. 

2. Scope

2.1 This test method is intended for use on both sealed and replaceable element type suction line filters and filter-driers of all types. 

2.2 The test method is based on using air as the testing medium and calculating the results to refrigerant gas flow under various application conditions. 


ANSI/ASHRAE Standard 79-2024 - Published standard. Supersedes ANSI/ASHRAE Standard 79-2015  
Method of Testing for Fan-Coil Units 

1. Purpose
The purpose of this standard is to prescribe laboratory methods of testing for fan-coil units to ensure uniform performance data for establishing ratings. 

2. Scope

This standard includes procedures that 

  1. describe and specify test instruments and apparatus, 
  2. describe and specify laboratory test methods and procedures, 
  3. describe and specify test data to be recorded, 
  4. describe and specify calculations to be made from test data, 
  5. define terms used in testing, and 
  6. specify standard thermodynamic properties. 

ANSI/ASHRAE Standard 84-2024 - Published standard. Supersedes ASHRAE Standard 84-2020. 
Method of Testing Air-to-Air Heat/Energy Exchangers 

1. Purpose
The purpose of this standard is to: 

  1. Establish a uniform method of test for obtaining for the effectiveness of air-to-air heat/energy exchangers; 
  2. Specify the test conditions, data required, uncertainty analysis to be performed, calculations to be used, and reporting procedures for testing the performance of an air-to-air heat/energy exchanger; and 
  3. Specify the types of test equipment for performing such tests. 

2. Scope

2.1  This standard prescribes the laboratory methods for testing the performance of air-to-air heat and energy exchangers.  In this standard, an air-to-air heat/energy exchanger is a device to transfer heat, or heat and water vapor, from one airstream to another. The types of air-to-air heat/energy exchangers covered by this standard are: 

2.1.1  Regenerators: 

  1. rotary regenerators (including heat wheels and total energy wheels), 
  2. fixed-bed regenerators, including double-core regenerators but excluding indoor fixed-bed regenerators that require connecting ductwork at station 1 and 4 in which reversing airflows will occur in the field, and single-core fixed-bed regenerators. 

2.1.2  Exchangers with intermediate energy transfer medium arranged in a closed-loop circuit: 

  1. heat pipe exchangers, 
  2. thermosiphon exchangers, 
  3. recovery loop exchangers (run-around loops), 

2.1.3  Recuperators: 

  1. fixed-plate exchangers (including sensible-only and enthalpic plates) 

ANSI/ASHRAE Standard 86-2013 (RA 2016) - Published standard. Supersedes ANSI/ASHRAE Standard 86-2013. 
Methods of Testing the Floc Point of Refrigeration Grade Oils 

1. Purpose
This standard provides a method for measuring the waxing tendency of refrigeration grade oils. 

2. Scope
The floc point measurement indicates the waxing tendency of refrigeration grade oils at low temperatures. The floc point is defined as the highest temperature at which wax or other solid substances precipitate when a mixture 10 percent by volume of oil and 90 percent by volume of R-12 is cooled under specified conditions. The results can be used to compare the waxing tendency of several different oils. 

SPC 86-2013R - Revision project committee authorized February 1, 2020.


ANSI/ASHRAE/IES 90.1-2025 - Published Standard. Supersedes ANSI/ASHRAE/IES 90.1-2019 
Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings 

1. Purpose

1.1 To establish the minimum energy efficiency requirements of buildings other than low-rise residential buildings, and sites for

  1. design, construction, and a plan for operation and maintenance; and 
  2. utilization of on-site renewable energy resources. 

2. Scope

2.1 This standard provides 

  1. minimum energy-efficient requirements for the design and construction, and a plan for operation and maintenance of
    1. new buildings and their systems,
    2. new portions of buildings and their systems,
    3. new systems and equipment specifically identified in this standard that are part of a site,
    4. new systems and equipment in existing buildings, and
    5. new equipment or building systems specifically identified in this standard that are part of process applications
       
  2. criteria for controlling systems in the building or on the site that modify energy usage based on communication with energy suppliers to facilitate the use of low-emissions energy sources; and

  3. criteria for determining compliance with these requirements. 

2.2 The provisions of this standard do not apply to

  1. single-family houses and related incidental structures, multifamily structures of three stories or fewer above grade, manufactured houses (mobile homes), and manufactured houses (modular) or 
  2. buildings that use neither electricity nor fossil fuel. 

2.3 Where specifically noted in this standard, certain other buildings or elements of buildings or sites shall be exempt. 

2.4 This standard shall not be used to circumvent any safety, health, or environmental requirements. 

SSPC 90.1 to maintain and revise Standard 90.1. Standard approved for continuous maintenance 9/16/1983. Revised TPS approved June 2026.
Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings

1. Purpose

1.1 To establish minimum energy efficiency requirements of buildings other than low-rise residential buildings, and sites for

  1. design, construction, and a plan for operation and maintenance; and
  2. utilization of energy resources.

2. SCOPE

2.1 This standard provides

a. minimum energy-efficient requirements for the design and construction, and a plan for operation and maintenance of,

    1. new buildings and their systems,
    2. new portions of buildings and their systems,
    3. new systems and equipment specifically identified in this standard that are part of a site,
    4. new systems and equipment in existing buildings, and
    5. new equipment or building systems specifically identified in this standard that are part of process applications;

b. criteria for

    1. communications managing the use of energy, and
    2. the transfer of energy to and from buildings and sites; and

c. criteria for demonstrating compliance with this standard.

2.2 The provisions of this standard do not apply to

  1. single-family houses and related incidental structures, multifamily structures of three stories or fewer above grade, manufactured houses (mobile homes), and manufactured houses (modular) or
  2. buildings that use neither electricity nor fossil fuel.

2.3 Where specifically noted in this standard, certain other buildings or elements of buildings or sites shall be exempt.

2.4 This standard shall not be used to circumvent any safety, health, or environmental requirements.


ASHRAE Standard 90.1MR-P, Proposed Standard authorized 6/27/26 (Austin)
Standard for Minimum Energy Requirements for Low-Rise Residential Buildings

1. Purpose: The purpose of this standard is to provide cost-justified minimum requirements for the energy-efficient design and construction of new residential buildings three stories or less above grade and for major renovations to existing residential buildings three stories or less above grade, considering first costs, economic impacts, and expected energy savings. This standard is intended to include a performance and simple prescriptive path to achieve the objectives for a minimum standard which balances first cost and operational costs for an affordable housing solution.

2. Scope:

2.1 This standard applies to:

        1. new residential buildings three stories or less above grade;
        2. additions to residential buildings three stories or less above grade where new energy-related assemblies, systems, or equipment are installed; and
        3. major renovations to existing residential buildings three stories or less above grade where the project includes substantial replacement, alteration, reconfiguration, or upgrade of energy-related assemblies, systems, or equipment.

2.2 This standard provides cost-justified minimum requirements for the design, construction, installation, and replacement, as applicable, of:

        1. building thermal envelope components;
        2. air leakage control measures;
        3. heating, ventilating, and air-conditioning systems;
        4. service water-heating systems;
        5. lighting systems;
        6. controls associated with covered systems; and
        7. other specifically identified energy-related residential building components and systems.

2.3 This standard applies to detached single-family houses, detached two-family houses, townhouses, and other residential buildings three stories or less above grade, and to residential portions of mixed-use buildings within the height limitations of this standard.

2.4 This standard does not apply to:

        1. transient lodging;
        2. buildings more than three stories above grade;
        3. nonresidential occupancies except residential portions of mixed-use buildings within the scope of this standard; or
        4. ordinary maintenance and repair activities that do not materially affect building energy use.

2.5 This standard shall not be used to abridge safety, health, environmental, or other applicable code requirements.


ANSI/ASHRAE/IES Standard 90.2-2024 - Published Standard. Supersedes ANSI/ASHRAE/IES Standard 90.2-2018. 
High-Performance Energy Design of Residential Buildings 

1. Purpose
The purpose of this standard is to establish whole-building design requirements that enable high levels of energy performance and greenhouse gas emission performance for residential buildings. 

2. Scope
This standard provides requirements for achieving high levels of energy performance and greenhouse gas emission performance of residential buildings and their systems. 

2.1 Buildings and Portions of Buildings Covered 

        1. Dwelling units in which the occupants are nontransient 
        2. Common areas associated with residential occupancies 
        3. Outbuildings associated with residential occupancies 

2.2 Systems Covered 

        1. Building envelope 
        2. HVAC and mechanical systems 
        3. Service water heating systems 
        4. Major appliances 
        5. Interior and exterior lighting systems 
        6. Snow and ice melt systems 
        7. Pools and spas 
        8. Renewable energy systems 
        9. Energy storage systems 
        10. Connected controls 

2.3 Exemptions. This standard does not apply to transient housing, such as hotels, motels, nursing homes, jails, dormitories, and barracks. 

2.3 Health, Safety, and Welfare. This standard shall not be used to abridge any safety, health, or environmental requirements. 

SSPC 90.2 to be cognizant project committee for maintenance of Standard 90.2. Standard 90.2 on continuous maintenance. Revised TPS approved February 2026.
High Performance Energy and Indoor Environmental Design of Residential Buildings

1. Purpose
The purpose of this standard is to establish whole-building design requirements that enable high levels of energy performance and greenhouse gas emission performance for residential buildings, which maintain high levels of indoor environmental quality.

2. Scope 
This standard provides requirements for achieving levels of energy performance and greenhouse gas emission performance of residential buildings and their systems, which maintains high levels of indoor environmental quality. 

2.1 Buildings and Portions of Buildings Covered

  1. Dwelling units in which occupants are non-transient
  2. Common areas associated with residential occupancies
  3. Outbuildings associated with residential occupancies


2.2 Systems Covered

  1. Building envelope
  2. HVAC and mechanical systems
  3. Service hot-water systems
  4. Major appliances
  5. Interior and exterior lighting systems
  6. Snow and ice melt systems
  7. Pools and spas
  8. Renewable energy systems
  9. Energy storage systems
  10. Connected controls
  11. Indoor environmental quality control systems


2.3
Exemptions. This standard does not apply to transient housing, such as hotels, motels, nursing homes, jails, dormitories, and barracks.

2.4 Health, Safety, and Welfare. This standard shall not be used to abridge any safety, health, or environmental requirements.


ANSI/ASHRAE Standard 90.4-2025, Published standard. Supersedes ANSI/ASHRAE Standard 90.4-2022. 
Energy Standard for Data Centers 

1. Purpose
The purpose of this standard is to establish minimum energy efficiency requirements for the design, construction, and planned operation and maintenance of data centers, and to balance those requirements with related factors affecting the environment. Factors to be evaluated include the following: 

        1. Nonrenewable energy consumption 
        2. Renewable energy consumption 
        3. Water consumption 
        4. Greenhouse gas emissions 

2. Scope 

2.1 This standard applies to 

        1. New data centers, or portions thereof, and their systems; 
        2. New additions to data centers, or portions thereof, and their systems; and 
        3. Modifications to systems and equipment in existing data centers or portions thereof. 

2.2 The provisions of this standard do not apply to 

        1. Telephone exchanges, 
        2. Essential facilities, and 
        3. Information technology equipment (ITE). 

2.3 Where specifically noted in this standard, certain other buildings or elements of buildings shall be exempt. 

2.4 This standard shall not be used to circumvent any safety, health, or environmental requirements. 

SSPC 90.4
      1. to maintain and revise Standard 90.4. Standard placed on continuous maintenance August 2016.

ANSI/ASHRAE Standard 97-2007(RA2017) - Published standard. Supersedes ANSI/ASHRAE Standard 97-2007. 
Sealed Glass Tube Method to Test the Chemical Stability of Materials for Use Within Refrigerant Systems 

1. Purpose
The purpose of this standard is to establish a test procedure utilizing sealed glass tubes for the evaluation of materials for use in refrigerant systems. 

2. Scope

2.1 This standard describes the preparation of sealed glass tubes and the procedure for charging them with refrigerant, lubricant, other materials to be tested, or combinations of these. 

2.2 A procedure for aging the tubes, usually at elevated temperatures, is described. The tubes are evaluated by quantitative or qualitative analysis, or both, of the tube contents to yield information for determining the compatibility or chemical stability of materials to refrigerant systems. 

2.3 The technique described may be used for evaluating many different types of materials. Therefore, the standard does not describe in detail the preparation of the materials to be tested prior to placing them in the glass tubes, the conditions of exposure, nor the methods of analysis. 

2.4 Detailed safety precautions are included in Section 8, Safety Requirements. 

SPC 97-2007R
      1. – Revision project committee authorized 2/2/2011 (Las Vegas) with same TPS. 

ANSI/ASHRAE/IES 100-2024 - Published standard. Published standard. Supersedes ANSI/ASHRAE/IESNA Standard 100-2018.
Energy and Emissions Building Performance Standard for Existing Buildings

1. Purpose

1.1  This standard establishes building greenhouse gas (GHG) emissions and energy consumption performance levels for existing buildings. This standard provides compliance requirements that will result in improved energy efficiency and reduced GHG emissions of existing buildings.

1.2  This standard is directed toward

        1. Setting performance targets based on operational GHG emissions and energy consumption
        2. Accommodating progressively more stringent performance targets
        3. Providing a technical basis for setting building performance standards
        4. Providing procedures and programs essential to energy-efficient operation, maintenance, management, and monitoring

2. Scope

This standard applies to existing buildings, portions of buildings, and building complexes, including the envelope and all systems in the building. This standard excludes industrial and agricultural processes in buildings for which the energy consumption and emissions targets do not include those processes.

SSPC 100 
      1. to revise and maintain Standard 100. Standard 100 placed on continuous maintenance January 2015. 


ANSI/ASHRAE Standard 103-2022  - Published Standard. Supersedes ASHRAE Standard 103-2017. 
Method of Testing for Annual Fuel Utilization Efficiency of Residential Central Furnaces and Boilers 

1. Purpose
The purpose of this standard is to provide procedures for determining the annual fuel utilization efficiency of residential central furnaces and boilers. 

2. Scope

2.1 This standard includes: 

        1. a test method for cyclic and part-load performance, 
        2. methods for interpolating and extrapolating test data, and 
        3. calculation procedures for establishing seasonal performance. 

2.2 This standard applies to central furnaces with inputs less than 225,000 Btu/h and boilers with inputs less than 300,000 Btu/h, having gas, oil, or electric input, intended for use in residential applications. This standard also applies to furnaces with inputs less than 225,000 Btu/h contained within the same cabinet with central air conditioners that have rated cooling capacities of 65,000 Btu/h or less. This standard applies to equipment that utilizes single-phase electric current or low-voltage DC current. 

2.3 The procedures are intended to be used to compare energy consumption measures of various furnace and boiler models. They are not intended to provide an absolute measure of performance in any specific installation configuration since the effects of heating system installation variables are not fully taken into account. 


ANSI/ASHRAE Standard 105-2021 - Published standard. Supersedes ANSI/ASHRAE Standard 105-2014. 
Standard Methods for Determining, Expressing and Comparing Building Energy Performance and Greenhouse Gas Emissions 

1. Purpose

This standard provides consistent methods for determining and reporting the energy performance of buildings to facilitate a comparison of design and operation strategies in new and existing buildings as well as the development of building energy performance standards and reporting of greenhouse gas emissions associated with building operation. This standard provides consistent methods for determining, expressing, and comparing the energy performance of, and the greenhouse gas emissions associated with, the design of new buildings and improvements to, or changes in, the operation of existing buildings. 

2. Scope

2.1 This standard covers: 

        1. New buildings and existing buildings or portions thereof, 
        2. the determination and expression of building energy use and the greenhouse gas emissions associated with that energy use; and 
        3. techniques for the comparison of the energy performance and associated greenhouse gas emissions between different buildings, alternative designs for the same new building, or improvements in the operation of existing buildings. 

2.2 This standard does not: 

        1. Establish building energy or greenhouse gas emissions goals or limits, 
        2. present a method for certification of prediction methodology, such as computer program, 
        3. address embodied energy of building materials and systems, or 
        4. incorporate transportation energy or associated greenhouse gas emission for building functions, including commuting, business travel and process transportation 

ASHRAE Standard 110-2016 (RA 2025) - Published standard. Supersedes ASHRAE Standard 110-2016. 
Method of Testing Performance of Laboratory Fume Hoods 

1. Purpose
This standard specifies a quantitative and qualitative test method for evaluating fume containment of laboratory fume hoods. 

2. Scope

2.1 This method of testing applies to conventional, bypass, auxiliary-air, and VAV laboratory fume hoods. 

2.2 This method of testing is intended primarily for laboratory and factory testing but may also be used as an aid in evaluating installed performance. 

SPC 110-2016R
      1. Revision project committee authorized September 28, 2018 with the same TPS.

ANSI/ASHRAE Standard 111-2024 - Published standard. (Supersedes ANSI/ASHRAE Standard 111-2008 RA2017)  
Measurement, Testing, Adjusting and Balancing of Building Heating, Ventilation and Air-Conditioning Systems 

1. Purpose
To provide uniform procedures for measurement, testing, adjusting, balancing, evaluating, and reporting the performance of building heating, ventilating and air-conditioning systems in the field. 

2. Scope

2.1 This standard applies to building heating, ventilating and air-conditioning (HVAC) systems of the air-moving and hydronic types and their associated heat transfer, distribution, refrigeration, electrical power and control subsystems. 

2.2 This standard includes: 

        1. Methods for determining thermodynamic, hydraulic, hydronic, mechanical, and electrical conditions 
        2. Methods for determining room air change rates, room pressurization, and cross contamination of spaces 
        3. Procedures for measuring and adjusting outdoor ventilation rates to meet specified requirements 
        4. Methods for validating collected data while considering system effects 

2.3 This standard establishes 

        1. Minimum system configuration requirements to ensure that the system can be field-tested and balanced 
        2. Minimum instrumentation required for field measurements 
        3. Procedures for field measurements in HVAC testing and balancing and equipment testing 
        4. Formats for recording and reporting results
        5. The field data collected and reported under this standard is intended for use by building designers, operators and users, and by manufacturers and installers of HVAC systems 

ANSI/ASHRAE Standard 113-2022 - Published standard. Supersedes ANSI/ASHRAE Standard 113-2013. 
Method of Testing for Room Air Diffusion 

1. Purpose
The purpose of this standard is to define a repeatable method of testing the steady state air diffusion performance of an air distribution system in occupied zones of building spaces. This method is based on air velocity and air temperature distributions at specified heating or cooling loads and operating conditions. 

2. Scope

2.1 This standard specifies equipment and procedures for measuring air speed and air temperature in occupied zones of building spaces. 

2.2  This standard applies to furnished or unfurnished spaces (actual or mock-up), with or without occupants. 

2.3  This standard applies to air distribution systems, including systems in which: 

        1. air outlets are located inside, inside and outside, or outside of the occupied zone and 
        2. local air velocities in the occupied zone are, or are not, under control by individual occupants 

2.4 This standard does not cover 

        1. rating of individual air outlets and inlets or 
        2. naturally ventilated building spaces. 

ASHRAE Standard 116-2010 – Published standard. (Supersedes ANSI/ASHRAE Standard 116-1995 [RA 2005])
Methods of Testing for Rating Seasonal Efficiency of Unitary Air-Conditioners and Heat Pumps

1. Purpose
This standard provides test methods and calculational procedures for determining the capacities and cooling seasonal efficiency ratios for unitary air conditioning and heat pump equipment and heating seasonal performance factors for heat pump equipment.

2. Scope

2.1 This standard covers electrically driven, air-cooled air conditioners and heat pumps used in residential applications with cooling capacity of 65,000 Btu/h and less or in the case of heating only heat pumps, heating capacity of 65,000 Btu/h and less.

2.2 The methods of test in this standard are broadly applicable, but this standard provides cooling and heating hours in temperature bins for only the contiguous states of the continental U.S.A.

2.3 This standard includes test methods for steady-state, cyclic, and part load performance, and methods for establishing seasonal performance. Equipment with single-speed, multiple-speed, variable-speed, unloading, or multiple compressors for ducted and ductless systems is included.

2.4 This standard does not apply to room air conditioners. See ASHRAE Standards 16 and 58 in Appendix B, Bibliography.

SPC 37 
      1. responsible for revising Standard 116-2010. SPC 37 merged with SPC 116 on January 24, 2015.

      1. SPC 37 will develop a standard with a combined TPS.

ANSI/ASHRAE Standard 118.1-2022 - Published standard. Supersedes Standard 118.1-2012. 
Method of Testing for Rating Commercial Gas, Electric, and Oil Service Water Heating Equipment 

1. Purpose
The purpose of this standard is to provide test procedures for rating directly heated commercial service water heating equipment. 

2. Scope

2.1  This standard provides test procedures for determining the efficiency and hot-water delivery capability of the water heating equipment to which it applies 

2.2 This standard applies to electric resistance, heat-pump, natural- and propane-gas-fired, and oil-fired water heating equipment, including hot-water supply boilers, with input ratings less than 12,500,000 Btu/h (3660 kW) that are described by one or more of the following: 

        1. Gas-fired water heaters with a self-contained, temperature-activated primary operating control and not requiring circulation of water for heating, with rated input greater than 105,000 Btu/h (30.8 kW). 
        2. Oil-fired water heaters with a self-contained, temperature-activated primary operating control and not requiring circulation of water for heating, with rated input greater than 140,000 Btu/h (41 kW). 
        3. Electric resistance water heaters with a primary self-contained, temperature-activated operating control and not requiring circulation of water for heating, with rated input greater than 12 kW. 
        4. Gas-fired water heaters with a self-contained, flow-activated primary operating control and requiring water flow for heating, with rated input greater than 200,000 Btu/h (58.6 kW). Flow sensing may be based on physical flow measurement or interpretation of a temperature measurement as flow. 
        5. Oil-fired water heaters with a self-contained, flow-activated primary operating control and requiring water flow for heating, with rated input greater than 210,000 Btu/h (61.5 kW). Flow sensing may be based on physical flow measurement or interpretation of a temperature measurement as flow. 
        6. Electric resistance water heaters with a self-contained, flow-activated primary control and requiring water flow for heating, with rated input greater than 58.6 kW. 
        7. Gas-fired water heaters with a remote temperature-activated primary operating control and requiring circulation through the heater for heating, with rated input greater than 105,000 Btu/h (30.8 kW). 
        8. Oil-fired water heaters with a remote temperature-activated primary operating control and requiring circulation of water through the heater for heating, with rated input greater than 140,000 Btu/h (41 kW). 
        9. Electric resistance water heaters with a remote temperature-activated operating control and requiring circulation through the heater for heating, with rated input greater than 12 kW. 
        10. Air-source, water-source, and direct geoexchange heat-pump water heaters, with rated input greater than 12 kW for electric vapor-compression heat pumps, or with rated input greater than 20,000 Btu/h (5.9 kW) for gas-fired heat pumps. 
        11. Water heaters designed to deliver water at a controlled temperature greater than 180°F (82°C). 
        12. Water heaters with three-phase electrical supply. 
        13. Water heaters with rated storage capacity greater than 120 gal (454 L). 
        14. Gas-fired or oil-fired hot-water supply boilers with rated input equal to or greater than 300,000 Btu/h (87.9kW). 

ANSI/ASHRAE Standard 118.2-2022 Published standard. Supersedes ANSI/ASHRAE Standard 118.2-2006. 
Method of Testing for Rating Residential Water Heaters and Residential-Duty Commercial Water Heaters 

1. Purpose
The purpose of this standard is to provide test procedures for rating the efficiency and hot water delivery capabilities of directly heated residential water heaters and residential-duty commercial water heaters. 

2. Scope 
This standard applies to water heaters designed to be capable of providing outlet water at a controlled temperature of at least the nominal outlet water temperature under the conditions specified by this test. 

This standard applies to the following: 
2.1 Electric heat pump storage water heaters that: 

        1. use electricity as the energy source, 
        2. have a nameplate input rating of 12 kW (40,956 Btu/h) or less, 
        3. have a rated storage capacity of 120 gal (450 L) or less, 
        4. are designed to transfer thermal energy from one temperature level to a higher temperature level for the purpose of heating water, and 
        5. are designed to heat and store water at a thermostatically controlled temperature less than or equal to 180°F (82°C). 

2.2 Electric instantaneous water heaters that: 

        1. use electricity as the energy source, 
        2. have a nameplate input rating of 58.6 kW ( 200,000 Btu/h) or less, 
        3. contain no more than one gallon of water per 4,000 Btu per hour (3.2 litres of water per kilowatt) of input, and 
        4. are designed to provide outlet water at a controlled temperature less than or equal to 180°F (82°C). 

2.3 Electric storage water heaters that: 

        1. use electricity as the energy source, 
        2. have a nameplate input rating of 12 kW (40,956 Btu/h) or less, 
        3. have a rated storage capacity of 120 gallons (450 liters) or less, 
        4. contain more than one gallon of water per 4000 Btu per hour (3.2 litres of water per kilowatt) of input, and 
        5. are designed to heat and store water at a thermostatically controlled temperature less than or equal to 180°F (82°C). 

2.4 Gas-fired heat pump storage water heaters that: 

        1. use gas as the main energy source, 
        2. have a nameplate input rating of 20,000 Btu/h (26.4 MJ/h) or less, 
        3. have a maximum current rating of 24 amperes (including all auxiliary equipment such as fans, pumps, controls, and, if on the same circuit, any resistive elements) at an input voltage of no greater than 250 volts, 
        4. have a rated storage volume not more than 120 gallons (450 liters), and 
        5. are designed to transfer thermal energy from one temperature level to a higher temperature level to deliver water at a thermostatically controlled temperature less than or equal to 180°F (82°C). 

2.5 Gas-fired instantaneous water heaters that: 

        1. use gas as the main energy source, 
        2. have a nameplate input rating less than 200,000 Btu/h (210 MJ/h), 
        3. contain no more than one gallon of water per 4,000 Btu per hour of input, and 
        4. are designed to provide outlet water at a controlled temperature less than or equal to 180°F (82°C). 

2.6 Gas-fired storage water heaters that: 

        1. use gas as the main energy source, 
        2. have a nameplate input rating of 105,000 Btu/h (110 MJ/h) or less, 
        3. have a rated storage capacity of 120 gallons (450 liters) or less, 
        4. contain more than one gallon of water per 4,000 Btu per hour of input, and 
        5. are designed to heat and store water at a thermostatically-controlled temperature less than or equal to 180°F (82°C). 

2.7 Oil-fired instantaneous water heaters that: 

        1. use oil as the main energy source, 
        2. have a nameplate input rating of 210,000 Btu/h (220 MJ/h) or less, 
        3. contain no more than one gallon of water per 4,000 Btu per hour of input, and 
        4. are designed to provide outlet water at a controlled temperature less than or equal to 180°F (82°C). 

2.8 Oil-fired storage water heaters that: 

        1. use oil as the main energy source, 
        2. have a nameplate input rating of 140,000 Btu/h (148 MJ/h) or less, 
        3. have a rated storage capacity of 120 gallons (450 liters) or less, 
        4. contain more than one gallon of water per 4,000 Btu per hour of input, and 
        5. are designed to heat and store water at a thermostatically-controlled temperature less than or equal to 180°F (82°C). 

ANSI/ASHRAE Standard 120-2022 – Published standard. Supersedes ANSI/ASHRAE Standard 120-2008.
Method of Testing to Determine Flow Resistance of HVAC Ducts and Fittings 

1. Purpose
This standard establishes uniform methods of laboratory testing of HVAC ducts and fittings to determine their resistance to airflow. 

2. Scope

2.1 This standard may be used to determine the change in total pressure resulting from airflow in HVAC ducts and fittings. 

2.2 The test results can be used to determine duct flow losses in pressure loss per unit length. Fitting losses are reported as local loss coefficients. 

2.3 This standard does not cover interpretation of the test data. 


ANSI/ASHRAE Standard 124-2007 (RA 2026) - Published standard. Supersedes ANSI/ASHRAE Standard 124-2007. 
Methods of Testing for Rating Combination Space-Heating and Water-Heating Appliances 

1. Purpose
The purpose of this standard is to establish a method of test to rate the performance of a combination space-heating and water-heating appliance. 

2. Scope

2.1 This test method is intended to cover electric, gas-fired, and oil-fired combination space-heating and water-heating appliances. 

2.2 This standard covers appliances up to 300,000 Btu/h (87.9 kW) rated input. 

SPC 124-2007R
      1. – Revision project committee authorized 2/2/2011 (Las Vegas) with same TPS

ANSI/ASHRAE Standard 125-2020 - Published standard. Supersedes ANSI/ASHRAE Standard 125-2016. 
Method of Testing Thermal Energy Meters for Liquid Streams in HVAC Systems 

1. Purpose
The purpose of this standard is to provide a method of testing factory-assembled thermal energy meters used to measure the thermal energy added to or extracted from a liquid stream supplying an HVAC system. 

2. Scope 

2.1 The test methods, procedures and facility descriptions in this standard are intended for use in determining measurement accuracy, pressure losses, service flow rate limits, temperature difference limits, and reliability effects of mounting attitude. 

2.2 This standard is limited to applications in which the fluid remains in a completely liquid state while traversing the thermal energy meter. 

2.3 The applications of this standard include, but are not limited to, thermal energy meters used for billing or revenue metering for hydronic applications. 

2.4 This standard does not apply to meters using principles of change-of-state of the fluid, simple elapsed time, or measured indoor or outdoor temperature difference to allocate consumption among various end-use consumers. 


ANSI/ASHRAE/SMACNA 126-2020 –Published standard. Supersedes ANSI/ASHRAE/SMACNA Standard 126-2016. 
Methods of Testing HVAC Air Ducts 

1. Purpose
This standard provides laboratory test procedures for the evaluation of HVAC air ducts 

2. Scope

2.1 This standard includes procedures to determine the structural strength, dimensional stability, durability, and leakage characteristics of HVAC air ducts.

2.2 This standard does not cover: 

        1. fittings 
        2. effects of aerosols, solid particulates, corrosive environments, or combustibility 
        3. long-term effects of extended service 
        4. seismic qualifications 
        5. underground ducts 
        6. plenums and equipment casings 
        7. supports for ductwork and fittings 

SPC 126-2020R - Revision project committee authorized September 27, 2023 with same TPS. 


ANSI/ASHRAE Standard 127-2020 -  Published Standard. Supersedes ANSI/ASHRAE Standard 127-2012.
Method of Testing for Rating Air-Conditioning Units Serving Data Center (DC) and Other Information Technology Equipment (ITE) Spaces 

1. Purpose

The purpose of the standard is to establish a uniform set of test requirements for rating air-conditioning units that are applied in data center (DC) and other information technology equipment (ITE) spaces. 

2. Scope

2.1 This standard applies to classes of air-conditioning units that are used to air condition data center (DC) and other information technology equipment (ITE) spaces. Such units must be able to be tested using an air enthalpy method and facilitate heat transfer across at least one heat exchanger. 

2.2 Exclusions 

        1. Rating of individual assemblies, such as condensing units 
        2. Cooling heat exchangers within ITE products 
        3. Heat-operated equipment (e.g., adsorption and absorption devices) 
        4. Vapor compression variable-refrigerant flow serving multiple evaporators 
        5. Source cooling equipment (e.g., chiller units for either water or refrigerant) 

ANSI/ASHRAE Standard 127-2020. Revised TPS approved April 24, 2023.
Method of Testing for Rating Cooling Equipment Serving Data Center (DC) and Other Information Technology Equipment (ITE) Spaces
 

1. Purpose
The purpose of the standard is to establish a uniform method of test requirements for rating cooling equipment that is applied in data center (DC) and other information technology facilities, spaces, and equipment. 

2. Scope
This standard applies to classes of cooling equipment that are used to remove thermal loads in data center (DC) and other information technology facilities, spaces, and equipment. 

SSPC 127 to maintain and revise Standard 127. Standard placed on continuous maintenance December 2020. Revised TPS approved April 24, 2023.
Method of Testing for Rating Cooling Equipment Serving Data Center (DC) and Other Information Technology Equipment (ITE) Spaces 

1. Purpose
The purpose of the standard is to establish a uniform method of test requirements for rating cooling equipment that is applied in data center (DC) and other information technology facilities, spaces, and equipment.

2. Scope
This standard applies to classes of cooling equipment that are used to remove thermal loads in data center (DC) and other information technology facilities, spaces, and equipment.


ANSI/ASHRAE Standard 128-2018 - Published standard. Supersedes ANSI/ASHRAE Standard 128-2011. 
Method of Rating Portable Air Conditioners 

1. Purpose
The purpose of this standard is to establish a uniform set of requirements for rating the cooling capacity of portable air conditioners. 

2. Scope

2.1 This standard is applicable to commercial-type portable air-conditioning units with a rated cooling capacity of 65,000 Btu/h (19,000 W) and greater, including those with heating capacity. 

2.2 The standard does not apply to 

        1. the testing and rating of individual assemblies, such as condensing units or direct expansion fan-coil units for separate use; 
        2. computer or data-processing-room air conditioners within the scope of ASHRAE Standard 127 1; or 
        3. room air conditioners within the scope of CAN/CSAC368.12  or AHAM RAC-13. 

SPC 128-2018R - Revision project committee authorized September 27, 2023 with same TPS. 


ASHRAE Standard 129-1997 (RA 2002) – Published standard. Supersedes ANSI/ASHRAE Standard 129-1997. 
Measuring Air-Change Effectiveness 

1. Purpose

This standard prescribes a method for measuring air-change effectiveness in mechanically ventilated spaces and buildings that meet specified criteria. The air-change effectiveness is a measure of the effectiveness of outdoor air distribution to the breathing level within the ventilated space. 

2. Scope

2.1 The method of measuring air-change effectiveness compares the age of air where occupants breathe to the age of air that would occur throughout the test space if the indoor air were perfectly mixed. 

2.2 The standard includes measurement procedures and criteria for assessing the suitability of the test space for measurements of air-change effectiveness. 

SPC 129R - Revision project committee authorized June 2020. Revised TPS approved February 7, 2023. 
Estimation of Ventilation Effectiveness for Ventilated Indoor Spaces 

1. Purpose
This standard prescribes a method for measuring and estimating ventilation effectiveness for ventilated spaces using tracer gas techniques and computational fluid dynamics (CFD) analyses.

2. Scope

2.1. The standard addresses various measures of ventilation effectiveness.

2.2. The standard includes laboratory testing, field testing, and CFD analysis.

2.3. The standard provides techniques for estimating ventilation effectiveness during design, commissioning, and operation of indoor air environments.


ANSI/ASHRAE Standard 130-2025 –Published standard. Supersedes ANSI/ASHRAE Standard 130-2016. 
Laboratory Methods of Testing Air Terminal Units 

1. Purpose            
This standard specifies instrumentation, test installation methods, and procedures for measuring the capacity and related performance of constant volume, variable volume, and modulating integral diffuser air terminals. 

2. Scope 

2.1 The methods of test in this standard apply to air control devices used in air distribution systems. These devices provide control of air volume with or without temperature by one or more of the following means and with or without a fan: 

        1. Fixed or adjustable directional vanes (i.e. bypass terminal) 
        2. Pressure dependent volume dampers or valves (including air induction nozzles and dampers) 
        3. Pressure independent volume dampers or valves (including air induction nozzles and dampers) 
        4. Integral heat exchanger 
        5. On/off fan control 
        6. Variable-speed fan control 
        7. Modulating integral diffuser terminals 

2.2 This standard covers test methods for use in determining the following performance characteristics: 

        1. Sound 
        2. Temperature mixing and stratification 
        3. Minimum operating pressure 
        4. Air leakage 
        5. Induced airflow 
        6. Fan performance 
        7. Condensation 
        8. Airflow sensor performance 
        9. Pressure Independence 

2.3 This standard shall not be used for field testing. 


ANSI/ASHRAE Standard 133-2024 – Published standard. Supersedes ANSI/ASHRAE Standard 133-2015.  
Method of Testing Direct Evaporative Air Coolers 

1. Purpose
This standard establishes a uniform method of laboratory testing for rating packaged and component direct evaporative air coolers. 

2. Scope

2.1 The scope of this standard covers a method of testing for rating the saturation effectiveness, airflow rate, and total power of packaged and component direct-evaporative air coolers. 

2.2 Covered tests also include methods for measuring static pressure differential of the direct evaporative air cooler, density of the air, and speed of rotation of the fan. 

2.3 This standard requires that packaged and component direct evaporative air coolers are simultaneously tested for airflow, total power, and saturation effectiveness. 

2.4 The ratings resulting from application of this standard are intended for use by manufacturers, specifiers, installers, and users of evaporative air cooling apparatus for residential, commercial, agricultural and industrial ventilation; air cooling applications; and for commercial, industrial, and agricultural processing applications. 


ANSI/ASHRAE Standard 135-2024 - Published standard. Supersedes ANSI/ASHRAE Standard 135-2020. 
BACnet - A Data Communication Protocol for Building Automation and Control Networks 

1. Purpose
This standard defines data communication services and protocols for computer equipment used for monitoring and control of HVAC&R and other building systems and to define, in addition, an abstract, object-oriented representation of information communicated between such equipment, thereby facilitating the application and use of digital control technology in buildings. 

2. Scope

2.1 This protocol provides a comprehensive set of messages for conveying encoded binary, analog, and alphanumeric data between devices including, but not limited to: 

        1. hardware binary input and output values, 
        2. hardware analog input and output values, 
        3. software binary and analog values, 
        4. text string values, 
        5. schedule information, 
        6. alarm and event information, 
        7. files, and 
        8. control logic. 

2.2 This protocol models each building automation and control computer as a collection of data structures called 'objects,' the properties of which represent various aspects of the hardware, software, and operation of the device. These objects provide a means of identifying and accessing information without requiring knowledge of the details of the device's internal design or configuration. 

SSPC 135 to maintain and revise Standard 135. Standard on continuous maintenance. 
BACnet - A Data Communication Protocol for Building Automation and Control Networks 


ANSI/ASHRAE Standard 135.1-2023 – Published Standard. Supersedes ANSI/ASHRAE Standard 135.1-2019. 
Method of Test for Conformance to BACnet 

1. Purpose
To define a standard method for verifying that an implementation of the BACnet protocol provides each capability claimed in its Protocol Implementation Conformance Statement (PICS) in conformance with the BACnet standard. 

2. Scope
This standard provides a comprehensive set of procedures for verifying the correct implementation of each capability claimed on a BACnet PICS including: 

        1. support of each claimed BACnet service, either as an initiator, executor, or both, 
        2. support of each claimed BACnet object-type, including both required properties and each claimed optional property, 
        3. support of the BACnet network layer protocol, 
        4. support of each claimed data link option, and 
        5. support of all claimed special functionality. 

SSPC 135 to maintain and revise Standard 135.1. Standard on continuous maintenance. 


ANSI/ASHRAE Standard 138-2021 - Published standard. Supersedes ANSI/ASHRAE Standard 138-2013. 
Method of Testing for Rating Ceiling Panels for Sensible Heating and Cooling 

1. Purpose
This standard establishes uniform methods of laboratory testing for rating steady-state thermal performance of ceiling panels used in indoor spaces for sensible heating or sensible cooling or both. The objective is to rate ceiling panels under repeatable conditions. 

2. Scope

2.1 This standard specifies procedures, apparatus, and instrumentation for rating thermal performance of ceiling panels in a specific indoor configuration and thermal conditions. 

2.2 Thermal performance of a ceiling panel is measured in terms of heat delivered or heat removed by the ceiling panel surface as a function of average fluid temperature of the heat transfer medium in the ceiling panel, and the temperatures characterizing the surrounding indoor space. 

2.3 This standard covers testing of ceiling panels in the following effective panel surface high and low temperature range limits: 

        1. Sensible Heating Panels: from 24° C (75° F) to 65° C (49° F) for nonmetal heat transfer elements in the ceiling panel or from 24° C (75° F) to 150° C (302° F) for metal heat transfer elements in the ceiling panel. 
        2. Sensible Cooling Panels from 14° C (57° F) to 24°C (75°F) 

2.4 This standard does not cover the following ceiling panels: 

        1. hybrid (combined thermal radiation and forced-convection) ceiling panels, 
        2. ceiling panels that are embedded into the ceiling, wall, or floor structure, or 
        3. test methods for design, production, or field testing of ceiling panels. 

ANSI/ASHRAE Standard 139-2025 – Published standard. Supersedes ANSI/ASHRAE Standard 139-2015. 
Method of Testing for Rating Desiccant Dehumidifiers Utilizing Heat for the Regeneration Process 

1. Purpose
The purpose of this standard is to provide test methods for determining the moisture removal capacity of heat-regenerated desiccant dehumidifiers as well as the coincident thermal energy performance so that comparative evaluations of capacity and performance can be made irrespective of the type or make of the device. 

2. Scope

2.1 This standard applies to desiccant based dehumidifiers operating at atmospheric pressure. The dehumidifier may utilize solid or liquid desiccants that are regenerated utilizing heat energy. 

2.2 Normally, equipment within this standard would consist of one or more desiccant contact stations through which the air to be dehumidified is moved, a means to expose the moisture-laden desiccant to a source of heat energy for regeneration, and a heating device. 

2.3 Ancillary devices are normally utilized to move air to be dehumidified through the device and provide ventilation for regeneration, but they are not a part of this standard. 

2.4 This standard is intended to: 

        1. Describe a uniform method of testing for obtaining performance data 
        2. Describe and specify test instruments and apparatus, 
        3. Describe and specify test data to be recorded, and 
        4. Describe and specify calculations to be made from test data. 

2.5 This standard does not apply to: 

        1. Dehumidifiers operating at other than atmospheric pressure, 
        2. Dehumidifiers not utilizing a desiccant for dehumidification, 
        3. Dehumidifiers not utilizing heat for regeneration of the desiccant,  
        4. Ancillary equipment which may be used in any dehumidification process such as fans, pre or post conditioning equipment, or, 
        5. Dehumidifiers using a sealing arrangement that results in leakage rates in excess of 1% of process flow. 

ANSI/ASHRAE/IBPSA Standard 140-2023 - Published standard. Supersedes ANSI/ASHRAE Standard 140-2020.) IBPSA is a cosponsor of this standard.
Method of Test for Evaluating Building Performance Simulation Software 

1. Purpose
This standard specifies test procedures for evaluating the technical capabilities and ranges of applicability of software that simulate the performance of buildings and their systems. 

2. Scope
These standard test procedures apply to software that simulate the performance of a building and its systems. While these standard test procedures cannot test all algorithms within a building performance simulation software, they can be used to indicate major flaws or limitations in capabilities. 


ANSI/ASHRAE Standard 143-2024 – Published Standard. Supersedes ANSI/ASHRAE Standard 143-2015
Method of Test for Indirect Evaporative Air Coolers. 

1. Purpose
This standard provides laboratory test procedures and calculations for establishing the cooling capacities and power requirements for indirect evaporative air-cooling equipment.

2. Scope: 

2.1 This standard applies to testing indirect evaporative air coolers that are operating under steady-state conditions that:

  1. sensibly cool a primary airstream through heat exchanger(s) by the evaporation of water into a secondary airstream, and
  2. are packaged systems or are components of packaged systems.

2.2 This standard does not apply to:

  1. devices that use mechanical refrigeration or thermal storage to cool the primary airstream, the secondary airstream or the water provided for evaporation during the test, or
  2. devices that dry the primary or secondary airstream during the test.

ANSI/ASHRAE Standard 145.1-2024 Published Standard. Supersedes ANSI/ASHRAE Standard 145.1-2015. 
Laboratory Test Method for Assessing the Performance of Gas-Phase Air- Cleaning Systems: Loose Granular Media 

1. Purpose
To provide a standard laboratory test method for assessing the performance of loose granular media used in gas-phase air cleaning systems. The results of these tests can provide information to the engineer useful for the design and selection of air cleaning equipment and the design of air cleaning systems for controlling indoor concentrations of gaseous air contaminants. 

2. Scope

2.1 This standard prescribes a small-scale laboratory test method for measuring the contaminant removal efficiency of loose granular sorptive media used in gas-phase air cleaning equipment as installed (in a test apparatus) in an airstream and challenged with test gases under steady-state conditions. This test is conducted at elevated gas challenge concentrations (relative to ventilation applications) and therefore should be used to compare media rather than directly predict performance in any particular application. 

2.2 The standard defines methods of calculating and reporting results obtained from the test data and establishes a results reporting system that can be applied to loose granular media covered by this standard. 

2.3 This standard does not apply to: 

  1. bonded carbon panels, beaded activated carbon, carbon cloths, absorbent loaded nonwovens, dry process carbon composites or 
  2. particulate removal equipment 

SSPC 145 to maintain and revise Standard 145.1. Standard on continuous maintenance. Standard 145.1 placed on continuous maintenance June 2011, Montreal. 
Test Method for Assessing the Performance of Gas-Phase Air Cleaning Equipment 


ANSI/ASHRAE Standard 145.2-2025 – Published Standard. Supersedes Standard 145.2-2016 
Laboratory Test Method for Assessing the Performance of Gas-Phase Air Cleaning Systems: Air Cleaning Devices 

1. Purpose
The purpose of this standard is to provide a standard laboratory test method for assessing the performance of gas-phase air-cleaning devices. The results of these tests can provide information to the engineer useful for the design and selection of air-cleaning equipment and the design of air-cleaning systems for controlling indoor concentrations of gaseous air contaminants. 

2. Scope 

2.1 This standard prescribes a full-scale laboratory test method for measuring the performance of in-duct gas-phase air-cleaning devices. This test is conducted under steady-state conditions at elevated gas challenge concentrations (relative to ventilation applications) and, therefore, shall be used to compare devices rather than directly predict performance in any particular application. 

2.2 The method of testing measures the performance of air-cleaning devices for removing one or more specified gaseous contaminants or gas mixtures intended to simulate operation during service life. The standard defines procedures for the dispersion of the gases required for conducting the test. It also provides a method for determining gas concentrations upstream and downstream of the air-cleaning device to calculate removal efficiency. 

2.3 This standard establishes performance specifications for the equipment required to conduct the tests, defines methods of calculating and reporting results obtained from the test data, and establishes a results reporting system that can be applied to the gas-phase air-cleaning devices covered by this standard. 

2.4 The test method defined by this standard is applied to a sample device that is assumed to be representative of other devices marketed with the same brand and model number. 

2.5 This standard does not apply to stand-alone room air cleaners. 

SSPC 145 to maintain and revise Standard 145.2. Standard on continuous maintenance. Standard 145.2 placed on continuous maintenance June 2011, Montreal.  
Test Method for Assessing the Performance of Gas-Phase Air Cleaning Equipment 


ASHRAE Standard 145.4P - Proposed Standard authorized June 2022. Standard 145.4P to be developed by SSPC 145.
Method of Test for Assessing the Gas-Phase Performance of Air Cleaning Devices and Systems in a Duct-Chamber Apparatus

1. Purpose
To provide a laboratory test method for evaluating air cleaning devices for challenge gas removal in a combined duct-chamber system with continuous recirculation.

2. Scope

2.1 This standard specifies a duct-chamber test method with continuous recirculation through the duct and chamber for measuring the performance of:

  1. in-duct air cleaning devices of any size
  2. in-room air cleaning devices used in commercial or industrial spaces

2.2 The test method measures the performance of air cleaning devices for removing challenge gases.

2.3 This test method is conducted at elevated challenge gas concentrations (relative to ventilation applications) and therefore should be used to compare devices rather than directly predict performance in real world applications. The challenge gas and likely byproducts will be measured over time.

2.4 Air cleaner performance is defined as the total impact of the air cleaner on the challenge gas in the chamber air and including any gaseous or particulate byproducts.

2.5 This standard provides performance specifications for the equipment and measurements required to conduct the test method, defines procedures for calculating and reporting results and provides a results reporting system.

2.6 This standard does not address the health and safety effects of operating devices and systems in an occupied room.


ANSI/ASHRAE Standard 146-2020 –– Published standard. Supersedes ANSI/ASHRAE Standard 146-2011. 
Methods of Test for Rating Pool Heaters 

1. Purpose
The purpose of this standard is to provide methods of testing for rating pool heaters. 

2. Scope

2.1 This standard provides methods of testing for heating capacity and energy efficiency. 

2.2 This standard applies to forced circulation heaters operated by gas, oil, and/or electricity, including heat pumps using ambient air, earth, water or a brine solution as a heat source, and hybrid heaters. 


ANSI/ASHRAE Standard 147-2019 - Published standard. Supersedes ASHRAE Standard 147-2013
Reducing the Release of Halogenated Refrigerants from Refrigerating and Air-Conditioning Equipment and Systems 

1. Purpose
This standard establishes practices and procedures that will reduce inadvertent release of halogenated refrigerants. 

2. Scope
The practices and procedures in this standard cover release reduction of halogenated hydrocarbon and halogenated ether refrigerants in the following circumstances: 

  1. from stationary refrigeration, air-conditioning, and heat-pump equipment and systems; 
  2. during manufacture, installation, testing, operation, maintenance, repair, and disposal of equipment and systems. 

SSPC 147 to revise and maintain Standard 147. Standard 147 placed on continuous maintenance September 26, 2013


ANSI/ASHRAE Standard 150-2025 – Published standard. Supersedes ANSI/ASHRAE Standard 150-2019 (RA2004). 
Methods of Testing the Performance of Installed Cool-Storage Systems 

1. Purpose
This standard prescribes a uniform set of testing procedures for determining the performance of installed cool-storage systems, including cooling capacities, efficiencies, flows, peak and key charging and discharging, and other performance requirements. 

2. Scope

2.1 This standard covers cool-storage systems composed of chillers, storage medium, storage device or vessel, heat sink equipment or heat sink systems, and other auxiliary equipment required to provide a complete and working system. The standard is limited to daily loads, weekly loads, and short-term industrial or food industry loads. 

2.2 This standard includes the following: 

  1. Three uniform methods of testing:
    1. Method 1—base acceptable testing of latent ice storage systems
    2. Method 2—base acceptable testing of sensible stratified chilled water or low-temperature fluids systems
    3. Method 3—enhanced performance test
  2. Identification of test equipment for performing such tests
  3. Identification of data required and calculations to be used
  4. Definitions and terminology 

2.3 This standard does not cover the following: 

  1. Testing of the air-side distribution 
  2. Seasonal storage systems 
  3. Warm-storage systems 

ANSI/ASHRAE Standard 153-2021 - Published standard. Supersedes ASHRAE Standard 153-2015. 
Method of Test for Mass Flow Capacity of Four-Way Refrigerant Reversing Valves 

1. Purpose
The purpose of this standard is to provide a test method for measuring the refrigerant vapor mass flow capacity of four-way refrigerant reversing valves. The standard aims to measure mass flow capacity with sufficient accuracy to facilitate application decisions. 

2. Scope
This standard describes test methods, procedures, instrumentation, computations, and suggested apparatus for this test 

SPC 153-2021R - Revision project committee authorized October 18, 2024 with the same TPS. 


ANSI/ASHRAE  Standard 154-2022 - Published standard. Supersedes ANSI/ASHRAE Standard 154-2016. 
Ventilation for Commercial Cooking Operations 

1. Purpose
The purpose of this standard is to provide design criteria for the performance of commercial cooking ventilation systems. 

2. Scope

2.1 This standard covers 

  1. Kitchen hoods 
  2. Exhaust systems, and 
  3. Replacement air systems 

2.2 This standard shall not be used to circumvent any safety, health or environmental requirement. 

SSPC 154 to maintain and revise Standard 154. Standard on continuous maintenance. SSPC 154 authorized 10/1/2010. 


ANSI/ASHRAE/AHRI Standard 155-2024 - Published Standard. 
Method of Testing for Rating Commercial Space Heating Boiler Systems 

1.  Purpose
This standard provides procedures for determining the steady-state thermal efficiency, part-load efficiency, and idling energy input rate of space heating boilers. 

2.  Scope

2.1  This standard applies to steam and hot water boiler systems (individual, modular or multiple boilers) for use in space heating applications and having individual boilers or modules with gas, oil, electric or multiple fuel inputs of at least 300,000 Btu/h (87.92kW) but no more than 12,500,000 Btu/h (3664 kW). 

Exception to 2.1:  Custom-designed, field-assembled boilers are not covered by this standard. 

2.2  This standard provides methods to compare energy consumption measures of various boiler systems.  It is not intended to provide an absolute measure of performance in any specific installation configuration. 

2.3  This standard includes:

  1. test methods for determining full load and part load steady state thermal efficiency, idling energy input rate and throughflow loss rate of individual boilers,
  2. methods for interpolating and extrapolating test data,
  3. rating conditions to be used in executing tests and calculations for a range of classes of spaceheating applications. 

2.4  This standard applies to the space heating performance of boiler systems used for multiple functions including space heating. 

2.5  This standard does not cover methods of testing boiler systems used only in service water heating applications. 


ANSI/ASHRAE Standard 158.1-2024 – Published standard. (Supersedes ANSI/ASHRAE Standard 158.1-2019) 
Methods of Testing Capacity of Refrigerant Solenoid Valves 

1. Purpose

This standard prescribes a method of testing the capacity of refrigerant solenoid valves for use in refrigerating systems. 

2. Scope

2.1 This standard is applicable to refrigerant solenoid valves in the following circumstances: 

  1. as defined in Section 3, 'Definitions,' 
  2. for either liquid or vapor refrigerant applications, and 
  3. to be used with refrigerants deemed available and suitable according to ANSI/ASHRAE Standard 151 Safety Standard for Refrigeration Systems, and ANSI/ASHRAE Standard 342, Designation and Safety Classification of Refrigerants. 

2.2 This standard specifies procedures, apparatus, and instrumentation that will produce accurate capacity data. 

2.3 This standard does not do the following:

  1. specify rating conditions or electrical or mechanical design requirements (Rating conditions may be found in ANSI/AHRI Standard 760, Performance Rating of Solenoid Valves for Use with Volatile Refrigerants, for I-P units, or ANSI/AHRI Standard 761, Performance Rating of Solenoid Valves for Use with Volatile Refrigerants, for SI units.)
  2. make recommendations for safety 
  3. specify tests for production, specification compliance, or field testing of solenoid valves. 

ANSI/ASHRAE Standard 158.2-2024 - Published standard. Supersedes ANSI/ASHRAE Standard 158.2-2018)
Methods of Testing Capacity for Refrigerant Pressure Regulators 

1. Purpose 
This standard provides methods of determining the mass flow capacity of refrigerant pressure regulators with sufficient accuracy to facilitate proper engineering application of the device in systems operating at various conditions with various refrigerants by 

  1. prescribing a method of measuring key flow and gradient characteristics of refrigerant pressure regulators using air or water as the working fluid and 
  2. prescribing computational means to enable reliable prediction of refrigerant vapor and liquid mass flow capacity based on the measured flow and gradient characteristics. 

2. Scope

2.1 This standard applies to refrigerant pressure regulators that meet the definition found in Section 3, and that are intended for refrigerant service in applications where only single-phase flow occurs within the regulator. 

2.2 This standard is applicable to refrigerant pressure regulators  

  1. for use in either liquid or vapor refrigerant applications, and 
  2. for use with refrigerants deemed suitable according to ANSI/ASHRAE Standard 151,  and ANSI/ASHRAE Standard 34-20042 

2.3 This standard specifies procedures, apparatus and instrumentation that will produce capacity and gradient information with sufficient accuracy to support the proper application of the tested regulator. 

2.4 This standard does not 

  1. specify rating conditions or electrical or mechanical design requirements (rating conditions may be found in ARI Standard 7703) or 
  2. make recommendations for safety, or 
  3. specify tests for production, specification compliance, or field testing of regulators. 

ANSI/ASHRAE Standard 160-2021 - Published standard. Supersedes ANSI/ASHRAE Standard 160-2016. 
Criteria for Moisture-Control Design Analysis in Buildings 

1. Purpose
The purpose of this standard is to specify performance-based design criteria for predicting, mitigating or reducing moisture damage to the building envelope, materials, components, systems and furnishings, depending on climate, construction type, and HVAC system operation. These criteria include the following: 

  1. criteria for selecting analytic procedures 
  2. criteria for inputs 
  3. criteria for evaluation and use of outputs 

2. Scope: 

2.1 This standard applies to the design of new buildings and to the retrofit and renovation of existing buildings. 

2.2 This standard applies to all types of buildings, building components, and materials. 

2.3 This standard applies to all interior and exterior zones and building envelope cavitiesB-1. 

2.4 This standard does not directly apply to thermal comfort or acceptable indoor air qualityB-1. 

2.5 This standard does not address the design of building components or envelopes to resist liquid water leakage from sources such as rainwater, ground water, flooding or ice damsB-1. 

Informative Note: All superscript notes such as B-1, B-2, and so forth refer to informative commentary on the standard that is contained in Informative Appendix B. 

SSPC 160 to maintain and revise Standard 160. Standard on continuous maintenance.


ANSI/ASHRAE Standard 161-2023 - Published standard. Supersedes ASHRAE Standard 161-2018
Air Quality Within Commercial Aircraft 

1. Purpose
This standard defines the requirements for air quality in air-carrier aircraft and specifies methods for measurement and testing in order to establish compliance with the standard. 

2. Scope

2.1 This standard applies to commercial passenger air-carrier aircraft carrying 20 or more passengers and certified under Title 14 CFR Part 251. 

2.2 This standard considers chemical, physical, and biological contaminants as well as moisture, temperature, pressure and other factors that may affect air quality. 

2.3 Because this standard cannot take into account every variable, especially those relating to safe operation of the aircraft, the diversity of sources and types of contaminants in aircraft cabin air, and the range of susceptibility in the population, compliance with this standard will not necessarily ensure acceptable aircraft cabin air quality for everyone. 

SSPC 161 to maintain and revise Standard 161. Standard placed on continuous maintenance in 6/2007. 


SSPC 164 approved June 26, 2020 to maintain and revise each of the 164 series individual standards. (Standards are on Periodic Maintenance). 
Methods of Test for Humidifiers  

ANSI/ASHRAE Standard 164.1-2025 Published standard. Supersedes ASHRAE Standard 164.1-2012 (RA2016). 
Method of Test for Residential Central-System Humidifiers 

1. Purpose 

 This standard establishes a uniform method of laboratory testing for rating central-system residential humidifiers. 

2. Scope

2.1 The scope of this standard covers a method of test for the humidification rate of central-system residential humidifiers intended for use with forced warm air heating and/or cooling systems. 

2.2 This method of test describes the test apparatus, conduct of the test, and information to be recorded. 

2.3 Tests covered include methods for measuring electrical power input, water flow rate, water temperature, and water pressure to the test humidifier. Also included are airflow rate, static pressure, temperature and relative humidity entering and maintained by the test apparatus. 

2.4 Information resulting from the application of this method of test is intended for use by manufacturers, specifiers, installers, and users of central-system residential humidifiers. 

2.5 This method of test does not apply to self-contained humidifiers, portable humidifiers, or humidifiers for commercial and industrial applications. 


ANSI/ASHRAE Standard 164.2-2012 (RA2026) Published standard. Supersedes ASHRAE Standard 164.2-2012 (RA2016). 
 Method of Test for Residential Self-Contained Humidifiers 

1. Purpose
This standard establishes a method of test for the humidification rate and power input of self-contained humidifiers for whole house applications. 

2. Scope

2.1 The scope of this standard covers a method of test for the humidification rate and power input of self-contained humidifiers for whole house applications. 

2.2 This method of test describes the test apparatus, conduct of the test, and information to be recorded. 

2.3 Tests covered include methods for measuring energy input, water flow rate, water temperature, and water pressure to the test humidifier. 


ASHRAE Standard 164.3-2015 - Published standard 
Method of Test for Commercial and Industrial Isothermal Humidifiers 

1. Purpose
This standard method of test establishes a uniform method of laboratory testing for rating commercial and industrial isothermal humidifiers. 

2. Scope 

2.1 The scope of this standard covers a method of test for the humidification rate of factory made commercial and industrial isothermal humidifiers. 

2.2 This method of test describes the test apparatus, conduct of the test, and information to be recorded. 

2.3 Information resulting from the application of this method of test is intended for use by manufacturers, specifiers, installers, and users of commercial and industrial isothermal humidifiers. 

Standard 164.3-2015R is being revised by SSPC 164. Revision project authorized December 18, 2019 with the same TPS.


ANSI/ASHRAE Standard 164.4-2021 - Published Standard. 
Methods of Test for Commercial and Industrial Adiabatic Humidifiers 

1. Purpose
This standard method of test establishes a uniform method of laboratory performance testing of commercial and industrial adiabatic humidifiers. 

2. Scope

2.1 This standard describes a method of test for the humidification rate and evaporation efficiency of commercial and industrial adiabatic humidifiers as defined in Section 3. 

2.2 This method of test describes the test apparatus, conduct of the test, and information to be recorded. 

2.3 Information resulting from the application of this method of test is intended for use by manufacturers, specifiers, installers, and users of commercial and industrial humidifiers. 


ANSI/ASHRAE Standard 169-2021 - Published standard. Supersedes ANSI/ASHRAE Standard 169-2020 
Climatic Data for Building Design Standards 

1. Purpose
This standard provides recognized climatic data for use in building-design and related equipment standards. 

2. Scope

2.1 This standard covers climatic data used in ASHRAE standards, including dry-bulb, dew-point and wet-bulb temperatures, enthalpy, humidity ratio, wind conditions, solar irradiation, latitude, longitude, and elevation for locations worldwide. 

2.2 This standard also includes statistical data such as mean temperatures, average temperatures, mean/median annual extremes, daily ranges, heating and cooling degree days and degree hours, and hours and seasonal percentages within ranges of temperatures as well as bins. 

SSPC 169 to maintain and revise ANSI/ASHRAE Standard 169 placed on continuous maintenance on 1/25/2006.


ANSI/ASHRAE/ASHE 170-2025  – Published standard.  Supersedes ANSI/ASHRAE/ASHE Standard 170-2021 
Ventilation of Health Care Facilities 

1. Purpose
The purpose of this standard is to define ventilation system design requirements that provide environmental control in health care facilities. 

2. Scope

2.1 The requirements in this standard apply to patient care areas, resident care areas, and related support areas within health care facilities. 

2.2 This standard applies to new buildings, additions to existing buildings, and those alterations to existing buildings that are identified within this standard. 

2.3 This standard considers chemical, physical, and biological contaminants that can affect the delivery of medical care to patients and residents, the convalescence of patients and residents, and the safety of patients, residents, health care workers, and visitors. 

2.4 This standard establishes design requirements for temperature and humidity. 

2.5 This standard establishes design requirements for odor control and asepsis. 

2.6 This standard establishes design requirements for ventilation rates including, but not limited to outdoor air to serve health care facilities.  

2.7 This standard does not establish comprehensive thermal comfort design requirements. 

SSPC 170 to maintain and revise Standard 170. Standard placed on continuous maintenance June 21, 2008. 


ANSI/ASHRAE Standard 171-2017 – Published Standard. Supersedes ANSI/ASHRAE Standard171-2008 
Method of Testing for Rating Seismic and Wind Restraints  

1. Purpose 
This standard provides a test procedure for rating the capacity of seismic and wind restraints for nonstructural components and systems by determining the maximum loads a restraint can withstand without breakage or excessive deformation. 

2. Scope 
This standard is limited in its application and is appropriate only for certain types of restraints made with certain materials, as defined below: 

2.1 Types of Seismic Restraints 

  1. Single-directional, single-axis, multiangle (e.g., cable restraints that provide tension-only restraint and can be installed at various angles). 
  2. Bidirectional, single axis, multiangle (e.g., rigid braces/restraints). 
  3. Single-directional, single-axis, single-angle (e.g., bumpers that limit the motion of nonstructural components in one direction). 
  4. Multidirectional, multi-axis, with no operating clearance (e.g., brackets and rigid restraints that connect nonstructural components directly to the structure). 
  5. Multidirectional, multi-axis, with operating clearance (e.g., snubbers that limit the motion of nonstructural components in multiple directions) 
  6. Multidirectional, multi-axis, with integral isolation (e.g., combination isolator/restraints that provide vibration isolation for nonstructural components and include a means of multiaxial restraint). 

2.2 Restraint Materials 

  1. Ferrous metals, including those used in ductile castings, structural stainless steel and structural carbon steel. 
  2. Non-ferrous metals such as aluminum, copper and brass 
  3. Non-metallic materials such as fiberglass, elastomer, natural rubber and composites. 

2.3 Not Included in Scope 

  1. This standard does not address the durability of any supported equipment, or other nonstructural components, and their ability to remain functional during and at the conclusion of a seismic event. 
  2. This standard does not apply to restraints using nonductile materials. 
  3. Unless otherwise defined, individual parts used in a complete restraint system assembly are not meant to be tested and rated using this standard. 
  4. Any attachment fasteners and any members in the load path on the structural side of the building-attached components are outside the scope of this standard. 
  5. Any intermediate component support frames or bases between the restraint and the nonstructural component being restrained are outside the scope of this test standard and, for the purposes of this method, are considered part of the component. 
  6. This standard is not appropriate for determining the capacity of devices that are used in extreme shock (e.g., blast) or long-term dynamic loading applications. 

SPC 171-2017R – Revision project committee authorized June 2024. 


ANSI/ASHRAE Standard 172-2024  – Published standard. Supersedes ANSI/ASHRAE Standard 172-2017 
Method of Test for Insoluble Materials in Lubricant and Refrigerant Systems 

1. Purpose
The purpose of this standard is to define a test method to determine the formation of insoluble materials in lubricant and refrigerant systems. 

2. Scope
The test will determine the presence of materials that separate from refrigerant and lubricant mixtures over a range of temperatures and concentrations. The test is based on the precipitation of insoluble material in a lubricant/refrigerant combination. The results can be used to compare lubricants and refrigerants. 


ANSI/ASHRAE Standard 173-2012 (RA 2026) – Published standard. Supersedes ANSI/ASHRAE Standard 173-2012 (RA 2016). 
Method of Test to Determine the Performance of Halocarbon Refrigerant Leak Detectors 

1. Purpose
The purpose of this standard is to establish a method of test for qualifying the performance of portable leak detectors designed for the detection of chlorofluorocarbon (CFC), hydrochlorofluorocarbon (HCFC), hudrofluorocarbon (HFC), and perfluorocarbon (PFC) halogenated gases. 

2. Scope
The practices and procedures in this standard cover the testing of refrigerant leak detectors intended for use in the leak testing of refrigerating, air-conditioning, and heat-pump systems and their components. 


ANSI/ASHRAE Standard 174-2022 – Published standard. Supersedes ANSI/ASHRAE Standard 174-2018. 
Method of Test for Rating Desiccant-Based Dehumidification Equipment 

1. Purpose
This standard provides test methods for rating the performance of desiccant-based dehumidification equipment. 

2. Scope
This method of test applies to dehumidification equipment operating at atmospheric pressure and using desiccants combined with other components to dehumidify air. 

SPC 175P – Redesignated as GPC 38P
SPC 177P – Redesignated as GPC 38P 


ANSI/ASHRAE/ACCA 180-2018 - Published standard. Supersedes ANSI/ASHRAE/ACCA 180-2012. 
Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems 

1. Purpose
The purpose of this standard is to establish minimum HVAC inspection and maintenance requirements that preserve a system’s ability to achieve acceptable thermal comfort, energy efficiency, and indoor air quality in commercial buildings. 

2. Scope

2.1 This standard provides minimum requirements for the HVAC system inspection and maintenance practice in new and existing buildings. Where specifically noted in this standard, different requirements apply. 

2.2 The provisions of this standard do not apply to: 

  1. single-family houses or multi-family structures of three or fewer stories above grade; 
  2. HVAC equipment and portions of building systems that primarily provide for industrial, manufacturing, or commercial processes; or 
  3. other building HVAC systems or elements of building HVAC systems that this standard specifically identifies. 

2.3 This standard shall not be used to circumvent any safety, health, or environmental requirements. 

SPC 180-2018R Revision committee approved by Standards Committee on October 19, 2021 with the same TPS. 


ANSI/ASHRAE Standard 181-2023 – Published Standard. Supersedes ANSI/ASHRAE Standard 181-2018. 
Methods of Testing for Rating Liquid to Liquid Heat Exchangers 

1. Purpose
This standard prescribes methods of testing the thermal performance and pressure drop of liquid-to-liquid heat exchangers. 

2. Scope
This standard 

  1. Lists and defines the terms for rating the thermal performance of liquid-to-liquid heat exchangers; and 
  2. Establishes the methods of test to be used as a basis for obtaining the thermal performance and pressure drop of liquid-to-liquid heat exchangers using water or other single-phase liquids. 
  3. Applies to laboratory testing for purposes of rating heat exchangers within its scope. This standard is not intended for field testing of heat exchangers of any type. 

SPC 181-2018R Revision committee approved by Standards Committee on 3/31/2021. 


ANSI/ASHRAE Standard 182-2020 - Published Standard. Supersedes of ANSI/ASHRAE Standard 182-2008. 
Method of Testing Absorption Water-Chilling and Water-Heating Packages 

1. Purpose
The purpose of this standard is to prescribe a method of testing absorption water-chilling and water-heating packages to verify capacity and thermal energy input requirements at a specific set of operating conditions. 

2. Scope
This standard applies to: 

  1. absorption packages used to chill and/or heat water, as defined below in Section 3, and 
  2. testing that will occur where proper instrumentation and load stability can be provided.  

It is not the intent of this standard to provide for testing in typical field installations, where steady-state conditions are often difficult to achieve and adequate provisions for measurement are not made. 


ANSI/ASHRAE/ACCA Standard 183-2024 – Published standard. Supersedes ANSI/ASHRAE Standard 183-2007 (RA2020).
Peak Cooling and Heating Load Calculations in Buildings Except Low-Rise Residential Buildings

1. Purpose
This standard establishes requirements for performing peak cooling and heating load calculations for buildings except low-rise residential buildings.

2. Scope
This standard sets minimum requirements for methods and procedures used to perform peak cooling and heating load calculations for buildings except low-rise residential buildings.


ANSI/ASHRAE Standard 184-2020 - Published Standard. 
Method of Test for Field Performance of Liquid-Chilling Systems 

1. Purpose
The purpose of this standard is to prescribe methods of field performance testing for liquid-chilling systems. 

2. Scope

2.1 This standard includes the following types of liquid-chilling systems. These system types are further described in Section 5, “Equipment Types”. 

 2.1.1 Vapor compression cycle 

2.1.2 Absorption cycle 

2.2 This standard does not include systems with a net refrigeration capacity less than 10 tonR [35kW].

2.3 This standard does not include a specification of standardized test conditions under which the liquid-chilling system must operate. Test conditions typically reflect the expected operating conditions and are customer specified. 

SPC 184-2020R Revision project committee authorized October 18, 2024 with the same TPS.


ANSI/ASHRAE Standard 185.1-2020 – Published Standard. Supersedes ANSI/ASHRAE Standard 185.1-2015. 
Method of Testing UV-C Lights for Use in Air-Handling Units or Air Ducts to Inactivate Airborne Microorganisms. 

1. Purpose
This standard establishes a test method for evaluating the efficacy of UV-C Lights for their ability to inactivate airborne microorganisms. 

2. Scope

2.1 This standard describes a method of laboratory testing to measure the performance of UV-C lights used in general ventilating systems. 

2.2 This method of test measures the performance of UV-C lights to inactivate selected indicator microorganisms in the air stream. The standard defines procedures for generating the bioaerosols required for conducting the test. It also provides a method for counting the airborne bioaerosols upstream and downstream of the UV-C light in order to calculate inactivation efficiency for each microorganism. 

2.3 This standard also establishes performance specifications for the equipment required to conduct the tests, defines methods of calculating and reporting results obtained from the test data, and establishes a reporting system to be applied to UV-C lights covered herein. 

SSPC 185 to maintain and revise Standard 185.1. Standard placed on continuous maintenance 10/13/2015. Methods of Test to Inactivate Microorganisms in HVAC Systems with UV-C lights 


ANSI/ASHRAE Standard 185.2-2020 – Published Standard. Supersedes ANSI/ASHRAE Standard 185.2-2014. 
Method of Testing Ultraviolet Lamps for Use in HVAC&R Units or Air Ducts to Inactivate Microorganisms on Irradiated Surfaces 

1. Purpose
This standard establishes a test method for measuring the intensity of ultraviolet lamps on irradiated surfaces under typical HVAC&R operating conditions. 

2. Scope

2.1 This standard describes a method of laboratory testing to measure the ultraviolet C (UV-C) irradiance of ultraviolet lamps used in HVAC&R systems. 

2.2 This standard also: 

  1. defines methods of calculating and reporting results obtained from the test data, and 
  2. establishes a reporting system to be applied to ultraviolet lamps covered by this standard. 

SSPC 185 to maintain and revise Standard 185.2. Standard placed on continuous maintenance 10/13/2015. Revised TPS approved October 2021. Method of Testing Ultraviolet Sources for Use in HVAC&R Units or Air Ducts on Irradiated Surfaces 

1. Purpose
This standard establishes a test method for measuring the intensity of ultraviolet sources on irradiated surfaces under typical HVAC&R operating conditions. 

2. Scope

2.1 This standard describes a method of laboratory testing to measure irradiance of ultraviolet sources used in HVAC&R systems. 

2.2 This standard also: 

  1. defines methods of calculating and reporting results obtained from the test data, and 
  2. establishes a reporting system to be applied to ultraviolet sources covered by this standard. 

ANSI/ASHRAE Standard 185.3 2024, Published standard. 
Method of Testing Commercial and Industrial In-Room Air-Cleaning Devices and Systems for Microorganism Bioaerosol Removal or Inactivation in a Test Chamber 

1. Purpose
The standard establishes a test method for evaluating commercial and industrial in-room air-cleaning devices and systems for microorganism bioaerosol removal or inactivation in a test chamber. 

2. Scope

2.1 The standard specifies selected indicator microorganisms in the test chamber and defines procedures for generating the bioaerosols required for the method of test. 

2.2 This standard provides a method for counting the number of viable microorganisms in the chamber to calculate the elimination efficiency for each microorganism. 

2.3 This standard establishes minimum performance specifications for the equipment required to conduct the tests, defines methods of calculating and reporting results obtained from the test data, and establishes a reporting system to be applied to in-room devices and systems covered herein. 

2.4 This standard does not address the health and safety effects of operating devices and systems in an occupied room.  

2.5 This standard applies to commercial and industrial in-room air-cleaning devices and systems. This standard is not intended to conflict with or replace ANSI/AHAM Standard AC-5 for testing portable residential air cleaners. 


ANSI/ASHRAE Standard 185.4-2024 – Published Standard. SSPC 185 to maintain and revise Standard 185.4. 
Method of Testing In-Room Ultraviolet Devices and Systems for Microbial Inactivation on Surfaces in a Test Room

1. Purpose
This standard establishes a test method for evaluating the efficacy of ultraviolet disinfection systems for microbial inactivation on multiple surface locations in a test room.

2. Scope

2.1 The standard applies to ultraviolet devices and systems using only germicidal ultraviolet energy for disinfection.

2.2 The method of test specifies selected indicator microorganisms and defines procedures for inoculating test carriers in a room-scale test chamber.

2.3 The method of test defines the test carrier quantity and positions in the test room.

2.4 This standard provides a method for counting the number of viable microorganisms on the test carriers before and after ultraviolet inactivation.

2.5 This standard establishes protocols and minimum requirements for the materials and equipment required to conduct the tests, defines methods of calculating and reporting results obtained from the test data, and establishes a reporting system to be applied to in-room devices and systems covered herein.

2.6 This standard does not address the health and safety effects of operating devices and systems in an occupied room.


SPC 185.5P – Redesignated as SPC 234P


ANSI/ASHRAE Standard 188-2021 - Published Standard. Supersedes ANSI/ASHRAE Standard 188-2018. 
Legionellosis: Risk Management for Building Water Systems 

1.  Purpose
The purpose of this standard is to establish minimum legionellosis risk management requirements for building water systems. 

2.  Scope

2.1 This standard provides minimum legionellosis risk management requirements for the design, construction, commissioning, operation, maintenance, repair, replacement, and expansion of new and existing buildings and their associated (potable and nonpotable) water systems and components.

2.2 This standard applies to human-occupied commercial, institutional, multiunit residential, and industrial buildings. This standard does not include single-family residential buildings. Only where specifically noted in this standard shall certain building water systems or parts of building water systems be exempt. 

2.3 This standard is intended for use by owners and managers of human-occupied buildings, excluding single-family residential buildings. This standard is also intended for those involved in the design, construction, installation, commissioning, operation, maintenance, and service of centralized building water systems and components. 

SSPC 400 is the cognizant project committee for maintenance of Standard 188 (approved January 2024).


ANSI/ASHRAE/ICC/USGBC/IES Standard 189.1-2023-  Published Standard. Supersedes ANSI/ASHRAE/ICC/USGBC/IES Standard 189.1-2020
Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings 

1. Purpose

1.1 The purpose of this standard is to provide minimum requirements for the siting, design, construction, and plans for operation of high-performance green buildings to  

  1. reduce emissions, enhance occupant health and comfort, conserve water, protect local biodiversity and ecosystem services, promote sustainable and regenerative materials cycles, and enhance resilience; and 
  2. support the goal of development that meets the needs of the present without compromising the ability of future generations to meet their own needs. 

1.2 This standard provides comprehensive requirements that can be adopted by national and local jurisdictions. 

2. Scope
This standard addresses site sustainability, water use efficiency, energy efficiency, indoor environmental quality (IEQ), materials and resources, and construction and plans for operation. It contains requirements that apply to the following: 

  1. New buildings and structures and their systems 
  2. New portions of buildings and structures and their systems 
  3. New systems and equipment in existing buildings  
  4.  Relocated existing buildings  
  5. The site on which the building or structure is located 
  6. Demolition and deconstruction of buildings and their systems 
  7. Change of occupancy classification or use 

2.2 The provisions of this standard do not apply to the following:

  1. single-family houses, multifamily structures of three stories or fewer above grade,    manufactured houses (mobile homes), and manufactured houses (modular) and 
  2. building projects and structures that use none of the following: 
    1. electricity 
    2. fossil fuel 
    3. water 

2.3 The requirements in this standard shall not be used to circumvent any applicable safety, health, or environmental requirements.

SSPC 189.1 to maintain and revise Standard 189.1. Standard is on continuous maintenance. Revised TPS approved April 2025.
Standard for the Design of High-Performance Green Buildings 

1. Purpose

1.1 The purpose of this standard is to provide minimum requirements for the siting, design, construction, and plans for operation of high-performance green buildings to

  1. reduce emissions, enhance occupant health and comfort, conserve water, protect local biodiversity and ecosystem services, promote sustainable and regenerative materials cycles, and enhance resilience; and
  2. support the goal of development that meets the needs of the present without compromising the ability of future generations to meet their own needs.

1.2 This standard provides comprehensive requirements that can be adopted by national and local jurisdictions.

2. Scope

2.1 This standard addresses site sustainability, water use efficiency, energy efficiency, indoor environmental quality (IEQ), materials and resources, and construction and plans for operation. It contains requirements that apply to the following:

  1. New buildings and structures and their systems
  2. New additions to buildings and structures and their systems
  3. Alterations to existing buildings and structures
  4.  New systems and equipment in existing buildings
  5.  Relocated existing buildings
  6.  The site on which the building or structure is located
  7.  Demolition and deconstruction of buildings and structures and their systems
  8.  Change of occupancy classification or use

 2.2 The provisions of this standard do not apply to the following:

  1. Single-family houses, multifamily structures of three stories or fewer above grade, manufactured houses (mobile homes), and manufactured houses (modular)
  2. Building projects and structures that use none of the following:
    1. Electricity
    2. Fossil fuel
    3. Water

2.3 The requirements in this standard shall not be used to circumvent any applicable safety, health, or environmental requirements.­­­­­­­­­­­­­­­­­­­­­­­­­


ANSI/ASHRAE/ASHE Standard 189.3-2025 Published Standard. Supersedes Standard 189.3-2021. 
Design, Construction and Operation of Sustainable High-Performance Health Care Facilities.  

1. Purpose

1.1 The purpose of this standard is to provide minimum requirements for the siting, for the design, construction and operation of high performance sustainable health care facilities to: 

  1. Reduce emissions, enhance occupant health and comfort, conserve water, protect local biodiversity and ecosystems services, promote sustainable and regenerative materials cycles, and enhance resilience; and 
  2. Support the goal of development that meets the needs of the present without compromising the ability of future generations to meet their own needs, including decarbonization of the building environment. 

1.2 This standard provides requirements that can be adopted by national and local jurisdictions. 

2. Scope

2.1 This standard applies to patient care areas and related support areas within health care facilities and their site, including hospitals, outpatient facilities, residential health, care and support facilities. 

2.2 This standard applies to new buildings, additions to existing buildings, and those alterations to existing buildings that are identified within the standard. 

2.3 This standard provides procedures for the integration of sustainable principles into the health care facility design, construction and operation process including: 

  1. integrated design 
  2. conservation of water 
  3. conservation of energy 
  4. indoor environmental quality 
  5. construction practices 
  6. commissioning 
  7. operations and maintenance 

2.4 The requirements in this standard shall not be used to circumvent any applicable safety, health, reimbursement, or environmental requirements. 

SSPC 189.3 to maintain and revise standard 189.3. Standard approved for continuous maintenance March 1, 2017. 


ANSI/ASHRAE Standard 190-2020 - Published standard. Supersedes ANSI/ASHRAE Standard 190-2013. 
Method of Testing for Rating Indoor Pool Dehumidifiers 

1. Purpose
The purpose of this standard is to prescribe test methods for determining the moisture removal capacity and efficiency, the pool heating capacity, and sensible and total cooling capacity for indoor pool dehumidifiers. 

2. Scope

2.1 This standard applies to indoor pool dehumidifiers using electrically driven, mechanical vapor-compression refrigeration systems consisting of one or more factory-made assemblies that dehumidify and circulate air and may include pool water heating, air reheating, cooling, filtering, and heat recovery. 

2.2 Systems other than those stated in Section 2.1 (e.g., cooling-only equipment) are excluded. 


Standard 191P - Proposed Standard authorized 9/29/06. Revised TPS approved by Technology Council, June 2022. ASPE/AWWA are co-sponsors to this standard. 
Standard for Water Balances and Efficiency in Mechanical and Process Systems 

1. Purpose

1.1 The purpose of this standard is to document a comprehensive water balance and define baseline requirements for the efficient use of water in mechanical and process systems. 

1.2 The purpose of the water balance is to identify the volumes of water from sources and to uses within a user-defined project boundary. The goal is to highlight potential opportunities to maximize the efficient use of water. 

2. Scope

2.1 This standard provides minimum criteria that: 

  1.  Apply to new buildings and renovation projects (new portions of buildings and their systems) and the surrounding site: a building or group of buildings, that utilize a single submittal for a construction permit or which are within the boundary of a contiguous area under single ownership. 
  2. Addresses water use through the concept of a water balance and efficiency measures implemented during design, construction, and operation of residential, commercial, institutional, and industrial projects. 

2.2 The provisions of this standard do not apply to:

  1. Storm or building waste water management, except as a means of reducing water use for mechanical and process systems as defined in the standard.
  2. Industrial process systems that are not identified within the standard. 

2.3 This standard shall not be used to circumvent any safety, health, or environmental requirements. 

2.4 This standard shall not be used to circumvent local or state water rights laws or any other local, municipal, and/or state statutes. 


ANSI/ASHRAE Standard 193-2010 (RA 2024) - Published standard. Supersedes ANSI/ASHRAE Standard 193-2010 (RA2014). 
Method of Test for Determining the Airtightness of HVAC Equipment 

1. Purpose
This standard prescribes a method of test to determine the airtightness of forced-air HVAC equipment prior to field installation. 

2. Scope

2.1 This standard applies to the following:

  1. Equipment intended for installation in ducted systems, including furnaces, heat pumps, air conditioners, coil boxes, filter boxes, and associated components.
  2. Equipment that moves less than 3000 cfm (1400 L/s) of air. 

2.2 This standard does not apply to ducts, plenums, or other field-constructed components. 

SPC 193R – Revision project committee authorized in February 2019.  Revised TPS approved June 2025.
Method of Test for Determining the Airtightness of HVAC Equipment 

1. Purpose
This standard prescribes a method of test to determine the airtightness of forced-air HVAC equipment prior to field installation. 

2. Scope

2.1 This standard applies to the following:

  1. Equipment intended for installation in ducted systems, including furnaces, heat pumps, air conditioners, coil boxes, filter boxes, and associated components.
  2. Equipment that moves less than 3000 cfm (1400 L/s) of air. 

2.2 This standard does not apply to ducts, plenums, other field-constructed components, or air terminal units within the scope of ANSI/ASHRAE Standard 130.


ANSI/ASHRAE Standard 194-2025 Published standard. Supersedes ANSI/ASHRAE Standard 195-2017.
Method of Test for Direct-Expansion Ground-Source Heat Pumps

1. Purpose
The purpose of this standard is to provide test procedures for rating factory-made residential, commercial, and industrial direct-expansion (DX) ground-source heat pumps (GSHPs), as defined in Section 3. This standard addresses heat-pump capacity ranges of 3.5 through 52.8 kW (12,000 through 180,000 Btu/h) and all standard voltage and frequency ratings.

2. Scope

2.1 This standard provides test procedures for determining heating capacity, cooling capacity, coefficients of performance (COPs), and energy efficiency ratios (EERs) for systems, as defined in Section 3.

2.2 This standard applies only to electrically driven, mechanical vapor-compression refrigeration systems.

2.3 This standard applies to the testing of heat pumps with an outdoor refrigerant to test liquid heat exchanger utilized to condition the refrigerant entering the system under test. This standard does not apply to individual assemblies for separate use.


ANSI/ASHRAE Standard 195-2024 Published standard. Supersedes ANSI/ASHRAE Standard 195-2013)
Method of Test for Rating Air Terminal Unit Controls

1. Purpose
This standard specifies instrumentation and facilities, test installation methods, and procedures for determining the accuracy and stability of airflow control systems for terminal units at various airflow set points.

2. Scope
This standard applies to electronic and/or pneumatic control systems used for pressure independent airflow control in terminal units for variable-air-volume (VAV) and constant-volume (CV) air-moving systems.

SPC 195-2024R Revision project committee authorized October 18, 2024 with the same TPS.
Method of Test for Rating Air Terminal Unit Controls

Standard 196P - Proposed standard authorized (Salt Lake City) June 24, 2008. Revised TPS approved January 27, 2017. 
Method of Test for Measuring Refrigerant Leak Rates 

1. Purpose
To establish procedures necessary to measure leak flow rates of refrigerant by using refrigerant as the test gas. The intent of these measurements is to allow predictions of leak rates of equipment. 

2. Scope
The scope of this standard covers measuring leaks of packaged refrigeration, air-conditioning and heat pump systems and system components. 


ASHRAE Standard 198-2013. Published Standard. 

Method of Test for Rating DX-Dedicated Outdoor Air Systems for Moisture Removal Capacity and Moisture Removal Efficiency

1. Purpose
This standard prescribes test methods for rating direct-exchange dedicated outdoor systems (DX-DOAS) units.

2. Scope
This method of test applies to air-cooled, water-cooled, or water-source factory-assembled DX-DOAS products that condition 100% outdoor air and may include factory assembled preconditioning device(s). Units containing water coils requiring a supply of water supplied by a liquid chiller located outside of the unit are not covered by this standard. This standard is not to be used to rate stand-alone preconditioning or energy-recovery devices.

SPC 198-2013R Revision project committee authorized February 1, 2017 (Las Vegas). Revised TPS approved in June 2025. 
Method of Test for Direct Expansion-Dedicated Outdoor Air System (DX-DOAS) Units 

1. Purpose
This standard provides methods of testing and calculations for moisture removal and heating by Direct Expansion-Dedicated Outdoor Air System (DX-DOAS) Units. 

2. Scope

2.1 This method of test applies to factory-assembled DX-DOAS that condition 100% outdoor air and can include factory assembled preconditioning device(s). This includes the following: 

  1. air-cooled, evaporatively-cooled, and water-cooled DX-DOAS units 
  2. air-source or water-source DX-DOAS heat pump units. 

2.2 Scope Exclusions:  

  1. Units containing water coils requiring a supply of water supplied by a liquid chiller located outside of the unit are not covered by this standard.   
  2. This standard is not to be used for the testing of stand-alone pre-conditioning or energy recovery devices. 
  3. Units that incorporate heat sources other than electricity for regeneration of desiccant heat exchangers are not in the scope of this standard. 

ANSI/ASHRAE Standard 199-2016 (RA 2026) Published Standard. Supersedes NSI/ASHRAE Standard 199-2016. 
Method of Testing the Performance of Industrial Pulse Cleaned Dust Collectors 

1. Purpose
The purpose of this standard is to provide a quantitative laboratory test method for determining the performance of industrial pulse cleaned dust collectors using a test dust. 

2. Scope
This method of test applies to bag, cartridge, or envelope industrial dust collectors that recondition the filter media by using a pulse of compressed air to discharge the dust cake from the filter media while the air cleaning device remains on line. 

SPC 199-2016R – Revision committee authorized by Standards Committee on April 11, 2022 with same TPS. 
Method of Testing the Performance of Industrial Pulse Cleaned Dust Collectors 


ANSI/ASHRAE Standard 200-2024 Published standard. Supersedes ANSI/ASHRAE Standard 200-2018. 
Methods of Testing Chilled Beams 

1. Purpose

1.1 To define laboratory methods of testing chilled beams to determine performance. 

2. Scope

2.1 Defines laboratory methods of testing chilled beams to determine performance. 

2.2 Specifies test instrumentation, facilities, installation methods, and procedures for determining the performance of chilled beams. 


ANSI/ASHRAE/NEMA Standard 201-2016 (RA2026) Published Standard. Supersedes ANSI/ASHRAE/NEMA Standard 201-2020. 
Facility Smart Grid Information Model 

1. Purpose
The purpose of this standard is to define an abstract, object-oriented information model to enable appliances and control systems in homes, buildings, and industrial facilities to manage electrical loads and generation sources in response to communication with a “smart” electrical grid and to communicate information about those electrical loads to utility and other electrical service providers. 

2. Scope
 This model provides the basis for common information exchange between control systems and end use devices found in single- and multi-family homes, commercial and institutional buildings, and industrial facilities that is independent of the communication protocol in use. It provides a common basis for electrical energy consumers to describe, manage, and communicate about electrical energy consumption and forecasts. 

The model defines a comprehensive set of data objects and actions that support a wide range of energy management applications and electrical service provider interactions including but not limited to: 

  1. on-site generation, 
  2. demand response, 
  3. electrical storage, 
  4. peak demand management, 
  5. forward power usage estimation, 
  6. load shedding capability estimation, 
  7. end load monitoring (sub metering), 
  8. power quality of service monitoring, 
  9. utilization of historical energy consumption data, and 
  10. direct load control. 

ANSI/ASHRAE/IES Standard 202-2024. Published Standard. Supersedes ANSI/ASHRAE/IES Standard 202-2018.
The Commissioning Process Requirements for New Buildings and New Systems

1. Purpose
The purpose of this standard is to identify the minimum acceptable Commissioning Process (Cx) for new buildings and new systems.

2. Scope

2.1 This standard applies to 

  1. New buildings and their systems 
  2. New portions of buildings and their systems
  3. New systems and equipment in existing buildings 

2.2 This provides procedures, methods, and documentation requirements for each activity for project delivery, from predesign through occupancy and operations, including

  1. An overview of Commissioning Process (Cx) Activities 
  2. A description of each process step’s minimum activities 
  3. Minimum documentation requirements 
  4. Acceptance requirements
SSPC 300 to be cognizant project committee for revision and maintenance of Standard 202 (approved June 2016). Standard 202 placed on continuous maintenance June 23, 2013. 

ANSI/ASHRAE Standard 203-2018 (RA 2025) –Published standard. Supersedes ANSI/ASHRAE Standard 203-2018 (RA2021). 
Method of Test for Determining Heat Gain of Office Equipment Used in Buildings 

1. Purpose
This standard prescribes methods of test to determine the range and average operating heat gains of electrical equipment for use in cooling load calculations. 

2. Scope
This standard applies to plug-load-type electrical equipment. 


ANSI/ASHRAE Standard  204-2020 – Published Standard 
Method of Test for Rating Micro Combined Heat and Power Devices 

1. Purpose
The purpose of this standard is to provide a uniform laboratory test method for determining the net electrical power generating performance and thermal power recovery performance of micro combined heat and power devices, referred to as “microcogeneration devices.” The standard specifies the equipment and instrumentation required, test methods, and calculation procedures. 

2. Scope 
This standard provides a comprehensive set of procedures for micro combined heat and power devices whose maximum net electrical power output is less than 50 kW and whose maximum useful thermal power output is less than 300 kW. The maximum allowable ratio of thermal power output (exclusive of any auxiliary heating equipment) to net electrical power output is 15. 

This standard applies to the following stationary micro combined heat and power devices that use, but are not limited to, an internal combustion engine, a turbine, a Stirling engine, or a fuel cell as the heat and power generating source. Only appliances that use natural gas, propane, or diesel as the fuel source are covered. Appliances that use biofuels or biogases as the fuel source are not covered, but the procedures and methods in this standard are applicable to the evaluation of those appliances. Separate tests are defined for stand-alone devices and devices that are part of a packaged system that includes ancillary heating equipment. These tests cover single stand-alone devices or single devices that are part of a package system. Groups of devices operating in parallel are not covered by this standard. 

This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices to determine the applicability of regulatory limitations prior to use. 

SPC 204-2020R Revision committee approved by Standards Committee on October 19, 2021 with the same TPS.  


ANSI/ASHRAE/IBPSA 205-2023 Published Standard. Standard 205 was placed on continuous maintenance June 28, 2022. IBPSA is a cosponsor of this standard.
Representation of Performance Data for HVAC&R and Other Facility Equipment 

1. Purpose
To facilitate automated sharing of equipment performance characteristics by defining data models and data serialization formats. 

2. Scope
This standard applies to performance data for any HVAC&R or other facility system, equipment, or component. 


ANSI/ASHRAE Standard 206-2024 Published standard. Supersedes ANSI/ASHRAE Standard 206-2013 (RA 2017). 
Method of Testing for Rating of Multipurpose Heat Pumps for Residential Space Conditioning and Water Heating 

1. Purpose  

1.1 The standard provides uniform test methods and calculation procedures for establishing the efficiencies of multipurpose residential heat pumps for space conditioning, water heating, and/or dehumidification. 

1.2 This standard specifies the test equipment for performing such tests, the data required and calculations to be used, and lists and defines the terms used in testing. 

1.3 The procedures in this standard may be used as a basis for establishing efficiency ratings for such equipment and for estimating annual energy consumption. 

 2. Scope 

2.1 This standard applies to electrically powered unitary integrated appliances that provide combinations of space conditioning, water heating, and/or dehumidification functions. 

2.2 The method of testing in this standard is broadly applicable, but this standard provides cooling and heating hours in temperature bins for only the contiguous states of the continental USA. 

2.3 This standard includes test methods for steady-state, cyclic, and part-load performance and methods for establishing seasonal performance. Equipment with single-capacity, multiple-capacity, and variable-capacity, or multiple compressors is covered.  

2.4 The equipment to which this standard applies may be ducted or ductless, but it is limited to forced air space conditioning.  


ANSI/ASHRAE Standard 207-2025, Published Standard. Supersedes ANSI/ASHRAE Standard 207-2021. 
Laboratory Method of Test of Fault Detection and Diagnosis for Air Economizers 

1. Purpose 
The purpose of this standard is to provide methods for laboratory testing of fault detection and diagnosis (FDD) systems to determine whether they perform as specified.  

2. Scope

2.1 This standard applies to the FDD systems that are intended to detect or diagnose faults that affect the performance of the air economizers of air conditioning equipment. 

2.2 This standard defines laboratory tests for faults in four categories of economizer functions: sensor communication, actuator communication, damper and actuator responsiveness, and damper position. 

2.3 This standard only applies to those FDD systems designed to detect or diagnose faults by evaluating instantaneous or short-term conditions and parameters. 


ANSI/ASHRAE/IBPSA Standard 209-2024, Published Standard. Supersedes ANSI/ASHRAE Standard 209-2018. 
Building Performance Simulation Process 

1. Purpose
To establish minimum requirements for the process of using simulation to evaluate building performance and inform decision making. 

2. Scope
This standard applies to the use of building performance simulation, including energy modeling, during the design, construction and operation of new buildings or major renovations of, or additions to, existing buildings. 

SSPC 209 to maintain and revise Standard 209. Standard approved for continuous maintenance April 2022. IBPSA is a co-sponsor to this standard. 


SPC 210P, Proposed Standard authorized (Chicago) January 25, 2012. Revised TPS approved January 23, 2016. 
Method of Testing for Rating Commercial Walk-in Cooler and Freezer Equipment 

1. Purpose
The purpose of this standard is to prescribe a uniform method of testing walk-in commercial cooler and freezer equipment for rating so that comparative evaluations can be made of energy and other performance factors. 

2. Scope
This standard applies to commercial walk-in cooler and freezer equipment, not including equipment designed and marketed exclusively for medical, scientific, or research purposes.  Equipment includes but is not limited to components and subsystems of the following: 

  1. Envelope 
  2. Refrigeration Equipment 
  3. Lighting 
  4. Auxiliary Equipment 

ANSI/ASHRAE/ACCA Standard 211-2018 (RA 2023) - Published Standard.
Supersedes ANSI/ASHRAE/ACCA Standard 211-2018. 
Standard for Commercial Building Energy Audits 

1. Purpose
The purpose of this standard is to establish consistent practices for conducting and reporting energy audits for commercial buildings. 

This standard 

  1. defines the procedures required to perform Energy Audit Levels 1, 2, and 3; 
  2. provides a common scope of work for these audit levels for use by building owners and others; 
  3. establishes consistent methodology and minimum rigor of analysis required; and 
  4. establishes minimum reporting requirements for the results of energy audits. 

2. Scope

2.1 This standard applies to all buildings except single-family houses, multifamily structures of three stories or fewer above grade, manufactured houses (mobile homes), and manufactured houses (modular). 

SSPC 211 to maintain and revise Standard 211. Standard on continuous maintenance. Revised TPS approved June 2026.
Standard for Commercial Building Energy Audits and Decarbonization Assessments

1. Purpose
The purpose of this standard is to establish consistent practices for conducting and reporting energy audits and decarbonization assessments for commercial buildings.

This standard:

  1. defines the procedures required to perform all levels of energy audits and decarbonization assessments,
  2. provides a common scope of work for these levels for use by building owners and others,
  3. establishes consistent methodology and minimum rigor of analysis required, and 
  4. establishes minimum reporting requirements for the results of energy audits and decarbonization assessments

2. Scope:

2.1 This standard applies to all buildings except single-family houses, multifamily structures of three stories or fewer above grade, manufactured houses (mobile homes), and manufactured houses (modular).

2.2 Decarbonization assessments covered by this standard address Scope 1 and Scope 2 greenhouse gas emissions and exclude Scope 3 greenhouse gas 


ANSI/ASHRAE Standard 212-2019 – Published standard. 
Method of Test for Determining Energy Performance and Water-Use Efficiency of Add-On Evaporative Precoolers for Unitary Air-Conditioning Equipment 

1. Purpose
To provide test methods for gathering performance data for use in calculating the energy savings potential and water-use performance of add-on evaporative precoolers for condenser inlet air of air-cooled, direct-expansion unitary air- conditioning equipment. 

2. Scope
This standard applies to add-on evaporative precooling accessories applied to the condenser inlet air of air-cooled unitary direct-expansion cooling equipment with less than or equal to 240,000 Btu/h (70kW) cooling capacity. 

SPC 212-2019R - Revision project committee authorized October 18, 2024 with the same TPS. 


SPC 213P, Proposed Standard authorized 6/26/2013. Revised TPS approved January 2021. 
Method for Calculating Moist Air Thermodynamic Properties 

1. Purpose
The purpose of this standard is to establish a standardized method for calculating thermodynamic properties of moist air for use in analyzing heating, ventilating, air-conditioning, and refrigerating applications.  

2. Scope

2.1. This standard provides mathematical relationships for the following thermodynamic properties:  pressure, dry-bulb temperature, wet-bulb temperature, dew-point temperature, relative humidity, humidity ratio, specific volume, specific enthalpy, specific heat capacity at constant pressure, and specific entropy.  

2.2 This standard applies to thermodynamic properties of moist air within the following range of conditions:  

2.2.1 Total pressure from 70 to 110 kPa (10 to 16 psi), 

2.2.2 Dry-bulb temperature from –60 to 85 °C (–80 to 185 °F), and  

2.2.3 Relative humidity from 0 to 100%. 


ANSI/ASHRAE Standard 214-2017 (RA 2023) - Published Standard. Supersedes ANSI/ASHRAE Standard 214-2017
Standard for Determining and Expressing Building Energy Performance in a Rating Program 

1. Purpose

1.1 The purpose of this document is to provide a standardized approach and methodology for determining and expressing building energy performance in a rating program. 

1.2 The purpose of this document is to standardize the content of the label associated with the energy component of a rating program and establish minimum requirements for rating program documentation. 

2. Scope

2.1 This standard applies to the following: 

  1. New and existing buildings. 
  2. The building site or campus on which the buildings are located and all accessory and appurtenant structures, energy-using systems, and equipment located on the building site. 

2.2 This standard establishes requirements for the following: 

  1. Disclosure of building energy use via a rating and supporting summary documentation. 
  2. Modeling of buildings and building sites to estimate or predict building energy use for an asset rating. 
  3. Determining energy use, with metered data, of buildings and building sites for an operational rating. 
  4. Acceptable credentialing criteria for individuals applying this standard and reporting building energy use. 
  5. The format and content of the rating disclosure, the label, and supporting documentation. 

2.3 This standard is intended to be used with one or multiple energy performance metrics. 

2.4 This standard applies to only the energy component of a rating program. 


ANSI/ASHRAE Standard 215-2018 (RA2021)- Published Standard. 
Method of Test to Determine Leakage of Operating HVAC Air Distribution Systems 

1.  Purpose
This standard specifies a method of test to determine leakage airflow and fractional leakage of operating HVAC air distribution systems, and determines the uncertainty of the test results. 

2.  Scope

2.1 This standard is for field application in both new and existing buildings. 

2.2 This standard can be applied to determine whole-system or sectional leakage airflow. 

2.3 This standard provides  

  1. test procedures and requirements for measuring inlet and outlet airflows during system operation,  
  2. methods for calculating leakage airflows to/from system surroundings,  
  3. methods for calculating leakage test uncertainties,  
  4. methods for documenting the test plan, and  
  5. methods for reporting test results. 

2.4 The test procedures in this standard are limited to single-duct supply and independent exhaust air systems. 

2.5 This standard is not for determining return air leakage. 

2.6 This standard is not for determining leakage involving ceiling and floor plenums, systems serving pressure-controlled spaces, and air dispersion systems. 

2.7 This standard does not replace ductwork pressurization leakage testing. 

2.8 This standard does not specify leakage acceptance criteria. 

2.9 This standard shall not be used to override any safety, health, or critical process requirements. 


ANSI/ASHRAE Standard 216-2020
Methods of Test for Determining Application Data of Overhead Circulator Fans

1. Purpose 
The purpose of this standard is to specify the instrumentation, facilities, test installation methods, and procedures to determine circulator fan application data for occupant thermal comfort in a space.

2. Scope

2.1
This standard applies to overhead circulator ceiling fans.


ANSI/ASHRAE Standard 217-2020 - Published document. 
Non-Emergency Ventilation in Enclosed Road, Rail and Mass Transit Facilities 

1.Purpose
This standard provides minimum ventilation requirements for ventilation systems within enclosed transportation facilities during non-emergency operating conditions. 

2. Scope 

2.1 This standard applies to enclosed transportation facilities, consisting of road tunnels, railway tunnels, mass transit tunnels and mass transit stations. 

2.2 This standard provides criteria for non-emergency ventilation. 

2.3 This standard addresses the design, construction, commissioning, operation and maintenance requirements of non-emergency ventilation systems and equipments. 

SPC 217-2020R - Revision project committee authorized September 27, 2023 with same TPS.  


ANSI/ASHRAE Standard 218-2026 - Published Standard. Supersedes ANSI/ASHRAE Standard 218-2019. 
Method of Test for Lubricant and Refrigerant Miscibility Determination 

1. Purpose
The purpose of this standard is to establish a test procedure to determine the critical solution locus of miscibile properties of a lubricant and refrigerant mixture. 

2. Scope
This standard applies to: 

2.1 Single-component refrigerant and lubricant mixtures 

2.2 Multi-component refrigerant and lubricant mixtures 


ANSI/ASHRAE Standard 219-2021, Published Standard 
Method of Testing the Ability of Liquid Line Filter Driers or Adsorbents to Remove Organic Acid 

1. Purpose
This standard establishes a suitable laboratory apparatus and test method for determining the ability of various adsorbents and refrigerant liquid line filter driers to remove specific organic acids from refrigerant-lubricant mixtures. 

2. Scope
This standard applies to the measurement of the mass of a specific organic acid removed from a refrigerant-lubricant mixture by a liquid line filter drier containing an adsorbent desiccant material or through a specific adsorbent material which can remove acid by adsorption and/or chemical reaction. The standard applies to methods associated with the extraction of both short and long chain carboxylic acids. 


ASHRAE Standard 220P - Proposed Standard Authorized January 27, 2016 (Orlando) 
Method of Testing for Rating Small Commercial Blast Chillers, Chiller-Freezers, and Freezers
1. Purpose
This standard prescribes a uniform method of testing small commercial blast chillers, chiller-freezers, and freezers to determine energy consumption, product temperature performance, and other performance factors.

2. Scope
This standard: 

  1. establishes uniform methods of testing for determining laboratory performance of  self-contained commercial blast chillers, chiller-freezers, and freezers of up to 500 ft3 (14 m3) product volume used for quick chilling or freezing of food products; 
  2. lists and defines terms used in the method of testing; 
  3. defines standard measurements for net usable volume; and 
  4. establishes test conditions for rating. 

ANSI/ASHRAE Standard 221-2020. Published Standard 
Test Method to Field-Measure and Score the Cooling and Heating Performance of an Installed Unitary HVAC System 

1. Purpose
The purpose of this standard is to prescribe a field evaluation and test method to measure and score the performance, in terms of delivered cooling or heating capacity, or cooling efficiency, of an installed unitary HVAC system. 

2. Scope 
This standard: 

  1. defines performance scoring methods for cooling and heating system delivered capacity and cooling system efficiency; 
  2. establishes uniform methods of measurements and testing procedures for airflow, temperature, enthalpy, and power; 
  3. specifies test instruments, specifications and calibration requirements for performing such measurements and tests; 
  4. specifies data required and calculations to be used; and 
  5. applies to single-zone unitary split and packaged direct expansion (DX) cooling, air-source heat pump, and combustion furnace HVAC systems of any capacity, and with forced-air distribution systems.

SSPC 221 to maintain and revise Standard 221. Standard approved for continuous maintenance June 2020. 


ANSI/ASHRAE Standard 222-2025 - Published standard. Supersedes ANSI/ASHRAE Standard 222-2018.
Standard Method of Test for Electrical Power Drive Systems 

1. Purpose
To determine the performance of power drive systems for rating the energy efficiency and electrical compatibility with the power supply systems and with motor insulation. 

2. Scope

2.1. This standard is intended for HVAC&R applications that operate from low voltage (≤690 V).  

2.2. This standard applies to adjustable speed electric power drive systems, which combine semiconductor power converters, including means for their control, protection, monitoring, and measurement with connected electric motors. All electric rotary motor types are included. 

2.3. This standard includes the following: 

  1. Power converters that are completely integrated in motor casings 
  2. Remote power converters that are tested with motors defined in this standard 
  3. Power drive systems that are operated from direct current or alternating current electricity supplies  

ASHRAE Standard 223P - Proposed Standard. Authorized February 1, 2017 (Las Vegas). This Standard is being developed by SSPC 135. Revised TPS approved June 26, 2020.
Semantic Data Model for Analytics and Automation Applications in Buildings

1. Purpose
The purpose of this standard is to formally define knowledge concepts and a methodology to apply them to create interoperable, machine-readable semantic models for representing building system information for analytics, automation, and control. 

2. Scope
This standard provides a way to apply Semantic Web standards to the creation of models that represent building system components, their relationships in various contexts, and associated data. Such models allow building analytics and enterprise knowledge tools to automatically find necessary information to implement applications including:

  1. automated fault detection and diagnostics,
  2. control system configuration,
  3. building system commissioning,
  4. digital twins,
  5. optimization of energy use,
  6. energy audits, and
  7. smart grid interactions.

ANSI/ASHRAE/NIBS 224-2023 Published Standard. This was approved for continuous maintenance in January 2024. NIBS is a co-sponsor to this standard. 
Standard for the Application of Building Information Modeling 
 
1. Purpose
This standard provides minimum requirements for the application of Building Information Modeling (BIM) to the planning, design, construction and operation of facilities, including both buildings and infrastructure. This standard defines how to incorporate BIM requirements in design, construction and operations services contracts. 

2. Scope 
This standard applies to new facilities or the renovation of, or additions to existing facilities using building information modeling (BIM) for planning, design, construction and operations


ANSI/ASHRAE Standard 225-2020 (RA 2025) – Published Standard. Supersedes ANSI/ASHRAE Standard 225-2020. 
Methods for Performance Testing Centrifugal Refrigerant Compressors and Condensing Units 

1. Purpose
This standard provides methods of testing for the performance rating of centrifugal refrigerant compressors and condensing units. 

2. Scope
This standard applies to centrifugal refrigerant compressors and condensing units utilizing any refrigerants. This standard applies to single and multi-stage compressors with or without means of intermediate cooling. 


SPC 226P- Designated as SPC 23P on November 14, 2010

ASHRAE Standard 227P, Proposed Standard authorized January 16, 2019. Revised TPS approved June 22, 2021. 
Passive Building Design Standard 

1. Purpose 
This standard provides requirements for the design of buildings that have exceptionally low energy usage and that are durable, resilient, comfortable, and healthy. 

2. Scope

2.1 This standard is applicable to all new and existing buildings intended for human occupancy. 

2.2 This standard provides requirements for the design, construction and plans for operation of the: 

  1. building envelope, 
  2. heating and cooling equipment and systems, 
  3. ventilation systems, 
  4. service hot water systems, 
  5. interior and exterior lighting systems, and 
  6. plug and appliance loads. 

2.3 This standard does not provide requirements for the use of buildings. 

2.4 This standard does not apply to process related systems or equipment. 

2.5 This standard shall not be used to circumvent any safety, health, or environmental requirements. 


ANSI/ASHRAE Standard 228-2023 – Published Standard. This standard was approved for continuous maintenance in January 2023.
Standard Method of Evaluating Zero Net Energy and Zero Net Carbon Building Performance 

1. Purpose
This standard sets requirements for evaluating whether a building or group of buildings meets a definition of “zero net energy” or whether those buildings meet a definition of “zero net carbon”. It provides a consistent method of expressing qualifications for zero net energy and zero net carbon buildings associated with the design of new buildings and the operation of existing buildings. 

2. Scope

2.1 This standard covers: 

  1. existing buildings, new buildings, groups of buildings, or portions of buildings; 
  2. determination, including calculation methodology, and expression of the building(s) zero net energy status; 
  3. determination, including calculation methodology, and expression of the building(s) zero net carbon status; 
  4. energy and carbon emissions associated with flows across the site boundary and off-site credited flows 

2.2 The provisions of this standard do not apply to: 

  1. establishment of building gross energy performance goals or limits 
  2. design guidance or design requirements 
  3. embodied energy or carbon of building materials and systems.  

ASHRAE Standard 229P - Proposed Standard Authorized November 15, 2019. Revised TPS approved June 2022. 
Protocols for Evaluating Ruleset Application in Building Performance Models 

1. Purpose
This standard establishes tests and acceptance criteria for application of rulesets and related reporting for building performance models. 

2. Scope 
This standard applies to evaluating the implementation of rulesets associated with new or existing buildings, their systems, controls, sites, and other aspects described by the ruleset. It establishes requirements for: 

2.1 building performance modeling software 

2.2 software that evaluates building performance models and associated information to check the application of a ruleset 


ANSI/ASHRAE Standard 230-2022 Published Standard. 
The Commissioning Process Requirements for Existing Buildings and Systems 

1. Purpose
The purpose of this standard is to identify the minimum acceptable Commissioning Process (Cx) for existing buildings and systems. 

2. Scope 

2.1  This standard provides procedures, methods, and documentation requirements for each commissioning activity from planning to assessment, investigation, implementation hand-off, and initial ongoing commissioning, including the following: 

  1. Overview of Existing Building Commissioning Process (EBCx)activities  
  2. Description of minimum activities for each process step  
  3. Minimum documentation requirements for each process step 

SSPC 300 to be cognizant project committee for maintenance of Standard 230. Standard 230 on continuous maintenance. 


ANSI/ASHRAE Standard 231-2026, Published Standard. 
A Control Description Language for Building Environmental Control Sequences

1. Purpose
The purpose of this standard is to define a declarative graphical programming language for building environmental control sequences that is both human and machine readable, designed for specification, implementation through machine-to-machine translation, documentation, and simulation.

2. Scope
This standard applies to building automation systems controlling environmental systems such as mechanical systems, active facades, and lighting.


ANSI/ASHRAE/IBPSA Standard 232-2024. Published Standard.  
Common Content and Specifications for Building Data Schemas 

1. Purpose
This standard defines metaschemas (such as data types, data elements, naming conventions, and formats) to specify and validate other standard schemas for data exchange among building performance and HVAC&R software. 

2. Scope
This standard applies to data models and schemas specified in other standards for the design, operation, and performance of buildings. 
 
SSPC 232 to maintain and revise Standard 232. Standard approved for continuous maintenance in 2024. IBPSA is a cosponsor to this standard. 


ASHRAE Standard 233P – Proposed Standard authorized November 2021. 
Testing, Evaluating, and Reporting of Phase Change Materials Performance 

1. Purpose
To provide a test method to evaluate the performance of Phase Change Materials (PCMs). This standard also provides a method of reporting the performance of different phase change materials in a standardized way based on laboratory testing. 

2. Scope

2.1. This standard covers the testing and evaluation of Phase Change Materials (PCM) 
thermal and life-cycle performance. 

2.2. This standard includes: 

  1. Uniform method of testing. 
  2. Identification of testing equipment for performing such testing. 
  3. Identification of data required and calculations to be used. 
  4. Identification of reporting method to be used. 
  5. Criteria for determining the life cycle performance. 
  6. Definitions and Terminology. 

2.3. This standard does not cover thermal energy storage system-level evaluation.


ASHRAE Standard 234P - Proposed Standard authorized in June 2022.  Revised TPS approved May 2026. (185.5P was redesignated to 234P.)
Method of Testing Air Cleaning Devices and Systems with Duct-Mounted Components for Particle and Microorganism Removal or Inactivation using a Chamber with a Recirculating Duct System

1. Purpose
The standard provides a method of test for evaluating air cleaning devices and systems that contain a duct-mounted component for particle and/or microorganism removal or inactivation in a chamber with a recirculating duct system.

2. Scope

2.1 The method of test identifies particle or selected indicator microorganisms to serve as the test challenge(s) for separate tests.

2.2 This standard defines procedures for generating, sampling, and quantifying the specified test challenge(s) to calculate device or system efficacy; and describes the environmental conditions and chamber characteristics required for the method of test.

2.3 This standard covers HVAC-duct mounted air cleaning devices and air cleaning systems that require a duct-mounted component and require a chamber with a recirculating duct system.

2.4 This standard establishes minimum performance specifications for the equipment required to conduct the tests and establishes a reporting system to be applied to HVAC-duct mounted devices and systems covered herein.

2.5 This standard specifies specific particle and bioaerosol challenges that are tested separately. One challenge type is considered one test.

2.6 This standard does not address the health and safety effects of operating devices and systems covered herein.


ASHRAE Standard 235P – Propose Standard authorized February 2026.
Standard for Indoor Environmental Quality (IEQ) in Buildings 

1. Purpose
The purpose of this standard is to establish requirements for evaluating and supporting acceptable Indoor Environmental Quality (IEQ) in buildings, considering multiple environmental domains that affect occupant health, well-being, and functional performance. 

The standard is intended to provide a coherent, integrated framework that complements rather than conflicts with existing ASHRAE standards, supports design and operation decisions, and informs policy and guidance, without directly regulating health outcomes. 

2. Scope
This standard applies to buildings and addresses Indoor Environmental Quality through consideration of multiple indoor environmental factors, including but not limited to indoor air quality, thermal conditions, lighting, acoustics, and building or system characteristics that influence environmental performance. 

The standard defines requirements and evaluation principles for IEQ at the building or space level. It does not prescribe specific design solutions, medical or clinical criteria, or regulatory compliance thresholds, nor does it replace or duplicate requirements contained in existing ASHRAE standards addressing individual environmental domains. 

📌ASHRAE announces Seed Document RFP for the development of New Standard – BSR/ASHRAE Standard 235P, Indoor Environmental Quality (IEQ) in Buildings

ASHRAE is pleased to solicit proposals for the development of a New Standard – BSR/ASHRAE Standard 235P, Standard for Indoor Environmental Quality (IEQ) in Buildings to establish a comprehensive framework for evaluating and supporting acceptable IEQ across buildings. It will address multiple environmental factors – such as air quality, thermal conditions, lighting, acoustics, and building or system characteristics that influence occupant health, well-being, and performance. If you intend to submit a proposal, please notify Leigh Lain Walker via email (lwalker@ashrae.org) so that any late or additional information on the RFP may be furnished to you prior to the final bid deadline of July 27, 2026.
Click here to learn more and access the full RFP.


ASHRAE Standard 236P - Proposed Standard Authorized October 27, 2025. 
Method of Test for Control Programming Conformance with HVAC Sequences of Operation 

1. Purpose 
This standard specifies a Method of Test to verify that control programming logic conforms with the functional intent of standardized HVAC control sequences. 

2. Scope

  1. This standard applies to the programming of building automation system controllers intended to implement standardized control sequences such as are included in ASHRAE Guideline 36. 
  2. This standard defines a series of test scripts detailing test conditions for applicable control points to be evaluated against expected responses, with pass/fail criteria for each test.  
  3. This standard defines a bench-scale procedure and software tool requirements that test control programming hosted on physical controllers through BACnet network communication protocols with no physical sensors or devices involved. 
  4. This standard does not apply to programming for which test scripts have not yet been specifically included in this standard.  

ASHRAE Standard 240P –  Proposed Standard authorized February 2022. ICC is a co-sponsor to this standard. Revised TPS approved via letter ballot November 2023. 
Quantification of Life Cycle Greenhouse Gas Emissions of Buildings 

1. Purpose
The purpose of this standard is to provide a methodology to quantify and document greenhouse gas emissions associated with buildings, building systems, and building equipment, and their sites over their life cycle. 

2. Scope
This standard provides minimum requirements for the quantification of embodied and operational greenhouse gas emissions associated with buildings, and their sites.  

2.1 This standard provides minimum requirements for documentation of life cycle greenhouse gas emissions. 

2.2 This standard does not set benchmarks or establish levels of building performance. 

2.3 This standard shall not be used to circumvent any safety, health, or environmental requirements. 


ASHRAE Standard 241-2023  - Published Standard. 
Control of Infectious Aerosols 

1. Purpose

1.1 The purpose of this standard is to establish minimum requirements for control of infectious aerosols to reduce risk of disease transmission in the occupiable space in new buildings, existing buildings, and major renovations to existing buildings, including requirements for both outdoor air system and air cleaning system design, installation, commissioning, operation, and maintenance. 

1.2 This standard defines the amount of equivalent clean airflow necessary to substantially reduce the risk of disease transmission during infection risk management mode. 

2. Scope

2.1 This standard 

  1. Does not address requirements for maintaining acceptable indoor air quality 
  2. May not substantially reduce transmission risk in all situations due to the diversity of infectious agents and personal      susceptibility 
  3. Addresses only indoor long-range transmission resulting from inhalation of infectious aerosol emitted by an infector who is not in close proximity to a susceptible occupant 

2.2 This standard does not determine the conditions under which infection risk management mode should be invoked. 

2.3 No requirement in this standard shall be used to circumvent any health, safety or comfort regulations required by the authority having jurisdiction. 

SSPC 241 to maintain and revise Standard 241. Standard approved for continuous maintenance June 2023. 


ASHRAE Standard 242P,   Proposed Standard authorized January 2024.  ICC is a cosponsor to this standard (approved June 2024). 

Standard Method for Calculation of Building Operational Greenhouse Gas Emissions 

1. Purpose 
This standard provides a common methodology for the calculation of greenhouse gas (GHG) and carbon emissions of new and existing buildings. This standard provides a consistent procedure and data to be referenced by other standards that define methods of evaluation, verification, limitations, or targets for new and existing buildings.  

2. Scope

2.1 This standard covers: 

  1. calculation methodology for determination and expression of building(s) GHG and carbon emissions associated with building operations including energy use; and 
  2. calculation methodology for determination and expression of the building(s) GHG and carbon emissions associated with flows across the site boundary and off-site credited flows.  

2.2 This standard provides: 

  1. Uniform method of calculation and minimum required level of rigor 
  2. Identification of data required and calculations to be used 
  3. Identification of reporting metrics to be used 
  4. Definitions and Terminology 

2.3 This standard does not establish methods of evaluation, verification, GHG or carbon emission goals or limits, or provide design guidance or requirements for buildings. 


ASHRAE Standard 243P, Proposed Standard authorized January 2024.
Safety Standard for Transportation Refrigerating Systems 

1. Purpose
This standard specifies safe design, construction, installation, and operation of refrigerating systems for use in transportation applications. 

2. Scope

2.1 This standard establishes safeguards for life, limb, health and property and prescribes safety requirements 

2.2 The design, construction, test, installation, operation, and inspection of mechanical refrigerating systems used in transportation applications 

2.3 Modifications, including replacement of parts or components if they are not identical in function and capacity 

2.4 Substitutions of refrigerants having a different designation 

2.5 This standard applies to refrigerating systems for the following applications 

  1. On road transport of goods 
  2. Refrigerated rail units and refrigerated boxcar 
  3. Self-contained marine 
  4. Intermodal transport 
  5. Passenger buses and trains 

2.6 This standard does not apply to 

  1. Mobile air conditioning (MAC) systems within the scope of SAE J639 
  2. Refrigerating and air conditioning systems integral to ships within the scope of ASHRAE Standard 26 
  3. Any refrigerating or air conditioning system designed to be operated during air travel 
  4. Refrigerating and air conditioning systems within scope of ASHRAE Standard 15 
  5. Residential refrigerating and air conditioning systems within scope of ASHRAE Standard 15.2 

ASHRAE Standard 244P – Proposed Standard authorized June 2024. Revised TPS approved June 2026.
Development and Application of Product Category Rules for HVAC&R-related Mechanical, Electrical, and Plumbing Products

1. Purpose
This standard provides requirements and best practices for program operators seeking to develop product category rules (PCRs) for HVAC&R-related mechanical, electrical, and plumbing (MEP) products in addition to those requirements and best practices found in ISO 14025, ISO/TS 14027, ISO 21930, and EN 15804. This standard is intended to create more consistent PCRs for HVAC&R-related mechanical, electrical, and plumbing (MEP) products to yield more consistent environmental product declarations (EPDs).

2. Scope

2.1 This standard is intended for use by manufacturers, program operators, and independent verifiers participating in the preparation of life cycle assessment-based product category rules.

2.2 This standard covers HVAC&R-related Mechanical, Electrical, and Plumbing (MEP) products.

2.3 This standard addresses:

  1. creating or adopting the necessary product category rules (PCRs)
  2. updating PCRs and reassessing products as needed
  3. development of reporting requirements for EPDs for MEP

2.4 This standard does not address:

  1. performing a life cycle assessment (LCA) in accordance with the PCRs
  2. reporting the LCA results in the product claim document
  3. registering the product claim document for public access

2.5 This standard is intended to supplement ISO 14025, ISO/TS 14027, and related standards, such as ISO 21930 and EN 15804, where an existing PCR product claim is

  1. unavailable
  2. insufficient per the requirements of this standard
  3. not relevant to the specific region or application
  4. out of cycle

2.6 The scope of this standard excludes the scope of standards within the ISO 14040 family.


ASHRAE Standard 245P - Proposed Standard authorized June 2024. Revised TPS approved June 2025.
Acceptable Performance Standard for District Cooling Systems 

1. Purpose

  1. To establish minimum acceptable performance requirements of district cooling system, for siting, design, construction, and operation and maintenance of components including, plant systems, distribution networks and energy transfer stations. 
  2. To minimize emissions from district cooling plants and plant systems, conserve water resources, materials, and resources, and construction and plans for operation.

2. Scope:

This standard provides: 

2.1  Minimum energy-efficiency requirements for the design and construction, and metrics for operation and maintenance of:

    1. new district cooling systems, equipment and their components,
    2. new portions of district cooling systems and their components,
    3. new equipment or component systems specifically identified in this standard that are part of a site, and
    4. new components, distribution networks, and equipment for existing district cooling systems.

2.2 Metrics for operation and maintenance of existing district cooling systems.

2.3 Criteria for determining compliance with these requirements.

2.4 Establish minimum criteria for the design of critical components.

2.5 The provisions of this standard do not apply to:

  1. Cooling plants that do not serve more than one building
  2. Industrial focused process cooling plants that are do not supply space cooling for human comfort applications.
  3. Distributed generation of space heating and cooling.

2.6 Where specifically noted in this standard, certain other plants or elements of plants or sites shall be exempt.

2.7 This standard shall not be used to circumvent any safety, health, or environmental requirements of the final assembly.


SSPC 300 – formed July 1, 2017 to revise and maintain commissioning series standards and guidelines.
SSPC 300
to revise and maintain Standard 202, Standard 230P, Guideline 0, Guideline 0.2, Guideline 1.1, Guideline 1.2, Guideline 1.3, Guideline 1.4, Guideline 1.5,, Guideline 1.6P and Guideline 1.7P.
Commissioning


SSPC 400 – formed January 24, 2024 to revise and maintain building water systems risk management series standards and guidelines.

SSPC 400 to maintain Guideline 12, Standard 188, and Standard 514.
Risk Management for Building Water Systems


ANSI/ASHRAE Standard 514-2023 Published Standard. 
Risk Management for Building Water Systems: Physical, Chemical, and Microbial Hazards 

1. Purpose 
The purpose of this standard is to establish minimum requirements to reduce illness and injury from physical, chemical, and microbial hazards from water systems in buildings. 

2. Scope

2.1.  This standard applies to the design, construction, commissioning, operation, maintenance, repair, replacement, and expansion of new and existing building water systems (potable and non-potable) and components. 

2.2.  This standard applies to human-occupied commercial, institutional, multiunit residential, assembly, educational, and industrial buildings. This standard does not include single-family residential buildings. 

2.3. This standard is intended for owners, authorities having jurisdiction, and those involved in the design, construction, management, installation, commissioning, operation, maintenance, and service of centralized building water systems and components. 

SSPC 400 is the cognizant project committee for maintenance of Standard 514 (approved January 2024). 

Close